AEROCONNECT
Installation
Fonctionnement
Mise en service
Maintenance
Installation
Operation
Commissioning
Maintenance
Montage-
Betriebs-und
Wartungs-
Anweisung
1er de couv.qxd 21/11/2008 13:44 Page 1

EN - 2
Contents
Sections Page
General......................................................................................................................
.
3
Board functions..........................................................................................
.
3
Limits of use ...............................................................................................
.
3
Compatible equipment...............................................................................
.
3
Control console........................................................................................................
.
4
Description of control console .................................................................
.
4
Display ........................................................................................................
.
5
Menu tree structure....................................................................................
.
5
Menu list .......................................................................................
.
5
Structure of the menus................................................................
.
5
Navigation...................................................................................................
.
6
Board functions: description ..................................................................................
.
7
Control choices ..........................................................................................
.
7
On/Off control (stages) ................................................................
.
7
Speed control ...............................................................................
.
7
Mixed control................................................................................
.
8
Automatic operation control .....................................................................
.
8
Manual override..........................................................................................
.
8
Two setpoints .............................................................................................
.
8
Stage runtime balancing............................................................................
.
8
Spray ...........................................................................................................
.
8
Free cooling................................................................................................
.
9
Link with CIAT chiller.................................................................................
.
9
BMS link......................................................................................................
.
9
Options......................................................................................................................
.
10
Relay boards...............................................................................................
.
10
Remote control console ............................................................................
.
10
Electrical connections .............................................................................................
.
10
General........................................................................................................
.
10
Connection diagram...................................................................................
.
11
Board connections.....................................................................................
.
13
Dry cooler configuration..........................................................................................
.
16
Configurations............................................................................................
.
16
Commissioning and configuration ...........................................................
.
16
Information available while the unit is running .......................................
.
18
Factory-set parameters..............................................................................
.
19
Condenser configuration.........................................................................................
.
20
Configurations............................................................................................
.
20
Commissioning and configuration ...........................................................
.
20
Information available while the unit is running .......................................
.
21
Factory-set parameters..............................................................................
.
23
BMS communication protocol ................................................................................
.
24
Communication interface ..........................................................................
.
24
Transmission mode ...................................................................................
.
24
Remote signalling register ........................................................................
.
24
Remote alarm register ...............................................................................
.
25
Remote measurement register..................................................................
.
25
Fault memory..............................................................................................
.
26
Counters .....................................................................................................
.
26
Remote configuration register ..................................................................
.
27
Functions 1 and 2.......................................................................................
.
29
Remote alarm and operating status ...........................................
.
29
Remote control.............................................................................
.
29
Remote diagnostics .....................................................................
.
29
Event counter ...............................................................................
.
29
Glossary....................................................................................................................
.
30

EN - 3
General
Board functions Integrated in an electrical panel, this board performs the following functions:
•temperature or pressure control,
•operation parameter monitoring,
•communication with CIAT chillers,
•diagnostics and fault storage,
•communication with the remote control console, ancillary boards,
and customer BMS (bus).
Limits of use Ambient air:
During operation: min./max. temperatures = -25°C/40°C
Stored: min./max. temperatures = -40°C/80°C
Single-phase fluid: min./max. adjustment temperature = 5/90°C (up to 150°C
optional)
Refrigerant: min./max. set pressure: 5/45 bar
Electrical Board supply voltage: 230 V
Compatible
equipment
The AeroConnect board is used to control the dry coolers and air-cooled
condensers
Possible configurations and identification conventions:
Flatbed or V-type coils
Flatbed
V-type
Unit with one or two fan lines
Unit with one or two coils
Unit with one or two circuits
Line 1 Line 2
Coil 2
Circuit 1 Circuit 2
+6%
-10%
Line 1 Line 2
Coil 1
Coil 1 Coil 2

EN - 4
Control console
Description of
control console
(local and remote)
Letter Illustration Function
A
Power button
LED Meaning
Off Machine off
On Machine on
Flashing Machine shut off by automatic control
B
LED on = system energised.
C LED flashing = fault
D
Press this button to select setpoint 1 or 2.
The corresponding LED lights up.
E
Press this button to activate or deactivate the fan manual override.
Flashing LED = manual override on.
F Display screen.
G
Status of the fan stages:
•Top row = Fan line 1
•Bottom row = Fan line 2
LED Meaning
Off Stage off
On Stage on
Flashing Stage fault
H
Measurement faults
LED No. Meaning
1 Circuit 1 coil 1
2 Circuit 2 coil 1
3 Circuit 1 coil 2
4 Circuit 2 coil 2
5 Outdoor temperature
I
Menu navigation buttons: see the Navigation section.
J
Reset button for certain faults.
Does not work with the remote control console.
A
B
C
D
E
F
HG
I
J

EN - 5
Control console (continued)
Display
Two-line LCD – Displays system readings and controls.
Menu tree
structure
Menu list
There are seven main menus for controlling the system.
Each menu contains different parameters.
MENUS Description
1-Setpoints Change setpoints - Menu not displayed if the unit is
run with a CIAT chiller.
2-Machine status Default menu. Contains read-only information on the
operation of the machine.
3-Measured values Displays read-only temperature and pressure values.
4-Machine parameters Machine configuration parameters.
5-Settings parameters Parameters set for the control and various options.
6-Reading parameters Displays the status of the inputs, outputs, counters,
etc. (read-only).
7-Fault memory Shows the nine most recent faults (read-only).
Structure
of the menus
All information in the menus is displayed in a tree structure.
This tree structure is split into three levels, as shown by the diagram below.
PARAMETRES
-Param
de réglage
100 Langue
Français
P203 ---------------
-------
4-Param
machine
3-Valeurs
mesurees
2-Etat
machine
1-Consigne
6-Param de
Lecture
7-Memoire
defauts
MENUS MODIFICATION DES
VALEURS
P100 Langue
----------
P100 Langue
Français
MENUS
1-Setpoint
2-Machine
status
3-Measured
values
4-Machine
parameters
5-Settings
parameters
6-Read
parameters
7-Fault
memory
P100 Language
En
g
lish
P100 Language
En
g
lish
P100 Language
-------------
PARAMETERS CHANGING OF
VALUES

EN - 6
Control console (continued)
Navigation
Four buttons are available for
navigating through the menus:
Navigating through
the menus
Each button is described in the table below:
ÎPress these buttons firmly!
Button Level
Menus
Level
Parameters
Level
Values
Back to
Menus level
Back to
Parameters level
Select menu Select parameter
Confirm value and
go back to
parameters
Lower the
parameter value or
scroll through the
values
Scroll
through the
parameters Raise the
parameter value or
scroll through the
values
Scroll
through the
menus
Pressing and holding the ‘+’ or ‘-‘ buttons
will cause the display to scroll faster.
When the machine is turned on, the "machine off – on/off" menu
[2-Machine status] screen appears. Press to go back to the menu
list.
If the control console is not used for one hour, the [2-Machine status]
menu reappears. Press to go back to the menu list.
Arrows on the right of the screen indicate that additional information is
available. To see this information, press the ‘+’ or ‘-‘ buttons.
Example
The active line in a menu is shown by a flashing box to the left of the menu
number.
Example
COIL PRESSURE ↑
20.7 B↓
▮100 LANGUAGE
ENGLISH

EN - 7
Board functions: descriptions
Control
choices
Three types of control are possible. Refer to your order acknowledgement
to see which type you have selected:
•On/Off: Cascade control by activation of fan stages.
•Speed control: Fan speed control.
•Mixed: Speed control on stage 1, cascade control for the following
stages.
On/Off control Used for cascade control of fan stages:
The diagram below illustrates this type of control:
Speed control
With a speed drive
(option)
Used to adjust the speed of all the fans.
The diagram below illustrates this type of control:
EXEMPLE POUR CIRCUIT 1
BATTERIE 1
A121 ou A122 Consigne
2
3
4
5
Mesure
6
A150 : Hystérésis étage 1
A152 : Hystérésis étage 2
A154 : Hystérésis étage 3
A156 : Hystérésis étage 4
A 158 : Hystérésis étage 5
A160 : Hystérésis étage 6
A159 : Ǝtage 6
A157 : Ǝtage 5
A155 : Ǝta
g
e 4
A151 : Ǝtage 2
A153 : Ǝtage 3
E
T
A
G
E
D
E
R
E
G
U
L
A
T
I
O
N
1
EXAMPLE FOR CIRCUIT 1
A 160: Stage 6 hysteresis
A 158: Stage 5 hysteresis
A 156: Stage 4 hysteresis
A 154: Stage 3 hysteresis
A 152: Stage 2 hysteresis
A 150: Stage 1 hysteresis
Stage 6
stage 5
stage 4
stage 3
stage 2
Measurement
A121 or A122 Setpoint
C
O
N
T
R
O
L
S
T
A
G
E
Tension
Mesure
A121 + A150
(A150=hystérésis)
0V
10V
EXEMPLE BATTERIE 1 CIRCUIT 1
CONSIGNE 1
Voltage
Measurement
(A150=hysteresis)
EXAMPLE FOR COIL 1, CIRCUIT 1,
SETPOINT 1

EN - 8
Board functions: descriptions (continued)
Control
choices
(continued)
Mixed control
With a speed drive
(option)
Used to adjust the speed on stage 1. Cascade control is used for the other
fan stages.
The diagram below illustrates this type of control:
Automatic
machine operation
control
Used to remotely authorise or prohibit the operation of the machine.
The machine is on when the contact is closed.
Manual
override
Used to turn on all the fans. The machine is in override mode when the
contact is closed.
Manual override can be activated and deactivated either directly on the unit or
remotely.
Two setpoints Used, for example, for summer/winter or day/night operation. Each circuit can
have up to two control setpoints. These setpoints can be switched via the dry
contact (On/Off), the console or over a BMS.
Stage runtime
balancing
The running time of each fan stage is balanced by a time counter.
Spray
(units with spray
ducts)
Used to increase the efficiency of the AeroConnect by spraying very fine
droplets of water into the ambient air to cool it through evaporation.
Two options:
- Optimised water consumption: the water spray does not start until all the
stages are on and the setpoint is exceeded.
- Optimised electricity consumption: the water spray does not come on until
the outdoor temperature reaches a preset value.
A121
Consigne
A121 + A150
(A150=hystérésis
)
Mesure
55% 65% 75% 85%
4°étage
1°étage
2°étage
5%
EXEMPLE POUR CIRCUIT 1
BATTERIE 1
5°étage
6°étage
3°étage
95%15% 25% 35% 45%
EXAMPLE FOR CIRCUIT 1
Measurement
Setpoint (A150=hysteresis)
1st stage
2nd stage
3rd sta
g
e
4th sta
g
e
5th sta
g
e
6th sta
g
e

EN - 9
Board functions: descriptions (continued)
Free cooling During free cooling, the dry cooler is run with a CIAT chiller. Both units are
controlled by the board.
The three-way valve can be controlled by the board provided the maximum
current is 3 A and the maximum voltage is 230 V. Refer to the chiller pump
curve to size the valve.
Link with CIAT
chiller
The following information is exchanged between the dry cooler (DC) or the
condenser (CO) and the chiller (CH):
CH > (DC / CO) (DC / CO) > CH
•Chiller on/off •DC or CO on/off
•Setpoint (CO) •Free cooling
•Pressure value (CO) •Fan stage fault
•Sensor fault
BMS link
With the exception of the language, control type (local, remote),
communication mode and bus number, all the parameters can be accessed
in read and write modes.
P
Dry cooler (DC)
Chiller (CH)
CH onlyDRY COOLER + CHILLER
DC only
Selection
temperature
Process
return
tem
p
.
Text

EN - 10
Options
Relay boards
Main board
Additional board
The boards must be installed in a cabinet.
It has dry contacts for displaying three parameters: unit operation, sensor faults
and fan stage faults.
For units with a motherboard and a daughterboard. It has dry contacts for
displaying two parameters: sensor faults and fan stage faults.
Remote control
console
Console mounting
dimensions (mm)
Used to view and control the operation of the unit from a distance.
Maximum distance of 1000 m.
Must be installed indoors.
Electrical connections
General
Communication bus
connection
On/Off input
connections
(automatic operation
control, manual override,
changeover of two
setpoints)
Analogue output
connections
On/Off output
connections
(General operation signal,
general fault signal)
Single-pair shielded cable required. Capacitance between wire and shield:
120 pF/m – Resistance of 56 Ω/km.
Examples: Filotex FMA 2P or Filotex IBM 7 362 211.
The shield must be connected at each end to the 0 V line (terminal 3 on J13 or
J12) on the units and the earth to the PLC end. The shielding braid must be as
short as possible (2 cm max.).
The cables must be routed at a distance of at least 30 cm from the power
cables. However, if a power cable intersects with a computer cable, they must
do so at a right angle.
For distances of less than 30 metres, use a shielded cable and keep it at least
30 cm away cm from all lines that could generate interference.
For distances of over 30 metres, install a relay for each input near the board.
Signal output of 0/10 V. Minimum VFD input impedance of 1 kΩ. Shielded cable
connections. Shield connected at both ends to earth. Minimum cross-section of
0.32 mm2(1.5 mm2 max.).
Potential-free dry contacts. Maximum current of 10 A (AC1 load), minimum of
5 mA. Voltage of 12 to 230 V AC. Maximum connection cross-section of
2.5 mm2.
Height = 55

EN - 11
Electrical connections (continued)
Connection
diagram
Link with CIAT chiller
BMS link
B (-)
A(+)
Position du commutateur de
résistance de fin de ligne W1
off on Position W1 si aéroconnect est le
dernier a
pp
areil de la liaison
Position W1 si aéroconnect n’est
p
as le dernier a
pp
areil de la liaison
Carte AEROCONNECT
Pu
p
itre local
A
PPAREIL
1
2
3
J13 W1
J11
Carte
Groupe de froid
1
2
3 J12 Connect
JA11 XtraConnect
UNIT
A
EROCONNECT
Local console
Board
Chiller
Position of line termination
resistance switch W1
Position of W1 if AeroConnect is
last unit in link
Position of W1 if AeroConnect is
not last unit in link
B
(
-
)
A
(
+
)
RS485 2 fils
Longueur max
1000m
Position du commutateur de
résistance de fin de ligne W1
off on
Position W1 sur le dernier appareil
Position W1 sur les autres appareils
Carte AEROCONNECT
P
up
itr
e
l
oca
l
A
PPAREIL N°1
1 2 3
J13 W1
J11
Carte AEROCONNECT
Pu
p
itre local
A
PPAREIL N°X
1 2 3
J13 W1
J11
J13 borne 1
J13 borne 2
J13 borne 3
APPAREIL
N°2
J13 borne 1
J13 borne 2
J13 borne 3
APPAREIL
N°
(
X-1
)
Automate ou PC
sortie RS485
UNIT No. 1
A
EROCONNECT board
PLC or PC
RS485 output
Local console
UNIT NO.
2
UNIT No.
(X-1)
2-wire RS485
(Max length:
1000 m)
J13 terminal 3
J13 terminal 1
J13 terminal 2
J13 terminal 3
J13 terminal 1
J13 terminal 2
UNIT No. X
A
EROCONNECT boa
r
d
Local console Position of line termination
resistance switch W1
Position of W1 on last unit
Position of W1 on the other units

EN - 12
Electrical connections (continued)
Connection
diagram
Free Cooling
Relay boards
Remote control
console
Pu
p
itre dé
p
orté
(
O
p
tion
)
Carte AEROCONNECT
Pu
p
itre local
A
PPAREIL
1
2
3
J12
J11
B
(
-
)
A
(
+
)
Alimentation
230V 50Hz
Ph
N
T
J1
0V
P
A
éroréfrigérant
Carte
Connect J12
Xtraconnect JA11
Carte
A
EROCONNECT
123
J13 W1
1
3
14
15
J10
Groupe de froid
B (-)
A
(
+
)
1 2 3
1
2
3
Chiller
Board
AEROCONNECT board
Dry cooler
Carte AEROCONNECT
Pu
p
itre local
A
PPAREIL
1
2
3
J12
J11
Pu
p
itre dé
p
orté
(
O
p
tion
)
B
(
-
)
A
(
+
)
Alimentation
230V 50Hz
Ph
N
T
J1
0V
Position du switch si la carte relais est
avec l’option pupitre déporté
Position du switch si la carte relais est
sans l’option pupitre déporté,
(Raccordement sur aéroconnect)
DETAIL
1
2
3
J5
3
2
1
J1
Carte relais
de base
(Option)
Carte relais
additionnelle
(
O
p
tion
)
Alimentation
230V 50Hz
Ph
N
T
Voir
détail
UNIT
AEROCONNECT board
Local console Additional
relay
board
(option)
Basic relay
board
(option)
Remote control console (option)
230 V / 50 Hz
supply 230 V / 50 Hz
supply
INSET
Position of switch if relay board with
remote control console option
Position of switch if relay board without
remote control console option,
(
Connection to AeroConnect
)
UNIT
AEROCONNECT board
230 V / 50 Hz
supply
230 V / 50 Hz
supply
Local console
Remote control console (option)
See
inset
E
N
L
E
N
L
E
N
L

EN - 13
Electrical connections (continued)
Board connections
Motherboard
The structure of the motherboard is illustrated in the diagram below:
CONNECTOR /
TERMINALS DESCRIPTION DIRECTION OF ACTION
On/Off inputs
J6 terms. 1-2 Automatic operation
control
The machine stops when the
contact opens
J6 terms. 2-3 Fan manual override The fans turn on when the
contact closes
J6 terms. 4-5 Setpoint 1 / Setpoint 2
selection
Setpoint 2 is enabled when
the contact is closed
On/Off outputs
J7 terms. 1-2 Operation signal The contact closes when the
unit is on
J7 terms. 3-4 Fault signal The contact opens when a
fault appears
J8 terms. 1-2 Chiller in free cooling
mode
The authorisation is sent to
the chiller when the contact
closes
J10 terms. 4-5 Free cooling three-way
valve control See wiring diagram
Analogue inputs
J2 terms. 1-2 Temperature sensor, coil 1, circuit 1
J2 terms. 2-3 Temperature sensor, coil 1, circuit 2
J3 terms. 1-2 Outdoor temperature sensor.
J3 terms. 2-3 Temperature sensor, coil 2, circuit 1
J3 terms. 4-5 Temperature sensor, coil 2, circuit 2
J12 terms. 1-2-3
Bus power supply connected by shielded cable to J1 on
relay board or J1 on remote control console (terminal 1 to
terminal 1, terminal 2 to terminal 2 and the shield to
terminals 3).
J13 terms. 1-2-3
Bus power supply connected by shielded cable to J12 on
the CONNECT board, or JA11 on the XTRACONNECT
board (terminal 1 to terminal 1, terminal 2 to terminal 2
and the shield to terminals 3) or the customer BMS.
Memory

EN - 14
Electrical connections (continued)
Board connections
Basic relay board
To be installed by the customer in his main electrical cabinet.
J2J5
J1
Mémoire
Cd
J3
J4
CONNECTOR /
TERMINALS DESCRIPTION DIRECTION OF
ACTION
J1 terms. 1-2-3
Bus power supply connected by shielded cable to J12
on AeroConnect board (terminal 1 to terminal 1, terminal
2 to terminal 2 and the shield to terminals 3).
J5 terms. 1-2-3 Single-phase 230 V power supply.
(L - N T)
Term. 1 Neutral
Term. 2 Live
Term. 3 Earth
J2 terms. 1-2 Unit running
J2 terms. 3-4 Sensor fault, coil 1, circuit 1
J2 terms. 5-6 Sensor fault, coil 2, circuit 1
J2 terms. 7-8 Fan fault, stage 1 / Fan fault,
stage 1, line 1
J2 terms. 9-10 Fan fault, stage 2 / Fan fault,
stage 2, line 1
J2 terms. 11-12 Fan fault, stage 3 / fan fault,
stage 3, line 1
J2 terms. 13-14 Fan fault, stage 4 / fan fault,
stage 4, line 1
J2 terms. 15-16 Fan fault, stage 5 / fan fault,
stage 5, line 1
J2 terms. 17-18 Fan fault, stage 6 / fan fault,
stage 6, line 1
The contacts are
closed when the
unit is running
without any
faults.
Memory

EN - 15
Electrical connections (continued)
Board connections
Additional relay board
Its dry contacts allow the following parameters to be viewed from a distance:
To be installed on the main board by the customer.
CONNECTOR /
TERMINALS DESCRIPTION DIRECTION OF
ACTION
J8 terms. 19-20 Sensor fault, coil 1, circuit 2
J8 terms. 21-22 Sensor fault, coil 2, circuit 2
J8 terms. 23-24 Fan fault, stage 1, line 2
J8 terms. 25-26 Fan fault, stage 2, line 2
J8 terms. 27-28 Fan fault, stage 3, line 2
J8 terms. 29-30 Fan fault, stage 4, line 2
J8 terms. 31-32 Fan fault, stage 5, line 2
J8 terms. 33-34 Fan fault, stage 6, line 2
The contacts are
closed when the
unit is running
without any
faults.
J2J5
Mémoire
Cd
J3
J4
J8
Memory

EN - 16
DRY COOLER configuration
Configurations
Flatbed unit
V-type unit
Application: dry cooler with one or two coils
Commissioning
and configuration
nTurning on the unit:
The screen displays "machine off - on/off" in the [2-Machine status] menu
Press ESC to go back to the menu list.
oMain parameters to be set: select the [5-Settings parameters] menu.
For information on navigating, go to the Control console / Navigation section.
Parameter
No. Description Default
values Display conditions
Menu 5: Settings parameters
A100 Language FR
A103 Control mode: local or remote local
A104 Communication mode (baud) 9600 BMS
A105 Bus number 1 BMS
A110 Stage runtime balancing yes Control = On/Off (stages) or
mixed
A111 Free cooling no V-type or 1-coil unit/flatbed
unit without spray
A112
Selection air temperature
The parameter is disabled if set to a value of
less than 5. Press to re-enable it.
10
Free cooling
A113 Optimisation of water or electricity
consumption
Water
optimisation
Spray
A116 Link with CIAT chiller yes
A120 No. of setpoints per coil 1
Coil 2
Coil 1
(Forced draught)
Coil 2
Coil 1
(Induced draught)

EN - 17
DRY COOLER configuration (continued)
Parameter
No.
Default values Default
values Display conditions
Setpoint 1 V-type or 1-coil unit/flatbed
unit
A121
Setpoint 1, coil 1
60°C
2 coils + flatbed unit
Setpoint 2 2 setpoints + V-type or 1-coil
unit/flatbed unit
A122
Setpoint 2, coil 1
50°C
2 setpoints + 2 coils/flatbed
unit
A125 Setpoint 1, coil 2 60°C 2 coils/flatbed unit
A126 Setpoint 2, coil 2 50°C 2 setpoints + 2 coils/flatbed
unit
Stage 1 hysteresis: 1 to 20°C V-type or 1-coil unit/flatbed
unit
A150
Stage 1 hysteresis, coil 1: 1 to 20°C
5°C
2 coils/flatbed unit
Difference between stages 1 and 2:
1 to 5°C
Control = On/Off + No. of
stages ≥2 + V-type or 1-coil
unit/flatbed unit
A151
Difference between stages 1 and 2 of
coil 1: 1 to 5°C
2°C
Control = On/Off + No. of
stages ≥2 +2 coils/flatbed
unit
Hysteresis of stages 2, 3, 4, 5 or 6:
1 to 10°C
Delta of stages 2, 3, 4, 5 or 6: 1 to 5°C
Control = On/Off + based on
No. of stages + V-type or
1-coil unit/flatbed unit
A152
to A160 Hysteresis of stages 2, 3, 4, 5 and 6 of
coil 1: 1 to 10°C
Delta of stages 2, 3, 4, 5 and 6 of coil 1: 1
to 5°C
5°C
Control = On/Off + based on
No. of stages +2 coils/flatbed
unit
A172 Stage 1 hysteresis, coil 2: 1 to 20°C 5°C 2 coils/flatbed unit
A173
Difference between stages 1 and 2 of
coil 2: 1 to 5°C 2°C
Control = On/Off + No. of
stages ≥2 +2 coils/flatbed
unit
A174
to A182
Hysteresis of stages 2, 3, 4, 5 and 6 of
coil 2: 1 to 10°C
Delta of stages 2, 3, 4, 5 and 6 of coil 2:
1 to 5°C
Control = On/Off + based on
No. of stages +2 coils/flatbed
unit
A199 Outdoor spray temperature 35°C Spray / elec. optimisation
Spray stage difference Spray / water optimisation +
V-type or 1-coil unit/flatbed
unit
A200
Spray stage difference, coil 1
2°C
Spray / water optimisation +
2 coils/flatbed unit
A202 Spray stage difference, coil 2 2°C Spray / water optimisation +
2 coils/flatbed unit
pTurning on the unit: Power button
To change the setpoint values rapidly: go directly to the [1- Setpoint] menu.
Not available in free cooling mode
with CIAT chillers

EN - 18
DRY COOLER configuration (continued)
Information
available while the
unit is running
[2-Machine status] menu: appears if the control console is not used for one hour.
Fault Information
No faults Setpoint and measurement values displayed.
Sensor fault The general fault LED and measurement fault LED
flash and a message appears stating which sensor is
faulty and the terminal references
Fan fault The general fault LED and stage status LED flash and
a message appears stating which stage is faulty
[3-Measured values] menu:
Parameter Description Display conditions
Outdoor temperature Value displayed Free cooling or spray
Coil temperature Value displayed V-type or 1-coil unit/
Flatbed unit
Coil 1 temperature Value displayed 2 coils/flatbed unit
Coil 2 temperature Value displayed 2 coils/flatbed unit
[6-Reading parameters] menu:
Parameter
No. Description Display conditions
A250 LED test: press Enter to check the operation
of the LEDs
A252 Outdoor air temperature Free cooling or spray
A253 Value of coil 1 setpoint
A255 Value of coil 2 setpoint 2 coils/flatbed unit
A257 Value of coil 1 temperature
A261 Value of coil 2 temperature 2 coils/flatbed unit
A270 to
A275
Running time of each stage
A299 Spray time Spray
A300 Free cooling time Free cooling
A400 to
A421
Status (open or closed) of the logic inputs on
the board
A430 to
A451
Status (open or closed) of the logic outputs
on the board
A460 Fan speed in % Control = mixed or speed
control
A555 CPU board version No.
A556 Control console version No.
A557 Daughter board version No.
The [7-Fault memory] menu contains the nine most recent faults on the fan
stages or outdoor temperature sensors.
To scroll through the faults, press .

EN - 19
DRY COOLER configuration (continued)
Factory-set
parameters
[4-Machine
parameters] menu
The [4-Machine parameters] menu contains the parameters used to configure
the machine. They were set in the factory and are locked. The symbol
appears at the top left of the screen.
In certain rare cases (such as adding the spray function) it may be necessary to
update a parameter. The parameters may be unlocked by changing parameter
A99. However, do not modify any parameters other than those that require
changing.
Parameter
No.
Parameter description Display condition
A01 Unit type (flatbed or V-coil)
Number of coils (1 or 2) Flatbed unit
A02 Parallel coil (yes) V-type unit
A03 Coil type 1 (1 LP or HT water
circuit)
A05 Coil type 2 (1 LP or HT water
circuit) 2 coils/flatbed unit
A07 Control type: On/Off (stages),
speed control or mixed
A08 Number of stages (1 to 6) Control = On/Off or
mixed
A10 Spray (yes or no)
A99 Lock parameters (yes)

EN - 20
CONDENSER configuration
Configurations
Flatbed unit
V-type unit
Application: condenser with one or two refrigerant circuits
Commissioning
and configuration
nTurning on the unit:
The screen displays "machine off - on/off" in the [2-Machine status] menu.
Press ESC to go back to the menu list.
oMain parameters to be set: select the [5-Settings parameters] menu.
For information on navigating, go to the Control console / Navigation section.
Parameter
No. Description Default
values Display conditions
Menu 5: Settings parameters
A100 Language FR
A103 Control mode: local or remote local
A104 Communication mode (baud) 9600 BMS
A105 Bus number 1 BMS
A110 Stage runtime balancing yes Control = On/Off (stages) or mixed
A113 Optimisation of water or electricity
consumption
Water
optimisation
Spray
A116 Link with CIAT chiller yes
A120 No. of setpoints per circuit or coil 1
A121 Setpoint 1, circuit or coil 1 12 bar
A122 Setpoint 2, circuit or coil 1 12 bar 2 setpoints
A123 Setpoint 1, circuit 2 2 refrigerant circuits + flatbed unit
or
A125 Setpoint 1, coil 2
12 bar
V-type unit
A124 Setpoint 2, circuit 2 2 setpoints & 2 refrigerant circ. +
flatbed unit
or
A126 Setpoint 2, coil 2
12 bar
2 setpoints + V-type unit
Not available for CIAT chillers
Circuit 1 Circuit 2
Line 1 Line 2
Coil 1 Coil 2
Line 1 Line 2
2 refrigerant circuits
Circuit 1
Circuit 2
1 refrigerant
circuit
Table of contents
Other CIAT Control Panel manuals
Popular Control Panel manuals by other brands

Global
Global JUNIOR V4-L Installation & commissioning manual

Global
Global JUNIOR V4 Installation & commissioning manual

Bosch
Bosch ICP-CC488 Quick reference guide

Side-Power
Side-Power S-link PJC-212 Installation and user manual

Digital Monitoring Products
Digital Monitoring Products COMMAND PROCESSOR XR500 installation guide

Siemens
Siemens MKB-1 operating instructions