Digital Monitoring Products XR500/XR500N Installation Guide
4
INTRODUCTION
3.2 Wiring Diagram
The XR500/XR500N system below shows some of the accessory modules you can connect for use in various
applications. A brief description of each module follows in section 3.4.
Heat detectors, pull
stations, or any other
contact devices listed
for Fire Protective
Signaling can be
connected to zones
9 and 10.
Zones 9 and 10 and
Model 715 compatibility
identifier: A
Maximum operating
range: 9.8 VDC to
14.0 VDC.
Class B (Style A).
See section 11.2 in the XR500 Installation
Guide (LT-0681) for a complete list of
approved 2-wire smoke detectors for zones
9, 10, and 715 Zone Expansion Module zones.
See LT-0164 for a list of approved 4-wire
smoke detectors and power supervision
relays.
WARNING: Incorrect connections may cause damage to the unit.
* For UL installations, total current combined from Auxiliary
(terminals 7, 11, 25, and 27) and Bell Power (terminal 5) cannnot
exceed:
1.3 Amp with 50 VA transformer, 1.0 Amp Max for Auxiliary Power
1.9 Amp with 56 VA transformer, 1.0 Amp Max for Auxiliary Power and
1.5 Amp Max for Bell
DMP Transformers
Model 327
16.5 VAC 50 VA
Class 2 Plug-in.
Model 322
16 VAC 56 VA
Class 2 Wire-in.
Secondary Power Supply
1.0 Amps Max. charging
current. Use only 12 VDC
rechargeable batteries.
DMP Models 365, 366, 367,
368, or 369. Replace
batteries every 3 to 5 years.
* Bell
12 VDC nominal
Minimum cutoff time is
5 minutes.
1.5 Amp Max
Keypads
Model 690
72mA at 8 to 14.5 VDC.
Models 790 and 791
75mA at 8 to 14.5 VDC.
Model 793
108mA at 8 to 14.5 VDC.
Model 630F
60mA at 8 to 14.5 VDC.
* Auxiliary Power
Total current combined from
terminals 7, 11, 25, and 27
1.5 Amp Max
UL Listed Resistors
1.0k Ohm - DMP Model 311
3.3k Ohm - DMP Model 309
10K Ohm - DMP Model 308
For UL Grade A burglary
applications use Ademco
Model AB12M bell and
bell housing.
Front and Rear
tamper protection
included with
Model 350A
Attack Resistant
Enclosure.
Bell cutoff time
range is 5 to 99
minutes marchtime
and non-coded.
AC
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18 199202122232425262728
+B BELL GND SMK GNDRED YEL GRN BLK Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8 Z9+ Z9– Z10+ Z10–AC –B GND GND GNDGND
K6 K7
Output 1 Output 2
J3
Phone Line
J10
J22
LX-Bus
Battery
Start
J23
J21
RS-232
Power
LED
J8
PROG
J4
Tamper
J16
Reset
Out1 Out2
Outputs 3-6
J11
3
4
5
6
J2
¼"
J1
Ethernet
R
L
X
Power LED
Link LED
OVC
XR500/XR500N
Command Processor™
Panel
POWER
ARMED
1k Ohm 1k Ohm 1k Ohm
DISARM
ARM
3.3k Ohm 3.3k Ohm 3.3k Ohm 3.3k Ohm
1k Ohm
Form C Relays (J2)
Output Color Code–Model 431 Harness
Output 1 N/C Violet
Output 1 Com Gray
Output 1 N/O Orange
Output 2 N/C VioletWhite
Output 2 Com White/Gray
Output 2 N/O Orange/White
Annunciator Outputs (J11)
Output Color Code
Output 3 Red
Output 4 Yellow
Output 5 Green
Output 6 Black
AC Wiring must be in conduit and exit
out the left side of the enclosure.
Wiring on terminals 5 through 22 must
exit right and maintain 1/4" separation
from the AC and battery positive wiring.
Front
Tamper
Rear
Tamper
s
16 to 18 gauge wire
Maximum AC Wire distance
with 16 gauge wire: 70 feet
with 18 gauge wire: 40 feet
RED
BLACK
Cold Water
Pipe Earth
Ground
Bell
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
3.3k
Ohm
Resistor
3.3k
Ohm
Resistor
Zone Expander
Model 715
7mA @ 12 VDC
Models 715-8, 715-16
20mA @ 12 VDC
Smoke
Detector
Use UL Listed Power
Supervision Relay
rated at 12 VDC.
1k Ohm
s
= Supervised Circuit
Zone
9
Zone
10
22 gauge minimum
22 gauge minimum
22 gauge minimum
22 gauge minimum
RED
YELLOW
GREEN
BLACK
1k Ohm 1k Ohm 1k Ohm
Zone Expander
Model 714
7mA @ 12 VDC
Models 714-8, 714-16
20mA @ 12 VDC
RED
YELLOW
GREEN
BLACK
RED
s
s
s
s s s s s
s
For UL installations, the Model
327 plug-in transformers shall
be installed in a DMP Model
ES501 enclosure. The plug-in
transformer shall plug into a
120 VAC 60 Hz outlet not
controlled by a switch and all
16 to 18 gauge wire
shall run
through conduit.
s
s
s
S S S S S S S S
S S S S
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
S SS SS SS S
1k Ohm
Zone Expander
(up to 8 zones)
Model 712-8
19mA @ 12
VDC
S S
Zone
Expander
Model 711
7mA @ 12
VDC
10k
Ohm
s
Keyswitch Arming
can be connected
to any zone. See
LT-0681 Section 10.4.
ssss s
s s s
TYPES OF SERVICE
Central Station DACT service may be
provided. See sections 29.4.
Suitable for Remote Station PPU DACT
Service. See sections 29.7. Suitable for
manual fire alarm, automatic fire alarm,
sprinkler supervisory, or water flow
alarm.
Suitable for Grade AA High Line
Encrypted Central Station with NET
communication. See section 23.8.
Grade B may be provided with dialer
communication and DMP 350A
Enclosure. See section 23.6.
Suitable for Bank Safe and Vault
Service with 350A Enclosure. See
section 26.6. Suitable for Household
Fire and Grade A Household Burglary.
Suitable for Grade A Local, Police
Station Connect, Mercantile, and
Proprietary with dialer direct
communication and 350A Enclosure.
See sections 23.3, 23.5, and 23.6.
Suitable for Proprietary, PPU, other
technologies, (iCOM – XR500 only),
local.
NFPA 72
This equipment should be installed in accordance with Chapter 11 of the National
Fire Alarm Code, ANSI/NFPA 72-2002, (National Fire Protection Association,
Batterymarch Park, Quincy, MA 02269). Printed information describing proper
installation, operation, testing, maintenance, evacuation planning, and repair
service is to be provided with this equipment.
POWER LIMITED
All circuits on the Model XR500/XR500N comply with the requirements for
inherent power limitation and are Class 2 except the red battery wire and AC
terminals.
NFPA 72 OPERATING INSTRUCTIONS
The operating instructions found on LT-0352 1/04
must be located adjacent to the control unit or
keypad.
HOUSEHOLD FIRE WARNING
UL recognized limited energy cable must be used
for connection of all initiating, indicating, and
supplementary devices.
WARNING
THIS UNIT MAY BE PROGRAMMED TO USE AN ALARM VERIFICATION FEATURE
THAT RESULTS IN DELAY OF THE SYSTEM ALARM SIGNAL FROM THE INDICATED
CIRCUITS. THE TOTAL DELAY (CONTROL UNIT PLUS SMOKE DETECTORS) SHALL
NOT EXCEED 60 SECONDS. NO OTHER SMOKE DETECTOR SHALL BE CONNECTED
TO THESE CIRCUITS UNLESS APPROVED BY THE LOCAL AUTHORITY HAVING
JURISDICTION (AHJ).
Verification
Zones
______
Control Unit
Delay
13.6 sec.
Smoke
Model
______
Detector
Delay
____sec.
In all applications where more than one wire is
under a terminal, the wire must be cut and
NOT looped around the screw terminal.
Zones 9, 10, and all
expanded zones are
suitable for Class B (as
applicable for the
initiating and signaling
line circuits per UL 864
Table 48.2 or 48.3).
Installation limits under
local Authority Having
Jurisdiction (AHJ).
Using verification delays
on zones 9 and 10 is
optional. Use the
delays marked on the
smoke detectors or
the smoke detector
installation wiring
diagram.
Figure 1: XR500/XR500N Wiring Diagram