CLIMAVENETA HRAN 0011 User manual

HRAT E - HRAT/HRAN 1English 09/02
INDEX
70°C
A
I
U
The manufacturer reserves the right to modify the data in this manual without warning.
Climaveneta is part of the Eurovent certification programme.
The following symbols are used in this publication and inside the unit:
User
Installer
Assistance
Important
Prohibition
Danger voltage
Danger moving blade
Danger high temperatures
General warnings 2
Fundamental safety rules 2
Identification 3
Receiving and handling the product 3
Description of standard unit 4
Dimensioned drawings 5
Installation 6
Hydraulic connections 6
Electrical connections 8
General technical data 17
Cooling performance HRAT-HRAT E 19
Cooling performance HRAN 21
Heat pump performance HRAN 23
Operating limits 25
Hydraulic data 26
Refrigerant circuit 27
Checking and starting up the unit 28
Activating and deactivating the unit 30
Setting service parameters 30
Alarm display 32
Operating characteristics 33
Shutting down for long periods 34
Routine maintenance 34
Extraordinary maintenance 34
Troubleshooting 35
Useful information 37
U I A
U I A
U I A
I A
I A
I
I
I A
I A
I A
A
A
A
I A
I A
I A
A
U I A
A
I A
I A
A
A
A
I A
U I A

HRAT E - HRAT/HRAN
2English 09/02
GENERAL WARNINGS
These units have been designed to chill
and/or heat water and must be used in applica-
tions compatible with their performance char-
acteristics.
Incorrect installation, regulation and mainte-
nance or improper use absolve the manufac-
turer from all liability, whether contractual or
otherwise, for damage to people, animals or
things. Only those applications specifically indi-
cated in this list are permitted.
Read this manual carefully. All work must
be carried out by qualified personnel in confor-
mity with current legislation in the country
concerned.
The HRAT-HRAN units contain R22 refrigerant
gas which damages the ozone layer. At the end
of their working life, they should be taken to a
special collection centre, as per the legislation
in force. Care should be taken to avoid damage
to the gas circuit and coil.
The guarantee is invalidated if the above
instructions are not respected and if the unit is
started up for the first time without the pres-
ence of personnel authorised by the Company
(where specified in the supply contract) who
should draw up a “start-up” report.
The documentation supplied with the
unit must be consigned to the owner who
should keep it carefully for future consultation.
When the items are consigned by the
carrier, check that the packaging and the unit
are undamaged. If damage or missing compo-
nents are noted, indicate this on the delivery
note. A formal complaint should be sent via fax
or registered post to the After Sales Depart-
ment within eight days from the date of receipt
of the items.
When operating equipment involving the use of electricity
and water, a number of fundamental safety rules must be
observed, namely:
The unit must not be used by children or by
unfit persons without suitable supervision.
Do not touch the unit with bare feet or with
wet or damp parts of the body.
Do not carry out cleaning operations without
disconnecting the unit from the electricity supply by
placing the general installation switch in the “off”
position.
Do not modify safety or regulation devices
without authorisation and instructions from the
manufacturer.
Do not pull, detach or twist the electrical
cables coming from the unit, even when discon-
nected from the mains electricity supply.
Do not open doors or panels providing access
to the internal parts of the unit without first ensur-
ing that the general installation switch is in the off
position.
Do not introduce pointed objects through the
air intake and outlet grills.
Do not dispose of, abandon or leave within
reach of children packaging materials (cardboard, sta-
ples, plastic bags, etc) as they may represent a hazard.
Respect safety distances between the unit and
other equipment or structures. Guarantee adequate
space for access to the unit for maintenance and/or
service operations.
Power supply: the cross section of the electrical
cables must be adequate for the power of the unit
and the power supply voltage must correspond with
the value indicated on the respective units.All units
must be earthed in conformity with current legisla-
tion in the country concerned.
Hydraulic connections should be carried out as
indicated in the instructions to guarantee correct
operation of the unit. Empty the hydraulic circuit or
add glycol if the unit is not used during the winter.
Handle the unit with the utmost care (see
weight distribution table) to avoid damage.
FUNDAMENTAL SAFETY RULES
UA
I
UA
I

HRAT E - HRAT/HRAN 3English 09/02
The chiller can be identified by the:
Packaging label
Giving the data identifying the product.
Rating plate
Giving the technical and performance data of the unit.
If this is lost, ask the After Sales Service for a replacement.
Tampering with or
the removal or
absence of rating plates or
other means enabling the
unit to be identified causes
problems during installa-
tion and maintenance.
IDENTIFICATION
MODEL:
VOLTAGE:
CODE:
De' Longhi S.p.a. - 31100 Treviso / Italia
Via L.Seitz, 47 - tel. 04224131 fax 0422413659
COOLING CAPACITY ------------------- kW
HEATING CAPACITY ------------------- kW
TYPE OF REFRIGERANT -------------------
REFRIGERANT CONTEN ------------------- Kg
MAXIMUM PRESSURE ------------------- bar
MAIN ELECTRICAL POWER SUPPLY ------------------- V---Hz
AUXILIARY ELECTRICAL POWER SUPPLY ------------------- V---Hz
MAX. POWER INPUT ------------------- kW
MAX. CURRENT INPUT ------------------- A
START-UP CURRENT ------------------- A
ELECTRICAL WIRING DIAGRAM ------------------- N°
OPERATING WEIGHT ------------------- Kg
YEAR OF FABRICATION -------------------
RECEIVING AND HANDLINGTHE PRODUCT
The chillers are supplied accompanied by:
-instruction manual;
-guarantee certificate;
-CE declaration.
These are contained in a plastic bag (A) attached to the
top of the chiller.
The unit should always be handled by qualified personnel
using equipment adequate for the weight of the chiller. If a
forklift truck is used, insert the forks under the bed plate,
spacing the forks as wide apart as possible. If a crane is
used, pass the cables through the bottom of the bed plate,
making sure they do not exert pressure on the unit. Once
the packaging has been removed, the unit can be lifted and
moved by inserting two metal tubes (max. diameter: 1”)
into the holes in the bed plate provided for this purpose
and using suitable handling equipment.
The instruction manual is an integral part of the
unit and should therefore be read and kept carefully.
It is recommended that the packaging should not
be removed until the unit is located in the installa-
tion site.
Do not dispose of packaging materials in the
environment or leave them within reach of children
as they may represent a hazard or source of pollution.
The weight of the chiller is biased towards the
compressor side (side of the packaging with the bar
code, see figure at the foot of the page).
During transport, the chiller should be kept in a
vertical position.
Foro Ø35
H
P
L
CODICE
A BARRE A
Dimension L 1100 1100 1100 1100 1240 1240 1240 1600 1600 1600 1600 1600
Dimension P 430 430 430 430 470 470 470 610 610 610 610 610
Dimension H 1030 1030 1280 1280 1280 1280 1280 1360 1360 1850 1850 1850
Gross weight HRAT - HRAT E 102 107 120 125 143 147 157 260 263 325 330 340
Gross weight HRAN 110 116 129 135 152 158 164 272 275 341 345 -
Model 0011 0021 0025 0031 0041 0051 0061 0071 0091 0101 0121 0151
UA
I
IA
BAR CODE
Foro Ø35

HRAT E - HRAT/HRAN
4English 09/02
DESCRIPTION OF STANDARD UNIT
These air cooled chillers with axial-flow fans and cycle
reversal operate with R22 refrigerant fluid (HRAT-HRAN)
or R407c refrigerant fluid (HRAT E), and are designed for
external installation. The units conform to the essential
requisites of EEC directive 89/392.They are factory tested
and on site installation is limited to water and electrical
connections.
STRUCTURE
Panels and bed plate are made from cataphoretic coat-
ed galvanised steel to ensure total resistance to atmos-
pheric agents.
COMPRESSORS
Hermetic rotary scroll compressor with sump heater
and thermal cut-out.
EVAPORATOR
AISI 316 stainless steel plate-type evaporator complete
with differential pressure switch. Casing lined with
anti-condensate closed cell neoprene cladding.
CONDENSING COILS
With copper tubes and high surface area aluminium fins.
Coil protection grilles as standard (HRAT E models).
FANS
External impeller axial-flow fans. Six-pole electric motor
with built-in thermal cut-out.
Housed in aerodynamic draught tubes with accident pre-
vention grill. Device for operation in low external air
temperatures with pressure transducer for contin-
uous regulation of fan rotation speed.
REFRIGERANT CIRCUIT
The refrigerant circuit includes the following components:
filter, fluid passage indicator, thermostatic expansion valve
with external equaliser. Safety pressure switches to control
delivery and intake pressures. Unit complete with non-
freezing oil and R22 (HRAT-HRAN) or R407c refrigerant
(HRAT E). Factory tested.
POWER AND CONTROL ELECTRICAL PANEL
Power and control electrical panel constructed in accor-
dance with IEC 204-1/EN60204-1, complete with compres-
sor contactor and thermal solenoid switch and door lock
safety device. Control via “HSW3” control panel.
OPTIONAL ACCESSORIES
-Removable metal mesh filter.
-Pump kit
-Inertial storage kit with pump, safety valve, filling assem-
bly, air vent valve, expansion tank, pressure gauge and
drain valve.
-Storage tank connection pipes.
-Rubber vibration dampers.
-Condensate collection pan kit.
-Remote keyboard kit.
-Serial interface kit.
-Protection grille kit (HRAT-HRAN models).
The above accessories are optional. Consult the relative
documentation for assembly instructions and technical
data.
9
8
7
4
5
2
1
3
6
10
11
1Electrical panel
2Control panel.
3Plate heat exchanger
4Low pressure switch
5High pressure switch
6Flow indicator
7Scroll compressor
8Dewatering filter
9Thermostatic valve
10 Axial-flow fan
11 Finned coil
AI

HRAT E - HRAT/HRAN 5English 09/02
DIMENSIONED DRAWINGS
E
1
2
C
G
F
NM
ML
W4
W1
W3
W2
H==
I==
D
A
B
1- Hydraulic connections IN 0011÷0031 Ø3/4” - 0041÷0151 Ø1”1/4
2- Hydraulic connections OUT 0011÷0031 Ø3/4” - 0041÷0151 Ø1”1/4
A 970 970 970 970 1100 1100 1100 1450 1450 1450 1450 1450
B 874 874 1125 1125 1125 1125 1125 1200 1200 1700 1700 1700
C 370 370 370 370 420 420 420 550 550 550 550 550
D 1028 1028 1028 1028 1156 1156 1156 1507 1507 1507 1507 1507
E86868686117117 117 117 117 117 117 117
F96969696222222 222 245 245 245 245 245
G 719 719 719 719 790 790 790 815 815 815 815 815
H 328 328 328 328 378 378 378 497 497 497 497 497
I 998 998 998 998 1126 1126 1126 1477 1477 1477 1477 1477
Dimension 0011 0021 0025 0031 0041 0051 0061 0071 0091 0101 0121 0151
Functional distances 0011 0021 0025 0031 0041 0051 0061 0071 0091 0101 0121 0151
L 900 900 900 900 900 900 900 900 900 900 900 900
M 200 200 200 200 400 400 400 400 400 400 400 400
N 600 600 600 600 600 600 600 600 600 600 600 600
Weight distribution HRAT-HRAT E
0011 0021 0025 0031 0041 0051 0061 0071 0091 0101 0121 0151
W1 30 31 37 40 45 46 50 83 84 106 107 110
W2 15 15 19 20 22 23 25 42 42 53 54 56
W3 14 15 18 18 21 22 23 40 40 49 50 52
W4 27 29 36 37 43 44 47 80 82 102 104 107
TOT 86 90 110 115 131 135 145 245 248 310 315 325
Weight distribution HRAN
0011 0021 0025 0031 0041 0051 0061 0071 0091 0101 0121 0151
W1 32 33 41 42 48 50 52 87 88 111 112 -
W2 15 17 21 22 24 25 26 44 44 55 56 -
W3 15 16 19 20 23 23 25 41 42 52 53 -
W4 30 31 38 41 45 48 49 85 86 108 109 -
TOT 92 97 119 125 140 146 152 257 260 326 330 -
I

HRAT E - HRAT/HRAN
6English 09/02
INSTALLATION
HYDRAULIC CONNECTIONS
CHOICE OF INSTALLATION SITE
Before installing the unit, agree with the customer the site
where it will be installed, taking the following points into
consideration:
-check that the fixing points are adequate to support the
weight of the unit;
-pay scrupulous respect to safety distances between the unit
and other equipment or structures to ensure that air enter-
ing the unit and discharged by the fans is free to circulate.
-The unit must be installed in a space designed to house
technical installations dimensioned according to current
legislation in the country concerned and large enough to
allow access for maintenance. If this is not possible,
then use of the protection grill kit is indispensable
(HRAT-HRAN only).
POSITIONING
Before handling the unit, check the capacity of the lift equip-
ment used, respecting the instructions on the packaging.
To move the unit in the horizontal, make appropriate use
of a lift truck or similar, bearing in mind the weight distrib-
ution of the unit. To lift the unit, insert tubes long enough
to allow positioning of the lifting slings and safety pins into
the special holes in the bed plate of the unit.
To avoid the slings damaging the unit, place protection
between the slings and the unit.
Position the unit in the site indicated by the customer.
Place either a layer of rubber (min. thickness 10 mm) or
vibration damper feet (optional) between the bed plate
and support surface.
Fix the unit, making sure it is level and that there is easy
access to hydraulic and electrical components.
If the site is exposed to strong winds, fix the unit ade-
quately to the support surface using tie rods if necessary.
If a heat pump unit is being installed, fit a condensate col-
lection pan (available as accessory).
The choice and installation of components is the responsi-
bility of the installer who should follow good working prac-
tice and current legislation. Before connecting the pipes,
make sure they do not contain stones, sand, rust, dross or
other foreign bodies which might damage the unit.
Construction of a by-pass is recommended to enable the
pipes to be washed through without having to disconnect
the unit (see drain valves).The connection piping should be
supported in such a way as to avoid it weighing on the unit.
It is recommended that the following devices are installed
in the hydraulic circuit of the evaporator.
1. Two pressure gauges with a suitable scale (inlet and outlet);
2. Two vibration damper joints (inlet and outlet);
3. Two gate valves (normal in inlet and calibrating in outlet);
4. A flow switch (in inlet) or a differential pressure switch
(inlet-outlet);
5. Two thermometers (inlet and outlet);
6. An inlet filter as close as possible to the evaporator and
positioned to allow easy access for routine maintenance.
The flow of water to the refrigerating assembly must con-
form to the values given on page 17-18.The flow of water
must be maintained constant during operation.
The water content of the unit must be such as to avoid
disturbing operation of the refrigerant circuits.
See the values given on page 26.
916
8
9 7
2 4
1
15
11
12
15 15
10
13
14
13
2 3
5
6
T
6
T
F
1
1
1Pressure gauge
2Vibration damper joint
3Gate valve
4Calibrating valve
5Flow switch
6Thermometer
7Pump
8Safety valve
9Air vent
10 Expansion tank
11 Filter
12 Top-up
13 Temperature sensor
14 Differential pressure switch
15 Drain/chemical washing valve
16 Automatic air vent (only for “plus” tube)
I
AI
Hydraulic connection diagram
with pump and storage tank (optional)
UTILITY
UNIT

HRAT E - HRAT/HRAN 7English 09/02
SIZE AND LOCATION OF CONNECTIONS
Model
0011 0021 0025 0031 0041 0051 0061 0071 0091 0101 0121 0151
If the installation requires a useful head higher than that
obtained by installing a pump assembly and storage tank,
it is recommended that an additional pump is installed
on the unit.
The pump can be easily installed on the unit by removing
the special pipe stub provided. Connect to terminal 4, 5
on the electrical panel.
The chillers must be provided with a filling/top-up
system connected to the return line and a drain cock
in the lowest part of the installation. Installations con-
taining anti-freeze or covered by specific legislation
must be fitted with hydraulic disconnectors.
The manufacturer is not liable for obstruction,
breakage or noise resulting from the failure to
install filters or vibration dampers.
Particular types of water used for filling or top-
ping up must be treated with appropriate treatment
systems. For reference values, see the table.
FILLINGTHE INSTALLATION
-Before filling, check that the installation drain cock is
closed.
-Open all installation and terminal air vents.
-Open the gate valves.
-Begin filling, slowly opening the water filling cock outside
the unit.
-When water begins to leak out of the air vent valves of
the terminals, close them and continue filling until the
pressure gauge indicates a pressure of 1.5 bars.
The installation must be filled to a pressure of
between 1 and 2 bars.
It is recommended that this operation be repeat-
ed after the unit has been operating for a number
of hours.The pressure of the installation should be
checked regularly and if it drops below 1 bar, the
water content should be topped-up.
Check hydraulic connections for tightness.
PH 6-8
Electrical conductivity less than 200 mV/cm (25°C)
Chlorine ions less than 50 ppm
Sulphuric acid ions less than 50 ppm
To tal iron less than 0,3 ppm
Alkalinity M less than 50 ppm
Total hardness less than 50 ppm
Sulphur ions nil
Ammonia ions nil
Silicon ions less than 30 ppm
EMPTYINGTHE INSTALLATION
-Before emptying, place the general installation switch in
the “off” position.
-Make sure the installation fill/top-up water cock is
closed.
-Open the drain cock outside the unit and all the installa-
tion and terminal air vent valves.
If the fluid in the circuit contains anti-freeze,
it should be not be allowed to drain freely as it is
pollutant. It should be collected for possible reuse.
A
C
B
A (mm) 86 86 86 86 117 117 117 117 117 117 117 117
B (mm) 96 96 96 96 222 222 222 222 245 245 245 245
C (mm) 719 719 719 719 790 790 790 790 815 815 815 815
Hydraulic connections (Ø) 3/4" 3/4" 3/4" 3/4"
1"1/4 1"1/4 1"1/4 1"1/4 1"1/4 1"1/4 1"1/4 1"1/4
1
92 4 6
T
1
13
14
13
235
11
15
15
812
10
7
6
T
F
Hydraulic connection diagram with pump installed in installation 1Pressure gauge
2Vibration damper joint
3Gate valve
4Calibrating valve
5Flow switch
6Thermometer
7Pump
8Safety valve
9Air vent
10 Expansion tank
11 Filter
12 Top-up
13 Temperature sensor
14 Differential pressure switch
15 Drain/chemical washing valve
WATER INLET
WATER OUTLET
UTILITY
UNIT

HRAT E - HRAT/HRAN
8English 09/02
ELECTRICAL CONNECTIONS
The chillers leave the factory completely cabled and ready
for connection to the mains electricity supply and for the
flow switch, remote ON/OFF switch and pump to be con-
nected to the terminals provided. Electrical connections
must be carried out by qualified personnel in respect of
current legislation.
For all electrical work, refer to the electrical wiring dia-
grams in this manual.
You are also recommended to check that:
-The characteristics of the mains electricity supply are
adequate for the power ratings indicated in the electrical
characteristics table below, also bearing in mind the pos-
sible use of other equipment at the same time.
Power to the unit must be turned on only after
installation work (hydraulic and electrical) has been
completed.
All electrical connections must be carried out
by qualified personnel in accordance with current
legislation in the country concerned.
Respect instructions for connecting phase, neu-
tral and earth conductors.
The power line should be fitted upstream with a
suitable device to protect against short-circuits and
leakage to earth, isolating the installation from oth-
er equipment.
Voltage must be within a tolerance of ±10%
of the rated power supply voltage for the unit (for
three phase units, the unbalance between the phas-
es must not exceed 3%).
If these parameters are not respected, contact the
electricity supply company.
For electrical connections, use double insulation
cable in conformity with current legislation in the
country concerned.
Install, if possible near the unit, an appropriate
protection device to isolate the unit from the mains
supply with delayed characteristic curve, contacts
opening by at least 3 mm and an adequate interrup-
tion and differential protection capacity.
If this device is not visible from the electrical
panel of the unit, it should be lockable
An efficient earth connection is obligatory.
Failure to earth the appliance absolves the manufac-
turer of all liability for damage.
In the case of three phase units, ensure the
phases are connected correctly.
Do not use water pipes to earth the unit.
supply (V-Ph-Hz) F.L.I. F.L.A. L.R.A. F.L.I. F.L.A. F.L.I. F.L.A. F.L.I. F.L.A. FU1 FU2 FU3 FU4 FU4*
(kW) (A) (A) (kW) (A) (kW) (A) (kW) (A)
Rated values (1) FUSES
Model Electrical power Compressors Fans Total Max. values (2) Glass 5x20mm 250V
0011 230~50 1,65 7,67 47,0 0,16 0,73 1,81 8,4 2,52 12,13 1A 1A 1A 1A 6,3A
0021 230~50 2,11 9,81 61,0 0,16 0,73 2,27 10,54 3,22 15,53 1A 1A 1A 1A 6,3A
0025 230~50 2,5 11,62 76,0 0,16 0,73 2,66 12,35 3,74 18,03 1A 1A 1A 1,6A 6,3A
0031 230~50 2,94 13,66 100,0 0,32 1,46 3,26 15,12 5,1 24,56 1A 1A 2A 1,6A 6,3A
0021 400-3N~50 2,07 3,77 40,0 0,16 0,73 2,23 4,5 2,98 5,83 1A 1A 1A 1A 6,3A
0025 400-3N~50 2,45 4,56 40,0 0,16 0,73 2,61 5,29 3,59 6,93 1A 1A 1A 1A 6,3A
0031 400-3N~50 2,86 5,22 46,0 0,32 1,46 3,18 6,68 4,2 8,46 1A 1A 2A 1,6A 6,3A
0041 400-3N~50 3,43 6,23 50,0 0,32 1,46 3,75 7,69 5,86 11,46 1A 1A 2A 1,6A 6,3A
0051 400-3N~50 4,21 7,98 66,0 0,32 1,46 4,53 9,44 7,18 13,86 1A 1A 2A 1,6A 6,3A
0061 400-3N~50 4,88 8,65 74,0 0,32 1,46 5,2 10,11 7,79 14,96 1A 1A 2A 1,6A 6,3A
0071 400-3N~50 6,31 12,04 101,0 0,67 3,3 6,98 15,34 9,03 18,4 1A 1A 10A 3,15A 6,3A
0091 400-3N~50 7,77 14,13 123,0 0,67 3,3 8,44 17,43 10,63 21,3 1A 1A 10A 3,15A 6,3A
0101 400-3N~50 8,93 16,23 127,0 1,34 6,6 10,27 22,83 12,8 27,3 1A 1A 10A 3,15A 6,3A
0121 400-3N~50 10,93 18,92 167,0 1,34 6,6 12,27 25,52 15,51 32,2 1A 1A 10A 3,15A 6,3A
0151 400-3N~50 13,4 20,0 198,0 1,34 6,6 14,7 26,6 18,10 36,6 1A 1A 10A 3,15A 6,3A
F.L.I. Power input
F.L.A. Current input
L.R.A. Compressor start-up current
(1) External air temperature 35°C - Water temperature at evaporator 12/7°C.
(2) Values refer to the lower rated voltage (50 Hz).
These values should be used to size the protection switches and power cables.
FU1* Fuse to replace FU1 if a storage tank pump + pump on unit are connected (supplied inside the electrical panel).
HRAT E ELECTRICAL DATA
AI

HRAT E - HRAT/HRAN 9English 09/02
ELECTRICAL PANEL
The electrical panel is located inside the unit at the top of
the technical compartment where the various components
of the refrigerant circuit are also to be found.
To access the electrical panel, remove the front panel of
the unit by undoing the metric screws.
To access the components in the electrical panel and the
terminal boards, undo the two screws on the panel itself.
supply (V-Ph-Hz) F.L.I. F.L.A. L.R.A. F.L.I. F.L.A. F.L.I. F.L.A. F.L.I. F.L.A. FU1 FU2 FU3 FU4 FU4*
(kW) (A) (A) (kW) (A) (kW) (A) (kW) (A)
Rated values (1) FUSES
Model Electrical power Compressors Fans Total Max. values (2) Glass 5x20mm 250V
0011 230~50 1,6 8 45,0 0,16 0,73 1,76 8,73 2,36 11,43 1A 1A 1A 1A 6,3A
0021 230~50 2,0 9,8 58,5 0,16 0,73 2,16 10,53 2,99 14,43 1A 1A 1A 1A 6,3A
0025 230~50 2,3 12,2 73,0 0,16 0,73 2,46 12,93 3,46 16,83 1A 1A 1A 1,6A 6,3A
0031 230~50 2,7 13,0 95,0 0,32 1,46 3,02 14,46 4,17 20,06 1A 1A 2A 1,6A 6,3A
0021 400-3N~50 1,97 3,72 31,0 0,16 0,73 2,13 4,45 2,66 5,53 1A 1A 1A 1A 6,3A
0025 400-3N~50 2,25 4,09 38,5 0,16 0,73 2,41 4,82 3,13 6,43 1A 1A 1A 1,6A 6,3A
0031 400-3N~50 2,6 4,6 43,5 0,32 1,46 2,92 6,06 3,76 8,08 1A 1A 2A 1,6A 6,3A
0041 400-3N~50 3,2 6,2 51,0 0,32 1,46 3,52 7,66 4,52 9,36 1A 1A 2A 1,6A 6,3A
0051 400-3N~50 4,2 7,1 59,5 0,32 1,46 4,52 8,56 5,52 11,46 1A 1A 2A 1,6A 6,3A
0061 400-3N~50 5,0 8,5 70,5 0,32 1,46 5,32 9,96 7,25 14,76 1A 1A 2A 1,6A 6,3A
0071 400-3N~50 6,0 11,2 94,0 0,67 3,3 6,67 14,5 8,28 17,9 1A 1A 10A 3,15A 6,3A
0091 400-3N~50 7,5 13,2 116,0 0,67 3,3 8,17 16,5 9,98 21,2 1A 1A 10A 3,15A 6,3A
0101 400-3N~50 8,1 15,1 127,0 1,34 6,6 9,44 21,7 11,34 25,8 1A 1A 10A 3,15A 6,3A
0121 400-3N~50 10,5 18,9 159,0 1,34 6,6 11,84 25,5 13,34 29,6 1A 1A 10A 3,15A 6,3A
F.L.I. Power input
F.L.A. Current input
L.R.A. Compressor start-up current
(1) External air temperature 35°C - Water temperature at evaporator 12/7°C.
(2) Values refer to the lower rated voltage (50 Hz).
These values should be used to size the protection switches and power cables.
FU1* Fuse to replace FU1 if a storage tank pump + pump on unit are connected (supplied inside the electrical panel).
HRAT-HRAN ELECTRICAL DATA

HRAT E - HRAT/HRAN
10 English 09/02
mode
on
off
21
set
HSW3
QS1
C4 A3 FU2
A1
KA1
KA2
QM1
KM1
A2
TCI
C2-3
FUI
FU2
FU4
ELECTRICAL PANEL LAYOUT HRAT-HRAN 0071÷0151
Channels containing live wires, even when the door lock disconnecting switch (QS) is off.
MORSETTIERA UTENTE
FU1 Transformer protection fuse
TC1 Safety transformer
FU2 Auxiliary circuit fuse
A2 Electronic controller
A1 Radio interference suppresser
C1 Radio interference capacitor
C2-3 Fan start capacitor/capacitors
QS1 Door lock disconnector switch
FU3 Fan protection fuse
FU4 Water pump protection fuse
KA1 High pressure switch relay
KA2 Water pump control relay
QM1 Compressor thermal overload switch
KM1 Compressor contactor
ELECTRICAL PANEL LAYOUT HRAT-HRAN 0011÷0061
mode
on
off
21
set
HSW3
C2-3 QS1
C1
A1
KA1
KA2
QM1
KM1
A2
TCI
FUI
FU2
FU3
FU4
MORSETTIERA UTENTE
FU1 Transformer protection fuse
TC1 Safety transformer
FU2 Auxiliary circuit fuse
A2 Electronic controller
A1 Radio interference suppresser
C1 Compressor start capacitor
C2-3 Fan start capacitor/capacitors
QS1 Door lock disconnector switch
FU3 Fan protection fuse
FU4 Water pump protection fuse
KA1 High pressure switch relay
KA2 Water pump control relay
QM1 Compressor thermal overload switch
KM1 Compressor contactor

HRAT E - HRAT/HRAN 11English 09/02
ELECTRICAL POWER CONNECTIONS
For the functional connection of the unit, bring the power
supply cable to the electrical panel inside the unit and con-
nect it to terminals U-N and PE, respecting the (U) phase,
(N) neutral and (PE) earth in the case of single phase units
(230V~50Hz), and U-V-W phases, N neutral and PE earth
in three phase units (400V-3N~50Hz).
AUXILIARY CONNECTIONS
All terminals referred to in the explanations below are to
be found on the terminal board inside the electrical panel
and described as “installer terminals”.
REMOTE START UP AND SHUT DOWN
To fit a remote on/off device, the jumper must be replaced
with a switch connected to terminals 6 and 7 of the
installer terminal board. For timed operation, connect a
daily or weekly timer between terminals 6 and 7.
REMOTE HEATING/COOLING CONTROL
To fit a remote heating/cooling switching device, the
jumper must be replaced with a switch connected to ter-
minals 8 and 9 of the installer terminal board.To install the
kit, proceed as follows:
-Select the parameter H27 on the HSW4 control panel
and set the value to 2.
REMOTE ALARM
For remote display of unit shut-down due to malfunction,
an audible or visual alarm warning device can be connected
between terminals 10 and 11. Connect the phase to termi-
nal 11 and the alarm warning device between terminal 10
and neutral (max. load: 500mA at 24V).
It is prohibited to earth the secondary of the 24V
transformer, as the chiller is compliant to the stan-
dards in force in the country concerned.
REMOTE KEYBOARD KIT
The remote keyboard kit can be used to display all unit func-
tions and access the parameters of the electronic board
from a point located at some distance from the unit itself.
It consists of a remote control module and a transformer.
To install the kit, proceed as follows:
-disconnect the power supply by means of the QS1 door
lock disconnecting switch then access the inside of the
electrical panel.
-connect the remote control module with 3 wires to ter-
minals 18, 19 and 20 on the installer terminal board.
terminal 18 connected to terminal 26 on the module;
terminal 19 connected to terminal 24 on the module;
terminal 20 connected to terminal 25 on the module;
Make sure that parameter H27 is set to 0.
To avoid interference due to magnetic fields,
the use of shielded cable is recommended. The
cable should not be more than 100m long.
CONNECTING A PUMP
If a pump is to be fitted to the unit or storage tank, it
should be connected to terminals 16, 17 and earth on the
installer terminal board.
CONNECTING A FLOW SWITCH
If a flow switch is used, connect it to terminals 14 and 15
on the installer terminal board after removing the jumper.

HRAT E - HRAT/HRAN
12 English 09/02
U
NN4
L2 U3
U1
A1 1
0
12VAC
230VAC
0
14
21
22
12VAC 12VAC
POWER
32
C1
R1
15
16
KM1
18
15
FU2
17
12DC TK ID3 ST1 ST2 ST3 ST4 GNDALL GND
ALARM ANALOG INPUTDIGITAL INPUT
1
E3 42
6 7 8 914 15
F3SA1 SA2
3
F1 2 4 5 6
10 11
+to
BT1
+to
BT2
+po
BP3
bianco
marrone
RD1
230/24VAC 500mA MAX
1
R2
DIGITAL OUTPUT
D56
YV1
KA2 KM1
1~
M
16 17
E1
KA2
1~
M
A1 2 3 4 5 6 7
EV1
U1 Z1 U2 Z2
15
KA1
1 2 3
KEYB
26 24 25
A2
5 64
24VAC
230VAC
3
TC1
19 2018
A6
KA1
4 5 5 6
17
33
15
42
42
33
4
0
3
3
0
0
3
3
42
33
0
20
0
19
21
22
30
32
33
35
36
38
39
40
41
42
FU1FU4
32
42
34
32
33
30
KA1
35
36
17
44
15
37
42
36
42
39
42
40
30
38
42 39
40
38
41
42
2727
2828
23 23
2424
25
26
47
46
45
25
29
45
46
47
15
23
15
24
15
2
17
3 4 5 6
C2
1
0
26
18
15
23
24
15
7 8
3
9
27
28
27
28
ID4
37
34
ID5
34
F5
ID1
F1F2
ID2
32
33
42
36
44
34
30
39
40
38
41
42
45
46
47
33
15
42
30
42
20
0
MORSETTI PER INSTALLATORE
INSTALLATOR TERMINAL BOX
42
41
FU3
2
2
3
4
0
3
3
0
2
U-V-W-NPE
230V~50Hz
QF1
U-N
L-N
1
1~
M
2 3
CSR
KM1
Z1
1
C1
QM1QS1
UN
45
46
47
WIRING DIAGRAM 0011-0021 SINGLE PHASE
Factory installed components
A1 Radio interference suppresser
A2 Electronic controller
A6 Unit control display keyboard
BP3 Condensing/evaporation control pressure transducer
BT1 Installation water inlet temperature sensor
BT2 Installation water outlet temperature sensor
C1 Compressor start capacitor
C2-3 Fan start capacitor
E1 Water pump
EV1-2 Fans
F1 High pressure switch
F2 Low pressure switch
F3 Flow switch
F5 Water differential pressure switch
FU1 Transformer protection fuse
FU2 Auxiliary circuit fuse
FU3 Fan protection fuse
FU4 Water pump protection fuse
KA1 High pressure switch relay
KA2 Water pump control relay
KM1 Compressor contactor
QF1 Chilling assembly protection switch
QM1 Compressor thermal overload switch
QS1 Door lock disconnector switch
R1 Compressor oil sump heater
R2 Frost heater
RD1 Red lockout warning light
SA1 On-off switch and/or timer input
SA2 Summer-winter switch input
TC1 Safety transformer
YV1 Cycle reversal valve
Z1 Compressor
1Switch not included in the supply
3Heat pumps only
4Lights not supplied
5Optional on-off switch and timer
6Optional summer-winter switch; for cooling-only mod-
els terminals 8-9 closed

HRAT E - HRAT/HRAN 13English 09/02
U
NN4
L2 U3
U1
A1 1
0
12VAC
230VAC
0
14
21
22
12VAC 12VAC
POWER
32
C1
R1
15
16
KM1
18
15
FU2
17
12DC TK ID3 ST1 ST2 ST3 ST4 GNDALL GND
ALARM ANALOG INPUTDIGITAL INPUT
1
E3 42
6 7 8 914 15
F3SA1 SA2
3
F1 2 4 5 6
10 11
+to
BT1
+to
BT2
+po
BP3
bianco
marrone
RD1
230/24VAC 500mA MAX
1
R2
DIGITAL OUTPUT
D56
YV1
KA2 KM1
1~
M
16 17
E1
KA2
1~
M
A1 2 3 4 5 6 7
EV1
U1 Z1 U2 Z2
15
KA1
1 2 3
KEYB
26 24 25
A2
2
5 64
24VAC
230VAC
3
TC1
19 2018
A6
1~
M
B1 2 3 4 5 6 7
EV2
U1 Z1 U2 Z2
KA1
4 5 5 6
17
33
15
42
42
48
5
0
3
3
48
33
4
0
3
3
0
0
3
3
0
0
3
3
48
33
0
20 0
19
21
22
30
32
33
35
36
38
39
40
41
42
FU1FU4
32
42
34
32
33
30
KA1
35
36
17
44
15
37
42
36
42
39
42
40
30
38
42 39
40
38
41
42
2727
2828
23 23
2424
25
26
47
46
45
25
29
45
46
47
15
23
15
24
15
2
17
3 4 5 6
C2 2
1
0
26
18
15
23
24
15
7 8
3
9
27
28
27
28
ID4
37
34
ID5
34
F5
ID1
F1F2
ID2
32
33
42
36
44
34
30
39
40
38
41
42
45
46
47
33
15
42
30
42
20
0
MORSETTI PER INSTALLATORE
INSTALLATOR TERMINAL BOX
42
41
FU3
C3
2
2
3
5
0
3
3
4
0
3
3
0
2
U-V-W-NPE
230V~50Hz
QF1
U-N
L-N
1
1~
M
2 3
CSR
KM1
Z1
1
C1
QM1QS1
UN
45
46
47
WIRING DIAGRAM 0025-0031 SINGLE PHASE
Factory installed components
A1 Radio interference suppresser
A2 Electronic controller
A6 Unit control display keyboard
BP3 Condensing/evaporation control pressure transducer
BT1 Installation water inlet temperature sensor
BT2 Installation water outlet temperature sensor
C1 Compressor start capacitor
C2-3 Fan start capacitor
E1 Water pump
EV1-2 Fans
F1 High pressure switch
F2 Low pressure switch
F3 Flow switch
F5 Water differential pressure switch
FU1 Transformer protection fuse
FU2 Auxiliary circuit fuse
FU3 Fan protection fuse
FU4 Water pump protection fuse
KA1 High pressure switch relay
KA2 Water pump control relay
KM1 Compressor contactor
QF1 Chilling assembly protection switch
QM1 Compressor thermal overload switch
QS1 Door lock disconnector switch
R1 Compressor oil sump heater
R2 Frost heater
RD1 Red lockout warning light
SA1 On-off switch and/or timer input
SA2 Summer-winter switch input
TC1 Safety transformer
YV1 Cycle reversal valve
Z1 Compressor
1Switch not included in the supply
2Only for models 0031
3Heat pumps only
4Lights not supplied
5Optional on-off switch and timer
6Optional summer-winter switch; for cooling-only mod-
els terminals 8-9 closed

HRAT E - HRAT/HRAN
14 English 09/02
U-V-W-NPE
400V-3N~-50Hz
QF1
U-V-W-N
L1-L2-L3-N
1
3~
M
2 3
T1 T2 T3
L1
L2
L3
KM1
QM1
Z1
QS1
U
NN4
L2 U3
U1
A1 1
0
1
12VAC
230VAC
0
14
21
22
12VAC 12VAC
POWER
32
C1
R1
15
16
KM1
18
15
FU2
17
12DC TK ID3 ST1 ST2 ST3 ST4 GNDALL GND
ALARM ANALOG INPUTDIGITAL INPUT
1
E3 42
6 7 8 914 15
F3SA1 SA2
3
F1 2 4 5 6
10 11
+to
BT1
+to
BT2
+po
BP3
bianco
marrone
RD1
230/24VAC 500mA MAX
1
R2
DIGITAL OUTPUT
D56
YV1
KA2 KM1
1~
M
16 17
E1
KA2
1~
M
A1 2 3 4 5 6 7
EV1
U1 Z1 U2 Z2
15
KA1
1 2 3
KEYB
26 24 25
A2
5 64
24VAC
230VAC
3
TC1
19 2018
A6
KA1
4 5 5 6
17
33
15
42
42
33
4
0
3
3
0
0
3
3
42
33
0
20 0
19
21
22
30
32
33
35
36
38
39
40
41
42
FU1FU4
32
42
34
32
33
30
KA1
35
36
17
44
15
37
42
36
42
39
42
40
30
38
42 39
40
38
41
42
2727
2828
23 23
2424
25
26
47
46
45
25
29
45
46
47
15
23
15
24
15
2
17
3 4 5 6
C2
1
0
26
18
15
23
24
15
7 8
3
9
27
28
27
28
ID4
37
34
ID5
34
F5
ID1
F1F2
ID2
32
33
42
36
44
34
30
39
40
38
41
42
45
46
47
33
15
42
30
42
20
0
MORSETTI PER INSTALLATORE
INSTALLATOR TERMINAL BOX
42
41
FU3
2
2
3
4
0
3
3
0
2
45
46
47
WIRING DIAGRAM 0011-0021 THREE PHASE
Factory installed components
A1 Radio interference suppresser
A2 Electronic controller
A6 Unit control display keyboard
BP3 Condensing/evaporation control pressure transducer
BT1 Installation water inlet temperature sensor
BT2 Installation water outlet temperature sensor
C1 Compressor start capacitor
C2-3 Fan start capacitor
E1 Water pump
EV1-2 Fans
F1 High pressure switch
F2 Low pressure switch
F3 Flow switch
F5 Water differential pressure switch
FU1 Transformer protection fuse
FU2 Auxiliary circuit fuse
FU3 Fan protection fuse
FU4 Water pump protection fuse
KA1 High pressure switch relay
KA2 Water pump control relay
KM1 Compressor contactor
QF1 Chilling assembly protection switch
QM1 Compressor thermal overload switch
QS1 Door lock disconnector switch
R1 Compressor oil sump heater
R2 Frost heater
RD1 Red lockout warning light
SA1 On-off switch and/or timer input
SA2 Summer-winter switch input
TC1 Safety transformer
YV1 Cycle reversal valve
Z1 Compressor
1Switch not included in the supply
3Heat pumps only
4Lights not supplied
5Optional on-off switch and timer
6Optional summer-winter switch; for cooling-only mod-
els terminals 8-9 closed

HRAT E - HRAT/HRAN 15English 09/02
U-V-W-NPE
400V-3N~-50Hz
QF1
U-V-W-N
L1-L2-L3-N
1
3~
M
2 3
T1 T2 T3
L1
L2
L3
KM1
QM1
Z1
QS1
U
NN4
L2 U3
U1
A1 1
0
1
12VAC
230VAC
0
14
21
22
12VAC 12VAC
POWER
32C 1
R1
15
16
KM1
18
15
FU2
17
12DC TK ID3 ST1 ST2 ST3 ST4 GNDALL GND
ALARM ANALOG INPUTDIGITAL INPUT
1E 3 42
6 7 8 9
14 15
F3SA1 SA2
3F 1 2 4 5 6
10 11
+to
BT1
+to
BT2
+po
BP3
bianco
marrone
RD1
230/24VAC 500mA MAX
1
R2
DIGITAL OUTPUT
D5 6
YV1
KA2 KM1
1~
M
16 17
E1
KA2
1~
M
A 1 2 3 4 5 6 7
EV1
U1 Z1 U2 Z2
15
KA1
1 2 3
KEYB
26 24 25
A2
2
5 64
24VAC
230VAC
3
TC1
19 2018
A6
1~
M
B 1 2 3 4 5 6 7
EV2
U1 Z1 U2 Z2
KA1
4 5 5 6
17
33
15
42
42
48
5
0
3
3
48
33
4
0
3
3
0
0
3
3
0
0
3
3
48
33
0
20 0
19
21
22
30
32
33
35
36
38
39
40
41
42
FU1FU4
32
42
34
32
33
30
KA1
35
36
17
44
15
37
42
36
42
39
42
40
30
38
42 39
40
38
41
42
2727
2828
23 23
2424
25
26
47
46
45
25
29
45
46
47
15
23
15
24
15
2
17
3 4 5 6
C2 2
1
0
26
18
15
23
24
15
7 8
3
9
27
28
27
28
ID4
37
34
ID5
34
F5
ID1
F1F2
ID2
32
33
42
36
44
34
30
39
40
38
41
42
45
46
47
33
15
42
30
42
20
0
MORSETTI PER INSTALLATORE
INSTALLATOR TERMINAL BOX
42
41
FU3
C3
2
2
3
5
0
3
3
4
0
3
3
0
2
45
46
47
WIRING DIAGRAM 0025-0061 THREE PHASE
Factory installed components
A1 Radio interference suppresser
A2 Electronic controller
A6 Unit control display keyboard
BP3 Condensing/evaporation control pressure transducer
BT1 Installation water inlet temperature sensor
BT2 Installation water outlet temperature sensor
C1 Compressor start capacitor
C2-3 Fan start capacitor
E1 Water pump
EV1-2 Fans
F1 High pressure switch
F2 Low pressure switch
F3 Flow switch
F5 Water differential pressure switch
FU1 Transformer protection fuse
FU2 Auxiliary circuit fuse
FU3 Fan protection fuse
FU4 Water pump protection fuse
KA1 High pressure switch relay
KA2 Water pump control relay
KM1 Compressor contactor
QF1 Chilling assembly protection switch
QM1 Compressor thermal overload switch
QS1 Door lock disconnector switch
R1 Compressor oil sump heater
R2 Frost heater
RD1 Red lockout warning light
SA1 On-off switch and/or timer input
SA2 Summer-winter switch input
TC1 Safety transformer
YV1 Cycle reversal valve
Z1 Compressor
1Switch not included in the supply
2Models 0031-0041-0051-0061 only
3Heat pumps only
4Lights not supplied
5Optional on-off switch and timer
6Optional summer-winter switch; for cooling-only mod-
els terminals 8-9 closed

HRAT E - HRAT/HRAN
16 English 09/02
U-V-W-NPE
400V-3N~-50Hz
QF1
U-V-W-N
L1-L2-L3-N
1
3~
M
2 3
T1 T2 T3
L1
L2
L3
KM1
QM1
Z1
QS1
U
NN4
L2 U3
U1
A1 1
0
C4
1
12VAC
230VAC
0
14
21
22
12VAC 12VAC
POWER
32C 1
R1
15
16
KM1
18
15
FU2
17
12DC TK ID3 ST1 ST2 ST3 ST4 GNDALL GND
ALARM ANALOG INPUTDIGITAL INPUT
1E 3 42
6 7 8 914 15
F3SA1 SA2
3F 1 2 4 5 6
10 11
+to
BT1
+to
BT2
+po
BP3
bianco
marrone
RD1
230/24VAC 500mA MAX
1
R2
DIGITAL OUTPUT
D56
YV1
KA2 KM1
1~
M
16 17
E1
KA2
1~
M
A 1 2 3 4 5 6 7
EV1
U1 Z1 U2 Z2
15
KA1
21 22 N5 25 26 N2 23 24 N6 27 28 N3 33 34
A3
1 2 3
KEYB
26 24 25
A2
2
5 64
24VAC
230VAC
3
F1
N1
FU3
TC1
19 20
18
A6
1~
M
B 1 2 3 4 5 6 7
EV2
U1 Z1 U2 Z2
KA1
4 5 5 6
30
31
17
33
15
43
43
48
11
10
9
8
48
33
5
4
3
2
11
10
9
8
5
4
3
2
13
12
7
6
48
33
0
20
0
19
21
22
30
31
32
33
35
36
38
39
40
41
42
FU1FU4
32
42
34
32
33
30
KA1
35
36
17
44
15
37
42
36
42
39
42
40
30
38
42 39
40
38
41
42
2727
2828
23 23
2424
25
26
47
46
45
25
29
45
46
47
15
23
15
24
15
2
17
3 4 5 6
C2 C3
2
30
31
1
0
26
18
15
23
24
15
7 8
17
9
31
27
28
27
28
ID4
37
34
ID5
34
F5
ID1
F1F2
ID2
F4
1 3 42
UN
17 17
15
43
42
32
33
42
36
44
31
34
30
39
40
38
41
42
45
46
47
30
31
33
15
43
30
42
20
0
MORSETTI PER INSTALLATORE
INSTALLATOR TERMINAL BOX
17
42
41
WIRING DIAGRAM 00271-0151 THREE PHASE
Factory installed components
ARadio interference suppresser
A2 Electronic controller
A6 Unit control display keyboard
BP3 Condensing/evaporation control pressure transducer
BT1 Installation water inlet temperature sensor
BT2 Installation water outlet temperature sensor
C1 Compressor start capacitor
C2-3 Fan start capacitor
E1 Water pump
EV1-2 Fans
F1 High pressure switch
F2 Low pressure switch
F3 Flow switch
F5 Water differential pressure switch
FU1 Transformer protection fuse
FU2 Auxiliary circuit fuse
FU3 Fan protection fuse
FU4 Water pump protection fuse
KA1 High pressure switch relay
KA2 Water pump control relay
KM1 Compressor contactor
QF1 Chilling assembly protection switch
QM1 Compressor thermal overload switch
QS1 Door lock disconnector switch
R1 Compressor oil sump heater
R2 Frost heater
RD1 Red lockout warning light
SA1 On-off switch and/or timer input
SA2 Summer-winter switch input
TC1 Safety transformer
YV1 Cycle reversal valve
Z1 Compressor
1Switch not included in the supply
2Models 0031-0041-0051-0061only
3Heat pumps only
4Lights not supplied
5Optional on-off switch and timer
6Optional summer-winter switch; for cooling-only mod-
els terminals 8-9 closed

HRAT E - HRAT/HRAN 17English 09/02
GENERALTECHNICAL DATA
No.of fansN°11122221122
Min. rotation speed g/m 430 430 430 430 430 430 420 430 430 310 310
Max. rotation speed g/m 760 870 870 760 870 870 860 870 870 620 620
Max. air flow m3/h 2400 3500 3500 4200 6800 6800 6400 9800 9800 14000 14000
Cooling capacity (1) kW 4,7 6,1 7,0 8,2 10,5 12,5 15,0 19,1 22,2 26,8 32,4
Compressor power input (1) kW 1,6 2,0 2,3 2,6 3,2 4,2 5,0 6,0 7,5 8,1 10,5
Total power input (1) kW 1,8 2,2 2,5 2,9 3,6 4,5 5,3 6,9 8,2 9,0 11,3
Total current input at rated conditions (1) A 8,5 10,7 13,0 14,1 7,8 8,6 10,1 14,6 18,0 20,6 24,3
Evaporator water flow m3/h 0,8 1,0 1,2 1,4 1,8 2,2 2,6 3,2 3,8 4,6 5,6
Evaporator pressure drop kPa 23 33 35 39 23 23 26 29 24 28 28
R22 Refrigerant Kg 1,6 1,8 2,4 2,2 2,8 2,9 3,1 5,4 5,7 9,8 9
White Oil Kg 1,0 1,0 1,1 1,1 2,0 2,0 1,65 ----
Suniso 3GS Oil Kg -------4,04,04,04,0
Operating weight Kg 86 90 110 115 131 135 145 245 248 310 315
Type of compressor Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Number of compressors N° 11111111111
Number of circuits N° 11111111111
Power steps N° 11111111111
Width mm 970 970 970 970 1100 1100 1100 1450 1450 1450 1450
Height mm 874 874 1125 1125 1125 1125 1125 1200 1200 1700 1700
Width mm 370 370 370 370 420 420 420 550 550 550 550
Hydraulic connections in/out Gas 3/4” 3/4” 3/4” 3/4” 1”1/4 1”1/4 1”1/4 1”1/4 1”1/4 1”1/4 1”1/4
Sound pressure level (3) dB(A) 50 55 55 55 58 58 58 65 65 65 65
HRAT 0011 0021 0025 0031 0041 0051 0061 0071 0091 0101 0121
Cooling capacity (1) kW 4,7 6,1 7,0 8,2 10,5 12,5 15,0 19,1 22,2 26,8 32,4 38,8
Compressor power input (1) kW 1,65 2,11 2,5 2,94 3,43 4,21 4,88 6,31 7,77 8,93 10,93 13,4
Total power input (1) kW 1,81 2,27 2,66 3,26 3,75 4,53 5,2 6,98 8,44 10,27 12,27 14,7
Total current input at rated conditions (1)
A 8,4 10,54 12,35 15,12 7,69 9,44 10,12 15,34 17,43 22,83 25,52 26,6
Evaporator water flow rate m3/h 0,8 1,0 1,2 1,4 1,8 2,2 2,6 3,2 3,8 4,6 5,6 6,7
Evaporator pressure drop kPa 23 33 35 39 23 23 26 29 24 28 28 34,9
R407c Refrigerant Kg 2,95 2,3 3,1 2,8 3,3 4,8 6,9 7,2 7,2 10,9 9,8 10,2
32 MMM POE Oil Kg 4,0 4,0 4,0 4,0 4,0 4,0 4,0 4,0 4,0 4,0 4,0 6,6
Operating weight Kg 86 90 110 115 131 135 145 245 248 310 315 325
Type of compressor Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Number of compressors N° 111111111111
Number of circuits N° 111111111111
Power steps N° 111111111111
Hydraulic connections in/out Gas 3/4" 3/4" 3/4" 3/4" 1"1/4 1"1/4 1"1/4 1"1/4 1"1/4 1"1/4 1"1/4 1"1/4
Sound pressure level (3) dB(A) 50 55 55 55 58 58 58 65 65 65 65 65
HRAT E 0011 0021 0025 0031 0041 0051 0061 0071 0091 0101 0121 0151
(1) condenser air in 35°C evaporator water in/out 12/7°C (3) at 1 m in open field, fan side
(2) evaporator air in 7°C 85% RH condenser water in/out 40/45°C
Width mm 970 970 970 970 1100 1100 1100 1450 1450 1450 1450 1450
Height mm 874 874 1125 1125 1125 1125 1125 1200 1200 1700 1700 1700
Width mm 370 370 370 370 420 420 420 550 550 550 550 550
IA
No.of fansN°111222211222
Min. rotation speed g/m 430 430 430 430 430 430 420 430 430 310 310 310
Max. rotation speed g/m 760 870 870 760 870 870 860 870 870 620 620 620
Max. air flow m3/h 2400 3500 3500 4200 6800 6800 6400 9800 9800 14000 14000 14000

HRAT E - HRAT/HRAN
18 English 09/02
Cooling capacity (1) kW 4,4 5,8 6,6 7,9 10,0 11,9 14,2 18,2 21,2 25,6 30,9
Compressor power input (1)(2) kW 1,6 2,0 2,3 2,6 3,2 4,2 5,0 6,0 7,5 8,1 10,5
Total power input (1)(2) kW 1,8 2,2 2,5 2,9 3,6 4,5 5,3 6,9 8,2 9,0 11,3
Total current input at rated conditions (1)(2) A 8,5 10,7 13,0 14,1 7,8 8,6 10,1 14,6 18,0 20,6 24,3
Heating capacity (2) kW 5,4 6,8 7,8 9,0 11,2 13,2 16,3 21,1 24,4 29,5 35,3
Water flow in heating (2) m3/h 0,9 1,2 1,4 1,6 2,0 23 2,8 3,7 4,2 5,1 6,1
Pressure drop (2) kPa 24 34 36 40 27 25 31 37 29 34 34
R22 Refrigerant Kg 2,95 2,3 3,1 2,8 3,3 4,8 6,9 7,2 7,2 10,9 9,8
White Oil Kg 1,0 1,0 1,1 1,1 2,0 2,0 1,65 ----
Suniso 3GS Oil Kg -------4,04,04,04,0
Operating weight Kg 92 97 119 125 140 146 152 257 260 326 330
Type of compressor Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Number of compressors N° 11111111111
Number of circuits N° 11111111111
Power steps N° 11111111111
Hydraulic connections in/out Gas 3/4” 3/4” 3/4” 3/4” 1”1/4 1”1/4 1”1/4 1”1/4 1”1/4 1”1/4 1”1/4
Sound pressure level (3) dB(A) 50 55 55 55 58 58 58 65 65 65 65
HRAN 0011 0021 0025 0031 0041 0051 0061 0071 0091 0101 0121
(1) condenser air in 35°C evaporator water in/out 12/7°C (3) at 1 m in open field, fan side
(2) evaporator air in 7°C 85% RH condenser water in/out 40/45°C
Width mm 970 970 970 970 1100 1100 1100 1450 1450 1450 1450
Height mm 874 874 1125 1125 1125 1125 1125 1200 1200 1700 1700
Width mm 370 370 370 370 420 420 420 550 550 550 550
No.of fansN°11122221122
Min. rotation speed g/m 430 430 430 430 430 430 420 430 430 310 310
Max. rotation speed g/m 760 870 870 760 870 870 860 870 870 620 620
Max. air flow m3/h 2400 3500 3500 4200 6800 6800 6400 9800 9800 14000 14000

HRAT E - HRAT/HRAN 19English 09/02
COOLING PERFORMANCE HRAT-HRAT E
Model 0025
Ta.Tw 5678910Ta.Tw 5678910
Model 0011
Ta: external air temperature (°C) Pa: compressor power input (kW) ∆Pev: evaporator pressure drop (kPa)
Tw :evaporator water outlet temperature (°C) Pat: total power input Pf: cooling capacity (kW)
Qev: evaporator water flow (m3/h)
Ta.Tw 5678910
Model 0021
Pf 4,9 5,0 5,2 5,3 5,4 5,6
Pa 1,3 1,3 1,3 1,3 1,4 1,4
25 Pat 1,4 1,4 1,4 1,4 1,4 1,4
Qev 0,8 0,9 0,9 0,9 0,9 1,0
∆Pev 24,6 26,0 27,6 29,2 30,8 32,5
Pf 4,6 4,8 4,9 5,1 5,2 5,3
Pa 1,5 1,5 1,5 1,5 1,5 1,5
30 Pat 1,5 1,6 1,6 1,6 1,6 1,6
Qev 0,8 0,8 0,8 0,9 0,9 0,9
∆Pev 22,4 23,7 25,1 26,6 28,1 29,6
Pf 4,6 4,7 4,8 5,0 5,1 5,2
Pa 1,5 1,5 1,6 1,6 1,6 1,6
32 Pat 1,6 1,6 1,6 1,6 1,7 1,7
Qev 0,8 0,8 0,8 0,9 0,9 0,9
∆Pev 21,5 22,8 24,1 25,5 27,0 28,5
Pf 4,4 4,5 4,7 4,8 4,9 5,1
Pa 1,6 1,6 1,6 1,7 1,7 1,7
35 Pat 1,7 1,7 1,8 1,8 1,8 1,8
Qev 0,8 0,8 0,8 0,8 0,9 0,9
∆Pev 20,1 21,3 22,6 23,9 25,3 26,7
Pf 4,1 4,3 4,4 4,5 4,7 4,8
Pa 1,8 1,8 1,9 1,9 1,9 1,9
40 Pat 1,9 1,9 1,9 2,0 2,0 2,0
Qev 0,7 0,7 0,8 0,8 0,8 0,8
∆Pev 17,8 18,9 20,1 21,3 22,5 23,8
Pf 4,0 4,1 4,2 4,4 4,5 4,6
Pa 2,0 2,0 2,0 2,0 2,0 2,0
43 Pat 2,0 2,1 2,1 2,1 2,1 2,1
Qev 0,7 0,7 0,7 0,7 0,8 0,8
∆Pev 16,4 17,4 18,5 19,7 20,8 22,0
Pf 6,3 6,5 6,7 6,9 7,0 7,2
Pa 1,6 1,6 1,6 1,6 1,6 1,6
25 Pat 1,7 1,8 1,8 1,8 1,8 1,8
Qev 1,1 1,1 1,1 1,2 1,2 1,2
∆Pev 35,2 37,4 39,5 41,8 44,2 46,6
Pf 6,0 6,2 6,4 6,6 6,7 6,9
Pa 1,8 1,8 1,8 1,8 1,8 1,8
30 2,00 Pat 1,9 1,9 2,0 2,0 2,0
Qev 1,0 1,1 1,1 1,1 1,2 1,2
∆Pev 32,3 34,2 36,3 38,4 40,5 42,8
Pf 5,9 6,1 6,3 6,4 6,6 6,8
Pa 1,9 1,9 1,9 1,9 1,9 1,9
32 Pat 2,0 2,0 2,0 2,0 2,1 2,1
Qev 1,0 1,0 1,1 1,1 1,1 1,2
∆Pev 3,1 33,0 34,9 37,0 39,1 41,3
Pf 5,7 5,9 6,1 6,3 6,4 6,6
Pa 2,0 2,0 2,0 2,0 2,0 2,0
35 Pat 2,1 2,1 2,2 2,2 2,2 2,2
Qev 1,0 1,0 1,0 1,1 1,1 1,1
∆Pev 29,3 31,1 33,0 34,9 36,9 39,0
Pf 5,4 5,6 5,8 6,0 6,1 6,3
Pa 2,2 2,2 2,2 2,2 2,3 2,3
40 Pat 2,4 2,4 2,4 2,4 2,4 2,4
Qev 0,9 1,0 1,0 1,0 1,1 1,1
∆Pev 26,4 28,0 29,8 31,5 33,4 35,3
Pf 5,3 5,4 5,6 5,8 5,9 6,1
Pa 2,3 2,4 2,4 2,4 2,4 2,4
43 Pat 2,5 2,5 2,5 2,5 2,6 2,6
Qev 0,9 0,9 1,0 1,0 1,0 1,1
∆Pev 24,7 26,2 27,9 29,5 31,3 33,1
Pf 7,2 7,5 7,7 7,9 8,1 8,3
Pa 1,8 1,8 1,9 1,9 1,9 1,9
25 Pat 2,0 2,0 2,0 2,0 2,0 2,1
Qev 1,2 1,3 1,3 1,4 1,4 1,4
∆Pev 37,8 40,0 42,3 44,7 47,2 49,7
Pf 6,9 7,1 7,3 7,5 7,7 7,9
Pa 2,0 2,1 2,1 2,1 2,1 2,1
30 Pat 2,2 2,2 2,2 2,3 2,3 2,3
Qev 1,2 1,2 1,3 1,3 1,3 1,4
∆Pev 34,5 36,5 38,6 40,8 43,1 45,4
Pf 6,8 7,0 7,2 7,4 7,6 7,8
Pa 2,1 2,2 2,2 2,2 2,2 2,2
32 Pat 2,3 2,3 2,3 2,4 2,4 2,4
Qev 1,2 1,2 1,2 1,3 1,3 1,3
∆Pev 33,1 35,1 37,1 39,2 41,4 43,7
Pf 6,6 6,8 7,0 7,2 7,3 7,5
Pa 2,3 2,3 2,3 2,3 2,4 2,4
35 Pat 2,5 2,5 2,5 2,5 2,5 2,5
Qev 1,1 1,2 1,2 1,2 1,3 1,3
∆Pev 31,1 32,9 34,9 36,9 38,9 41,1
Pf 6,2 6,4 6,6 6,8 6,9 7,1
Pa 2,6 2,6 2,6 2,6 2,6 2,6
40 Pat 2,7 2,7 2,8 2,8 2,8 2,8
Qev 1,1 1,1 1,1 1,2 1,2 1,2
∆Pev 27,7 29,4 31,1 32,9 34,8 36,7
Pf 6,0 6,2 6,3 6,5 6,7 6,9
Pa 2,7 2,7 2,8 2,8 2,8 2,8
43 Pat 2,9 2,9 2,9 2,9 3,0 3,0
Qev 1,0 1,1 1,1 1,1 1,2 1,2
∆Pev 25,6 27,2 28,9 30,6 32,3 34,1
Model 0051
Ta.Tw 5678910Ta.Tw 5678910
Model 0031
Ta.Tw 5678910
Model 0041
Pf 8,6 8,8 9,1 9,3 9,6 9,8
Pa 2,1 2,1 2,1 2,1 2,1 2,2
25 Pat 2,2 2,2 2,3 2,3 2,3 2,3
Qev 1,5 1,5 1,6 1,6 1,6 1,7
∆Pev 42,2 44,7 47,3 50,0 52,8 55,7
Pf 8,2 8,4 8,7 8,9 9,2 9,4
Pa 2,3 2,3 2,4 2,4 2,4 2,4
30 Pat 2,5 2,5 2,5 2,5 2,6 2,6
Qev 1,4 1,5 1,5 1,5 1,6 1,6
∆Pev 38,5 40,8 43,2 45,7 48,3 50,9
Pf 8,0 8,3 8,5 8,7 9,0 9,2
Pa 2,4 2,4 2,5 2,5 2,5 2,5
32 Pat 2,6 2,6 2,6 2,6 2,7 2,7
Qev 1,4 1,4 1,5 1,5 1,5 1,6
∆Pev 37,0 39,3 41,6 44,0 46,4 49,0
Pf 7,8 8,0 8,2 8,5 8,7 8,9
Pa 2,6 2,6 2,7 2,7 2,7 2,7
35 Pat 2,8 2,8 2,9 2,9 3,0 3,0
Qev 1,3 1,4 1,4 1,5 1,5 1,5
∆Pev 34,8 36,9 39,1 41,3 43,7 46,1
Pf 7,3 7,6 7,8 8,0 8,2 8,5
Pa 2,9 2,9 3,0 3,0 3,0 3,0
40 Pat 3,1 3,1 3,1 3,1 3,2 3,2
Qev 1,3 1,3 1,3 1,4 1,4 1,5
∆Pev 31,0 32,9 34,9 36,9 39,1 41,3
Pf 7,1 7,3 7,5 7,7 7,9 8,2
Pa 3,1 3,1 3,2 3,2 3,2 3,2
43 Pat 3,3 3,3 3,3 3,3 3,4 3,4
Qev 1,2 1,3 1,3 1,3 1,4 1,4
∆Pev 28,8 30,5 32,4 34,3 36,3 38,4
Pf 10,9 11,2 11,5 11,8 12,2 12,5
Pa 2,6 2,6 2,7 2,7 2,7 2,7
25 Pat 2,9 3,0 3,0 3,0 3,0 3,1
Qev 1,9 1,9 2,0 2,0 2,1 2,2
∆Pev 24,5 26,0 27,5 29,1 30,8 32,5
Pf 10,4 10,7 11,1 11,4 11,7 12,0
Pa 2,9 2,9 2,9 3,0 3,0 3,0
30 Pat 3,2 3,2 3,2 3,3 3,3 3,3
Qev 1,8 1,8 1,9 2,0 2,0 2,1
∆Pev 22,5 23,9 25,3 26,8 28,4 29,9
Pf 10,2 10,5 10,8 11,2 11,5 11,8
Pa 3,0 3,0 3,0 3,1 3,1 3,1
32 Pat 3,3 3,3 3,4 3,4 3,4 3,4
Qev 1,8 1,8 1,9 1,9 2,0 2,0
∆Pev 21,7 23,0 24,4 25,8 27,3 28,8
Pf 9,9 10,2 10,5 10,8 11,1 11,4
Pa 3,2 3,2 3,3 3,3 3,4 3,4
35 Pat 3,5 3,5 3,6 3,6 3,7 3,7
Qev 1,7 1,8 1,8 1,9 1,9 2,0
∆Pev 20,3 21,6 22,9 24,2 25,6 27,1
Pf 9,3 9,6 9,9 10,1 10,4 10,7
Pa 3,5 3,5 3,5 3,6 3,6 3,6
40 Pat 3,8 3,8 3,9 3,9 3,9 4,0
Qev 1,6 1,6 1,7 1,7 1,8 1,8
∆Pev 17,9 19,0 20,2 21,4 22,6 23,9
Pf 8,9 9,2 9,4 9,7 10,0 10,3
Pa 3,7 3,7 3,7 3,8 3,8 3,8
43 Pat 4,0 4,0 4,1 4,1 4,1 4,2
Qev 1,5 1,6 1,6 1,7 1,7 1,8
∆Pev 16,4 17,4 18,5 19,6 20,7 21,9
Pf 13,1 13,5 13,8 14,2 14,6 15,0
Pa 3,4 3,4 3,5 3,5 3,6 3,6
25 Pat 3,7 3,8 3,8 3,8 3,9 3,9
Qev 2,3 2,3 2,4 2,5 2,5 2,6
∆Pev 23,8 25,2 26,7 28,2 29,8 31,4
Pf 12,5 12,8 13,2 13,6 13,9 14,3
Pa 3,8 3,8 3,8 3,9 3,9 3,9
30 Pat 4,1 4,1 4,1 4,2 4,2 4,3
Qev 2,1 2,2 2,3 2,3 2,4 2,5
∆Pev 21,6 22,9 24,3 25,7 27,1 28,6
Pf 12,2 12,6 12,9 13,3 13,6 14,0
Pa 3,9 3,9 4,0 4,0 4,1 4,1
32 Pat 4,2 4,3 4,3 4,3 4,4 4,4
Qev 2,1 2,2 2,2 2,3 2,4 2,4
∆Pev 20,7 22,0 23,2 24,6 26,0 27,4
Pf 11,8 12,1 12,5 12,8 13,2 13,5
Pa 4,1 4,2 4,2 4,2 4,3 4,3
35 Pat 4,4 4,5 4,5 4,6 4,6 4,6
Qev 2,0 2,1 2,1 2,2 2,3 2,3
∆Pev 19,2 20,4 22,6 22,9 24,2 25,5
Pf 11,0 11,3 11,6 11,9 12,3 12,6
Pa 4,5 4,6 4,6 4,7 4,7 4,8
40 Pat 4,9 4,9 4,9 5,0 5,0 5,1
Qev 1,9 1,9 2,0 2,1 2,1 2,2
∆Pev 16,7 17,7 18,8 19,8 21,0 22,1
Pf 10,4 10,7 11,0 11,4 11,7 12,0
Pa 4,8 4,8 4,9 4,9 5,0 5,0
43 Pat 5,1 5,2 5,2 5,2 5,3 5,3
Qev 1,8 1,8 1,9 2,0 2,0 2,1
∆Pev 15,1 16,0 17,0 18,0 19,0 20,1
A

HRAT E - HRAT/HRAN
20 English 09/02
Ta: external air temperature (°C) Pa: compressor power input (kW) ∆Pev: evaporator pressure drop (kPa)
Tw :evaporator water outlet temperature (°C) Pat: total power input Pf: cooling capacity (kW)
Qev: evaporator water flow (m3/h)
Model 0091
Ta.Tw 5678910Ta.Tw 5678910
Model 0061
Ta.Tw 5678910
Model 0071
Pf 15,6 16,1 16,5 17,0 17,4 17,8
Pa 4,0 4,0 4,1 4,1 4,1 4,2
25 Pat 4,3 4,4 4,4 4,4 4,5 4,5
Qev 2,7 2,8 2,8 2,9 3,0 3,1
∆Pev 27,7 29,4 31,0 32,7 34,4 36,1
Pf 14,9 15,3 15,8 16,2 16,6 17,0
Pa 4,5 4,5 4,5 4,6 4,6 4,6
30 Pat 4,8 4,8 4,8 4,9 4,9 4,9
Qev 2,6 2,6 2,7 2,8 2,9 2,9
∆Pev 25,3 26,8 28,3 29,8 31,3 32,8
Pf 14,6 15,0 15,5 15,9 16,2 16,6
Pa 4,6 4,7 4,7 4,8 4,8 4,8
32 Pat 5,0 5,0 5,0 5,1 5,1 5,1
Qev 2,5 2,6 2,7 2,7 2,8 2,9
∆Pev 24,3 25,7 27,2 28,6 30,1 31,5
Pf 14,1 14,6 15,0 15,3 15,7 16,1
Pa 5,0 5,0 5,0 5,1 5,1 5,1
35 Pat 5,3 5,3 5,3 5,4 5,4 5,5
Qev 2,4 2,5 2,6 2,6 2,7 2,8
∆Pev 22,8 24,1 25,5 26,8 28,1 29,5
Pf 13,3 13,7 14,1 14,4 14,8 15,1
Pa 5,5 5,5 5,6 5,6 5,6 5,7
40 Pat 5,8 5,9 5,9 5,9 6,0 6,0
Qev 2,3 2,4 2,4 2,5 2,5 2,6
∆Pev 20,2 21,4 22,6 23,7 24,9 26,0
Pf 12,8 13,2 13,5 13,6 14,2 14,5
Pa 5,9 5,9 5,9 6,0 6,0 6,0
43 Pat 6,2 6,2 6,2 6,3 6,3 6,4
Qev 2,2 2,3 2,3 2,4 2,4 2,5
∆Pev 18,6 19,7 20,8 21,9 22,9 24,0
Pf 19,8 20,3 20,9 21,5 22,1 22,7
Pa 4,7 4,7 4,7 4,8 4,8 4,8
25 Pat 5,3 5,4 5,4 5,4 5,5 5,5
Qev 3,4 3,5 3,6 3,7 3,8 3,9
∆Pev 31,2 33,1 35,1 37,1 39,2 41,4
Pf 18,9 19,5 20,0 20,6 21,2 21,8
Pa 5,2 5,3 5,3 5,3 5,4 5,4
30 Pat 5,9 6,0 6,0 6,0 6,1 6,1
Qev 3,3 3,3 3,4 3,5 3,6 3,7
∆Pev 28,5 30,3 32,1 34,0 35,9 38,0
Pf 18,5 19,1 19,7 20,2 20,8 21,4
Pa 5,5 5,5 5,6 5,6 5,6 5,7
32 Pat 6,2 6,2 6,2 6,3 6,3 6,3
Qev 3,2 3,3 3,4 3,5 3,6 3,7
∆Pev 27,4 29,1 30,9 32,7 34,6 36,6
Pf 18,0 18,5 19,1 19,6 20,2 20,8
Pa 5,9 6,0 6,1 6,1 6,2 6,2
35 Pat 6,7 6,8 6,9 6,9 7,0 7,0
Qev 3,1 3,2 3,3 3,4 3,5 3,6
∆Pev 25,8 27,4 29,1 30,8 32,6 34,5
Pf 17,0 17,5 18,1 18,6 19,1 19,7
Pa 6,6 6,6 6,7 6,7 6,8 6,8
40 Pat 7,3 7,3 7,4 7,4 7,4 7,5
Qev 2,9 3,0 3,1 3,2 3,3 3,4
∆Pev 23,1 24,6 26,1 27,7 29,3 31,0
Pf 16,4 16,9 17,4 18,0 18,5 19,0
Pa 7,1 7,1 7,1 7,2 7,2 7,3
43 Pat 7,7 7,8 7,8 7,9 7,9 7,9
Qev 2,8 2,9 3,0 3,1 3,2 3,3
∆Pev 21,5 22,9 24,3 25,8 27,3 28,9
Pf 23,2 23,9 24,5 25,2 25,9 26,6
Pa 5,8 5,9 5,9 6,0 6,0 6,1
25 Pat 6,5 6,6 6,6 6,7 6,7 6,7
Qev 4,0 4,1 4,2 4,3 4,5 4,6
∆Pev 25,4 27,0 28,6 30,2 31,9 33,6
Pf 22,1 22,8 23,4 24,1 24,8 25,4
Pa 6,6 6,6 6,7 6,7 6,8 6,8
30 Pat 7,2 7,3 7,3 7,4 7,5 7,5
Qev 3,8 3,9 4,0 4,1 4,3 4,4
∆Pev 23,2 24,6 26,0 27,5 29,1 30,7
Pf 21,7 22,3 23,0 23,6 24,3 24,9
Pa 6,9 6,9 7,0 7,0 7,1 7,2
32 Pat 7,6 7,6 7,7 7,7 7,8 7,8
Qev 3,7 3,8 4,0 4,1 4,2 4,3
∆Pev 22,2 23,6 25,0 26,4 28,0 29,5
Pf 21,0 21,6 22,2 22,9 23,5 24,2
Pa 7,4 7,4 7,5 7,5 7,6 7,7
35 Pat 8,0 8,1 8,2 8,2 8,3 8,3
Qev 3,6 3,7 3,8 3,9 4,1 1,2
∆Pev 20,9 22,1 23,5 24,8 26,3 27,7
Pf 19,8 20,4 21,0 21,6 22,2 22,8
Pa 8,2 8,3 8,4 8,4 8,5 8,6
40 Pat 8,9 9,0 9,0 9,1 9,2 9,2
Qev 3,4 3,5 3,6 3,7 3,8 3,9
∆Pev 18,6 19,7 20,9 22,2 23,4 24,8
Pf 19,1 19,6 20,2 20,8 21,4 22,0
Pa 8,8 8,9 8,9 9,0 9,1 9,1
43 Pat 9,5 9,5 9,6 9,7 9,7 9,8
Qev 3,3 3,4 3,5 3,6 3,7 3,8
∆Pev 17,2 18,3 19,4 20,6 21,8 23,0
Model 0151
Ta.Tw 5678910Ta.Tw 5678910
Model 0101
Ta.Tw 5678910
Model 0121
Pf 27,7 28,5 29,4 30,2 31,0 31,9
Pa 6,1 6,2 6,2 6,2 6,3 6,3
25 Pat 6,9 6,9 7,0 7,0 7,0 7,1
Qev 4,8 4,9 5,1 5,2 5,3 5,5
∆Pev 29,5 31,3 33,2 35,2 37,2 39,2
Pf 26,5 27,3 28,1 28,9 29,8 30,6
Pa 6,9 7,0 7,0 7,0 7,1 7,1
30 Pat 7,7 7,7 7,8 7,8 7,8 7,9
Qev 4,6 4,7 4,8 5,0 5,1 5,3
∆Pev 27,1 28,8 30,5 32,3 34,2 36,1
Pf 26,0 26,8 27,6 28,4 29,2 30,0
Pa 7,2 7,3 7,3 7,4 7,4 7,5
32 Pat 8,0 8,0 8,1 8,1 8,2 8,2
Qev 4,5 4,6 4,8 4,9 5,0 5,2
∆Pev 26,1 27,7 29,4 31,1 32,9 34,8
Pf 25,3 26,0 26,8 27,6 28,4 29,2
Pa 7,9 8,0 8,1 8,1 8,2 8,2
35 Pat 8,8 8,9 9,0 9,0 9,1 9,1
Qev 4,3 4,5 4,6 4,8 4,9 5,0
∆Pev 24,6 26,1 27,7 29,4 31,1 32,9
Pf 24,0 24,7 25,5 26,2 27,0 27,7
Pa 8,7 8,8 8,8 8,9 8,9 9,0
40 Pat 9,5 9,5 9,6 9,6 9,7 9,7
Qev 4,1 4,3 4,4 4,5 4,6 4,8
∆Pev 22,1 23,5 25,0 26,5 28,1 29,7
Pf 23,1 23,9 24,6 25,3 26,1 26,8
Pa 9,3 9,4 9,4 9,5 9,5 9,6
43 Pat 10,1 10,1 10,2 10,2 10,3 10,3
Qev 4,0 4,1 4,2 4,4 4,5 4,6
∆Pev 20,6 21,9 23,3 24,7 26,2 27,8
Pf 33,7 34,7 35,7 36,7 37,7 38,7
Pa 8,2 8,3 8,4 8,4 8,5 8,5
25 Pat 9,0 9,1 9,1 9,2 9,2 9,3
Qev 5,8 6,0 6,1 6,3 6,5 6,7
∆Pev 29,9 31,7 33,6 35,5 37,5 39,6
Pf 32,2 33,1 34,1 35,0 36,0 37,0
Pa 9,3 9,3 9,4 9,5 9,5 9,6
30 Pat 10,0 10,1 10,2 10,2 10,3 10,4
Qev 5,5 5,7 5,9 6,0 6,2 6,4
∆Pev 27,3 28,9 30,6 32,4 34,3 36,2
Pf 31,5 32,5 33,4 34,4 35,3 36,3
Pa 9,7 9,8 9,8 9,9 10,0 10,1
32 Pat 10,5 10,5 10,6 10,7 10,7 10,8
Qev 5,4 5,6 5,8 5,9 6,1 6,3
∆Pev 26,2 27,8 29,5 31,2 33,0 34,8
Pf 30,6 31,5 32,4 33,3 34,3 35,2
Pa 10,4 10,5 10,5 10,6 10,7 10,8
35 Pat 11,2 11,2 11,3 11,4 11,5 11,5
Qev 5,3 5,4 5,6 5,7 5,9 6,1
∆Pev 24,6 26,1 27,7 29,3 31,0 32,7
Pf 28,9 29,7 30,6 31,5 32,4 33,3
Pa 11,6 11,7 11,8 11,9 12,0 12,0
40 Pat 12,4 12,5 12,5 12,6 12,7 12,8
Qev 5,0 5,1 5,3 5,4 5,6 5,7
∆Pev 22,0 23,3 24,7 26,2 27,7 29,3
Pf 27,8 28,7 29,5 30,4 31,3 32,1
Pa 12,4 12,5 12,6 12,7 12,8 12,8
43 Pat 13,2 13,3 13,3 13,4 13,5 13,6
Qev 4,8 4,9 5,1 5,2 5,4 5,5
∆Pev 20,4 21,7 23,0 24,4 25,8 27,3
Pf 40,8 42,5 44,3 46,1 47,9 49,7
Pa 10,9 11,1 11,2 11,2 11,3 11,3
25 Pat 12,0 12,2 12,3 12,3 12,4 12,4
Qev 7,0 7,3 7,6 7,9 8,2 8,5
∆Pev 38,0 41,4 44,9 48,5 52,3 56,1
Pf 38,2 39,8 41,5 43,3 44,9 46,8
Pa 12,1 12,2 12,3 12,4 12,4 12,5
30 Pat 13,2 13,3 13,4 13,5 13,5 13,6
Qev 6,6 6,8 7,1 7,4 7,7 8,0
∆Pev 33,8 36,0 39,2 42,6 46,0 49,7
Pf 37,2 38,9 40,5 42,2 43,9 45,6
Pa 12,7 12,8 12,9 12,9 13,0 13,0
32 Pat 13,8 13,9 14,0 14,0 14,1 14,1
Qev 6,4 6,7 6,9 7,2 7,5 7,8
∆Pev 31,8 34,9 37,0 40,3 43,7 47,3
Pf 35,6 37,2 38,8 40,5 42,0 43,7
Pa 13,2 13,3 13,4 13,6 13,8 13,9
35 Pat 14,3 14,4 14,5 14,7 14,9 15,0
Qev 6,1 6,4 6,7 6,9 7,2 7,5
∆Pev 28,9 31,8 34,9 37,0 40,3 43,7
Pf 33,0 34,5 36,0 37,5 38,9 40,4
Pa 14,3 14,3 14,4 14,6 14,8 14,9
40 Pat 15,4 15,4 15,5 15,7 15,9 16,0
Qev 5,7 5,9 6,2 6,4 6,7 6,9
∆Pev 25,2 27,0 29,9 31,8 34,9 37,0
Pf ------
Pa ------
43 Pat ------
Qev ------
∆Pev ------
This manual suits for next models
35
Table of contents
Other CLIMAVENETA Chiller manuals
Popular Chiller manuals by other brands

Marstair
Marstair 929 Series Technical manual

KKT
KKT Compact-Line cBoxX 30 operating instructions

Carrier
Carrier 30GTN015-035 installation instructions

Johnson Controls
Johnson Controls YVAM 350 Wiring diagram

Johnson Controls
Johnson Controls York YCAL0012-0032 Start-Up Checklist

Aqua Cooler
Aqua Cooler R Series product manual