2. PULL WIRING
IMPORTANT:
1. DECK
FOUNDATION
Drill a fifth hole in the center to accommodate the conduit.
To prevent tampering, it is advisable to tack weld the
lower nuts to the threaded rod.
Drill four holes through the deck or floor for the four
3/4” threaded rods. The holes should be aligned, using
the tem- plate provided in such a way that the phone
faceplate on the unit will face in the desired direction.
Position the second plate working from below the deck.
Have another worker hold the upper plate and rods in place
from above the deck.
1.4.1 Place the second plate gasket and then the second
plate over the threaded rods.
1.4.2 Secure the second plate with nuts and washers pro-
vided. If required, readjust the nuts so that six inches of the
rods are above the top of the upper plate.
A minimum of two feet of wire must be available from the
conduit for electrical and communications wiring.
Position the first plate working from above the deck.
1.3.1 Thread a nut and washer on the end of each rod so
that approximately six inches extends beyond the base of
the washer.
1.3.2 Insert each rod through the top side of the plate, plate
gasket, and down through the four holes in the deck.
Electrical and telephone line conduit is run through the deck
and the center openings (two-inch diameter) of the upper and
lower deck plates. A minimum of four inches and a maximum of
six inches of conduit above the upper plate is required.
Deck Mount Kit Instructions
2.2 Conduit
1.1 Drill Deck Holes
1.2 Drill Conduit Hole
1.5 Secure Lower Nuts
1.3 Position Upper Deck Plate
1.4 Position Lower Deck Plate
2.1 Pull Power and Phone Line up through Conduits
NOTE: The top of the plate is the side with the tapered edge.
Wire gauge must be selected to meet code for voltage/current required for the product to
operate correctly: Minimum 14 AWG. Conduit used must comply to National Electrical Standards as
ob- served locally.
NOTE: Communications wire must be shielded phone line. The phone line must be pulled into the unit using
a separate conduit from the power. Along with a service loop of wire, as noted by the NEC standards.
CB 1 Series
Administrator Guide
GU-157-FF
SKIP if installation does not include a Deck Mount Kit
page 10 of 31
Code Blue • 259 Hedcor Street • Holland, MI 49423 USA • 800.205.7186 • www.codeblue.com