Condair 2583810 User manual

Humidication and Evaporative Cooling
2585293-K EN 2202
Gateway Board for
BACnet and LonWorks
Supplemental Installation and Operation Manual
For use with RS, EL, DL, and
ME humidifiers with
Software version 5.9.x.x and 5.10.x.x

Thank you for choosing Condair
Installation date (MM/DD/YYYY):
Commissioning date (MM/DD/YYYY):
Site:
Model:
Serial number:
Contact
Condair Ltd.
2740 Fenton Road, Ottawa, Ontario K1T3T7
TEL: 1.866.667.8321, FAX: 613.822.7964
EMAIL: na.info@condair.com, WEBSITE: www.condair.com
Proprietary Notice
This document and the information disclosed herein are proprietary data of Condair Ltd. Neither this document, nor
the information contained herein shall be reproduced, used, or disclosed to others without the written authorization
of Condair Ltd., except to the extent required for installation or maintenance of recipient's equipment.
Liability Notice
Condair Ltd. does not accept any liability due to incorrect installation or operation of the equipment or due to the
use of parts/components/equipment that are not authorized by Condair Ltd.
Copyright Notice
© Condair Ltd., All rights reserved.
Technical modications reserved

3Contents
Contents
1 Introduction 4
1.1 Notes on this addendum manual 4
1.2 Functions overview 5
2 For your safety 6
3 Network integration via the optional LonWorks and BACnet Gateway boards 8
3.1 Notes for the planning engineer 8
3.1.1 Overview 8
3.1.2 Principle Network diagrams 9
3.1.2.1 Principle BACnet network 9
3.1.2.2 Principle LonWorks network 11
3.2 Installation work 12
3.2.1 Installing the BACnet/LonWorks gateway board on the Integrated Controller 12
3.2.2 Wiring 13
3.3 Conguration 14
3.3.1 Conguring the Condair Integrated Controller 14
3.3.1.1 Setup control settings 14
3.3.1.2 Monitoring of bus communication 15
3.3.1.3 BMS Timeout and Modbus settings 16
3.3.2 Gateway conguration 17
3.3.2.1 Requirements for gateway conguration 17
3.3.2.2 Congure the IP settings 18
3.3.2.3 Modifying the BACnet conguration 23
3.4 Communication tables 26
3.4.1 DL - BACnet (Integrated Controller software version 5.9.x.x) 26
3.4.2 DL - LonWorks (Integrated Controller software version 5.9.x.x) 29
3.4.3 ME - BACnet (Integrated Controller software version 5.9.x.x and 5.10.x.x) 32
3.4.4 ME- LonWorks (Integrated Controller software version 5.9.x.x and 5.10.x.x) 35
3.4.5 RS - BACnet (Integrated Controller software version 5.9.x.x) 38
3.4.6 RS - LonWorks (Integrated Controller software version 5.9.x.x) 42
3.5 Troubleshooting 46
3.5.1 Operating trouble list 46
3.5.2 LED functions 48
4 Appendix 51
4.1 Object abbreviations 51
5 Ordering form 52

4Introduction
1 Introduction
1.1 Notes on this addendum manual
Condair devices equipped with an Integrated Controller can either be connected via the corresponding
interface on the Integrated Controller (BACnet on-board) to a BACnet IP network or a BACnet MS/TP
network or via the optional LonWorks or BACnet gateway boards (ProtoCessor gateway) to a LonWorks,
BACnet IP or BACnet MS/TP network to a building management system.
This manual describes how to install and congure the optional LonWorks and BACnet gateway boards
(see chapter 3) to connect the corresponding Condair devices to a building management system.
This addendum manual is intended for use by engineers and properly trained technical personnel. Please
read this manual thoroughly before installing and conguring the BACnet or LonWorks based network.
If you have questions after reading this documentation, please contact your Condair representative.
They will be glad to assist you.
Symbols used in this manual
CAUTION!
The catchword "CAUTION" used in conjunction with the caution symbol in the circle designates notes
in this manual that, if neglected, may cause damage and/or malfunction of the unit or other mate-
rial assets.
WARNING!
The catchword "WARNING" used in conjunction with the general caution symbol designates safety
and danger notes in this manual that, if neglected, may cause injury to persons.
DANGER!
The catchword "DANGER" used in conjunction with the general caution symbol designates safety and
danger notes in this manual that, if neglected, may lead to severe injury or even death of persons.

5Introduction
Safekeeping
Please safeguard this addendum manual in a safe place, where it can be immediately accessed. If the
equipment changes hands, the documentation must be passed on to the new operator.
If the documentation gets mislaid, please contact your Condair representative for replacement.
Language versions
This addendum manual is available in various languages. Please contact your Condair representative
for information.
1.2 Functions overview
The following table gives you an overview of the supported protocols and functions.
Optional BACnet
Gateway board
Optional LonWorks
Gateway board
BACnet IP and BACnet MS/TP BTL certied yes no
BACnet IP yes no
BACnet MS/TP Master Mode yes no
BACnet MS/TP Slave Mode yes no
LonWorks certied no yes
Remote"RS draining" yes yes
BACnet Service COV (Change of Value) yes no
Please refer to the objects tables for detailed information.

6For your safety
2 For your safety
General
Every person working with the Condair Integrated Controller must have read and understood this ad-
dendum manual, and the installation manual and operation manual of the Condair Integrated Controller,
before carrying out any work.
Knowing and understanding the contents of the manuals is a basic requirement for protecting the person-
nel against any kind of danger, to prevent faulty operation, and to operate the unit safely and correctly.
All icons, signs and markings applied to the unit must be observed and kept in readable state.
Qualication of personnel
All work described in this addendum manual may only be carried out by specialists who are well
trained and adequately qualied and are authorised by the customer.
For safety and warranty reasons any action beyond the scope of this manual must be carried out only
by qualied personnel authorised by the manufacturer.
It is assumed that all persons working with the Condair Integrated Controller are familiar and comply
with the appropriate local regulations on work safety and the prevention of accidents.
Intended use
The optional LonWorks or BACnet gateway boards are intended exclusively for connecting the Condair
Integrated Controller to a LonWorks or BACnet based network. Any other type of application, without
the written consent of the manufacturer, is considered as not conforming with the intended purpose and
may lead to the Condair Integrated Controller becoming dangerous.
Operation of the equipment in the intended manner requires that all the information contained in this
addendum manual as well as in the installation manual and operation manual of the Condair
Integrated Controller are observed.
Danger that may arise from the Condair Integrated Controller
DANGER!
Risk of electric shock!
The electrical compartment where the Integrated Controller is located may have live mains
voltage connected for other uses of the device. Live parts may be exposed when the control
unit is open. Touching live parts may cause severe injury or danger to life.
Prevention: Before commencing any work on the control unit disconnect the mains supply voltage to
the humidier via the electrical isolator in the mains supply line, and secure electrical isolator in "Off"
position against inadvertent switching on.

7For your safety
Safety reporting
All persons working with the Condair Integrated Controller are obliged to report any alterations to the
system that may affect safety to the owner without delay and to secure such systems against ac-
cidental power-up.
Prohibited modications to the unit
No modications must be undertaken on the optional LonWorks or BACnet gateway boards and on
the Condair Integrated Controller without the express written consent of the manufacturer.
For the replacement of defective components use exclusively original accessories and spare parts
available from your Condair representative.

8Network integration via the optional LonWorks and BACnet Gateway boards
3 Network integration via the optional LonWorks and
BACnet Gateway boards
3.1 Notes for the planning engineer
3.1.1 Overview
The optional LonWorks or BACnet gateway boards allow the integration of the Condair Integrated Con-
troller into a BACnet IP, BACnet MS/TP or a LonWorks network. The optional LonWorks or BACnet
gateway boards feature a serial-interface gateway which converts the information from the host RTU
Modbus protocol to a specied secondary protocol.
Important: Please note that the gateway board is congured for the latest software version of the In-
tegrated Controller. To guarantee correct data communication it is therefore mandatory to update the
software of the Integrated Controller to the latest version before installing the gateway board. Please
contact your Condair distributor regarding a software update of the Integrated Controller.
The following protocol options are available and must be specied when ordering:
Part Number Protocols Part Description
2583810 BACnet IP BMS Set Master BACnet IP ME
2583813 BACnet MS/TP BMS Set Master BACnet MS/TP ME
2583808 LonWorks BMS Set Master LonWorks ME
2583809 BACnet IP BMS Set Master BACnet IP RS
2583812 BACnet MS/TP BMS Set Master BACnet MS/TP RS
2583807 LonWorks BMS Set Master LonWorks RS
2582291 BACnet IP BMS Set Master BACnet IP DL
2583811 BACnet MS/TP BMS Set Master BACnet MS/TP DL
2582290 LonWorks BMS Set Master LonWorks DL
2586239 BACnet IP BMS Set Master BACnet IP EL
2586240 BACnet MS/TP BMS Set Master BACnet MS/TP EL
2587508 LonWorks BMS Set Master LonWorks EL
Please refer to the BACnet object or Lonworks SNVT tables in chapter 3.4 for detailed information re-
garding the available read out and settings functions.

9Network integration via the optional LonWorks and BACnet Gateway boards
3.1.2 Principle Network diagrams
3.1.2.1 Principle BACnet network
The principle diagram below shows the connection of the Condair Integrated Controller to an Ethernet
network.
Principle BACnet IP network
Abb. 1: Principle BACnet IP network
Ethernet (BACnet IP)
CAT6A cable (or higher) with RJ45 termination
BACnet gateway board
(connected to integrated controller
inside control unit)

10 Network integration via the optional LonWorks and BACnet Gateway boards
Principle BACnet MS/TP network
Abb. 2: Principle BACnet MS/TP network
Ethernet (BACnet IP)
GND
+
–
BACnet MS/TP to BACnet IP
Router RS485 Network (BACnet MS/TP)
Shielded twisted-pair cable:
– 120 Ohm impedance
– Terminate shield at one end only
BACnet gateway board
(connected to integrated controller
inside control unit)

11Network integration via the optional LonWorks and BACnet Gateway boards
3.1.2.2 Principle LonWorks network
This principle diagram below shows the connection of the Condair Integrated Controller to a LonWorks
network via a shielded twisted-pair cable.
Abb. 3: Principle LonWorks network
–+
Network via shielded
twisted-pair cable
LonWorks
Device
LonWorks
Device
LonWorks
Router
Shielded twisted-pair cable:
– 120 Ohm impedance
– Terminate shield at one end only
LonWorks Gateway board
(connected to integrated controller
inside control unit)

12 Network integration via the optional LonWorks and BACnet Gateway boards
3.2 Installation work
3.2.1 Installing the BACnet/LonWorks gateway board on the Integrated Controller
1. Isolate power supply to the controller unit.
2. Remove the front cover of the control unit.
CAUTION!
Electronic components are very sensitive to electrostatic discharge. Before proceeding with the
next step, appropriate measures (ESD-protection) must be taken to prevent damage to electronic
components. A wrist strap should be worn to connect the maintenance specialist with a common
ground point. For more information, refer to ANSI/ESD-S20.20.
3. Open the control unit inner door.
4. Fix BACnet or LonWorks gateway board to the TTL interface on the Condair Integrated Controller.
Important: Ensure pin alignment when xing.
5. Remove Jumper "J7".
Abb. 4: Installing the BACnet/LonWorks gateway board on the integrated controller (ME control
module shown).
J7
Remove Jumper
from "J7"
TTL interface on Integrated Controller for
connecting the BACnet or LonWorks gateway board
BACnet or LonWorks gateway board

13Network integration via the optional LonWorks and BACnet Gateway boards
3.2.2 Wiring
1. Lead the network cable through the rectangular cable lead-through into the control unit. Inside the
control unit run the cable to the BACnet or LonWorks gateway board, respectively.
2. Connect network cable according to the following wiring diagrams.
BACnet
Abb. 5: BACnet IP network connection
Abb. 6: BACnet MS/TP network connection
LonWorks
Abb. 7: LonWorks network connection
To network via CAT6A cable (or
higher) with RJ45 termination
To network via shielded twisted-pair cable:
– 120 Ohm impedance
– Terminate shield at one end only
To network via shielded twisted-pair cable:
– 120 Ohm impedance
– Terminate shield at one end only
Net (–)
Net (+)
+
–
GND

14 Network integration via the optional LonWorks and BACnet Gateway boards
3.3 Conguration
After wiring connections have been completed, the Condair Integrated Controller needs to be setup to
operate and communicate through its optional BACnet or LonWorks gateway board. This setup includes
the settings in the "Control Settings" and the "Communication" submenu of the Condair Integrated
Controller unit and the Gateway conguration.
3.3.1 Conguring the Condair Integrated Controller
3.3.1.1 Setup control settings
By default the Condair Integrated Controller is congured to operate on a hardwired analog control signal
from an external humidity controller or a humidity sensor (if internal P or PI controller is used) connected
to the driver board inside the control unit.
Note: If you want the Condair Integrated Controller to be controlled via a hardwired analog control signal
set "Signal Source" to "Analog" and set the other control settings as required (see "Operation Manual"
of the corresponding device for details).
If you want to control the Condair Integrated Controller entirely via the network through the optional
BACnet or LonWorks gateway board the "Control Settings" must be adjusted as follows:
1. Close control unit and switch it on.
2. Select "Control Settings" submenu as shown below.
Password: 0335
3. Set control settings as follows (see rightmost screen):
Signal Source: Modbus
System Mode: Humidifying or Cooling (only by ME)
Control Mode: Demand (if you use a external demand control signal)
RH P (if you use a sensor signal and proportional controller)
RH PI (use a sensor value and proportional-integral controller)
Note: see Humidier Operation Manual for details on control settings.

15Network integration via the optional LonWorks and BACnet Gateway boards
3.3.1.2 Monitoring of bus communication
The monitoring of the bus communication described below only takes place if the "Source" parameter
in the "Control Settings" menu is not set to "Analog".
As soon as the signal is transmitted via a BACnet or LonWorks gateway board, communication via the
bus system is also monitored. The control signal must be periodically updated within the time set in
"BMS Timeout".
If the control signal is not updated within the set time, warning "W35 - BMS Timeout" will be triggered
and the humidication will be stopped until a valid signal is returned.
This monitoring is intended to prevent the humidier from humidifying with the last transmitted value in
the event of a bus failure.
Note: The gateway board transfers the control signal to the humidier only if the value changes!

16 Network integration via the optional LonWorks and BACnet Gateway boards
3.3.1.3 BMS Timeout and Modbus settings
To allow the Condair Integrated Controller to be controlled via the BMS through the optional BACnet or
LonWorks gateway board the Condair Integrated Controller must be congured as follows:
1. Switch on control unit (if not already switched on).
2. Select "Communication" submenu as shown below.
Password: 0335
3. Select "BMS Timeout" tab and set BMS Timeout to the desired values:
Factory setting: 300 s
Setting range: 1 - 300 s
4. Select "Modbus Parameter" tab and set Modbus settings as follows (see rightmost screen):
Modbus: Modbus/RTU
Modbus Address: 10
Parity: Even
Baud Rate: 9600
Register Sequence: MSR rst
Important! Please note that the gateway board is communicating with the Integrated Controller of the
device via the Modbus RTU protocol. When using a gateway board the "BACnet" function in the "Con-
guration > Communication" submenu must be deactivated!

17Network integration via the optional LonWorks and BACnet Gateway boards
3.3.2 Gateway conguration
The protocol conguration is made at the factory, prior to nal testing. The following values are set
ex factory (adjustable values see chapter 3.3.2.2 and chapter 3.3.2.3):
BACnet
Protocol Baud rate BACnet MS/TP
MAC Address
Node ID Parity
BACnet IP 10 / 100 BaseT --- DL: 300
RS: 710
ME: 410
EL: 220
---
BACnet MS/TP
Master
9600 Baud 127 1001 None
LonWorks
Protocol Baud rate Lonmark Objects
LonWorks 78125 bps #0 Node #520 Analog Input * #521 Analog Output
* The Condair RS consists of two analog input objects (Unit A and unit B). The second analog input
object holds only the SNVT's of unit B.
3.3.2.1 Requirements for gateway conguration
Hardware Requirements
A PC with web browser that connects over Ethernet on port 80 and a Ethernet cable to establish the
connection between Computer/Laptop and BACnet or LonWorks gateway board.
PC Software Requirements
One of the following web browsers must be used:
– Mozilla Firefox 13.0 and up
– Microsoft Internet Explorer 8 and up
– Google Chrome 19.0 and up
– Opera 11 and up
– Microsoft Edge
Please note that the computer and network rewalls must be opened for Port 80 to allow FS-GUI to
function.

18 Network integration via the optional LonWorks and BACnet Gateway boards
3.3.2.2 Congure the IP settings
For BACnet and LonWorks application, an IP address and the subnet mask must be assigned to the
BACnet/LonWorks gateway board in order to access it. The IP address and subnet mask may be as-
signed at the factory or can be modied at any time via the integrated FS-GUI (Fieldserver Graphic User
Interface) of the gateway board.
Ex factory the gateway board is congured to the following default settings:
IP address 10.232.72.172
Subnet mask 255.255.0.0
Default gateway 10.232.72.1
To congure a new IP address, subnet mask and default gateway via the integrated FS-GUI of the
gateway board proceed as follows:
1. Connect the gateway board to a PC using an Ethernet cross-over cable or directly to the network
using a straight cable.
2. Make sure your PC is in the same IP network as the gateway board (default IP settings see table
above); otherwise assign a static IP address (e.g. 10.232.72.100) to your PC.
3. Switch on Condair Integrated Controller unit in order to power up the gateway board.
4. Open your internet browser and enter the IP address of the gateway board (by default ex factory
10.232.72.172), then conrm the entry with the Enter key.

19Network integration via the optional LonWorks and BACnet Gateway boards
5. Depending on the FS-GUI version either the start screen or the login screen appears:
• If the start screen appears: Press the <Diagnostics & Debbuging> button at the bottom right of
the screen.
• If the login screen screen appears: Enter "admin" as the username and the password (can be
found on the sticker of the gateway board). Then conrm your entries with the <Log In> button.
Note: The password should later be changed under "Setup > User Management / Password"
(see step 6).
Note: After 5 unsuccessful attempts to enter the password, access will be blocked for 10 minutes!
The FS-GUI will be started.

20 Network integration via the optional LonWorks and BACnet Gateway boards
6. Select the menu point "Setup > User Management / Password" in the "Navigation Tree". Enter
the new password and conrm it with the <Conrm> button.
CAUTION!
Remember the new password. The password on the sticker of the gateway board is no longer
valid after the alteration.
7. Select the menu point "Setup > Security" in the "Navigation Tree" in order to select the security
mode the FS-GUI should use.
CAUTION!
The gateway board is factory congured for HTTP protocol. It is strongly recommended to change
this setting to an HTTPS protocol (HTTPS = encrypted, secure connection)!
Select the desired protocol type and then press <Save>.
This manual suits for next models
11