Condair CONTROLS Series User manual

2597793-0 EN 1908
Humidication and Evaporative Cooling
READ AND SAVE THESE INSTRUCTIONS
Addendum manual for the configuration
of the optional Condair MN KNX Gateway
KNX GATEWAY
KNX

Thank you for choosing Condair
Installation date (MM/DD/YYYY):
Commissioning date (MM/DD/YYYY):
Site:
Model:
Serial number:
Proprietary Notice
This document and the information disclosed herein are proprietary data of Condair Group AG. Neither this docu-
ment, nor the information contained herein shall be reproduced, used, or disclosed to others without the written
authorisation of Condair Group AG, except to the extent required for installation or maintenance of recipient's
equipment.
Liability Notice
Condair Group AG does not accept any liability due to incorrect installation or operation of the equipment or due
to the use of parts/components/equipment that are not authorised by Condair Group AG.
Copyright Notice
© Condair Group AG, All rights reserved.
Technical modications reserved.

3Contents
Contents
1 Introduction 4
1.1 Notes on this addendum manual 4
2 For your safety 5
3 KNX Gateway 7
3.1 General information 7
3.2 Connecting the KNX Gateway to a KNX network 8
3.3 Download the "MN Option KNX.KNXPROJ" project le 8
3.4 Importing the project le "MN Option KNX.KNXPROJ" into the ETS5 software 9
4 Communication table 10
4.1 Data points 10
4.2 Parameter 12

4Introduction
1 Introduction
1.1 Notes on this addendum manual
Subject of this addendum manual is the electrical installation and the conguration of the optional Cond
air MN KNX gateway.
This addendum manual is intended for use by engineers and properly trained technical personnel. Please
read this manual thoroughly before conguring the optional Condair MN KNX gateway.
If you have questions after reading this documentation, please contact your Condair representative.
They will be glad to assist you.
Symbols used in this manual
CAUTION!
The catchword "CAUTION" used in conjunction with the caution symbol in the circle designates notes
in this addendum manual that, if neglected, may cause damage and/or malfunction of the unit or
other material assets.
WARNING!
The catchword "WARNING" used in conjunction with the general caution symbol designates safety
and danger notes in this addendum manual that, if neglected, may cause to injury to persons.
DANGER!
The catchword "DANGER" used in conjunction with the general caution symbol designates safety and
danger notes in this addendum manual that, if neglected, may lead to severe injury or even death
of persons.
Safekeeping
Please safeguard this addendum manual in a safe place, where they can be immediately accessed. If
the equipment changes hands, the documentation must be passed on to the new operator.
If the documentation gets mislaid, please contact your Condair representative.
Language versions
This operation manual is available in various languages. Please contact your Condair representative
for information.

5For your safety
2 For your safety
General
Every person who has been assigned to electrically install and congure the optional KNX gateway of
the Condair MN must have read and understood this addendum manual.
Knowing and understanding the contents of this addendum manual is a basic requirement for protecting
the personnel against any kind of danger, to prevent faulty installation, operation and conguration, and
to operate the Condair MN safely and correctly.
Qualication of personnel
All work described in this addendum manual may only be carried out by persons who are well trained
and adequately qualied.
For safety and warranty reasons any action beyond the scope of this manual must be carried out only
by qualied personnel authorised by Condair Group AG.
It is assumed that all persons working on the optional KNX gateway and on the Condair MN are familiar
and comply with the appropriate regulations on work safety and the prevention of accidents.
The optional KNX gateway and the Condair MN may not be used by persons (including children) with
reduced physical, sensory or mental abilities or persons with lacking experience and/or knowledge.
Children must be supervised to make sure that they do not play with the optional KNX gateway and the
Condair MN.
Intended use
The optional KNX gateway is intended exclusively for controlling and querying of operating values
of the control software of the Condair MN according to the instructions in this manual. Any other
type of application, without the written consent of Condair Group AG, is considered as not conforming with
the intended purpose and may lead to the Condair MN becoming dangerous and will void any warranty.
Operation of the equipment in the intended manner requires that all the information contained in this
addendum manual, in the additional manuals to the Condair MN as well as in the separate docu-
mentations of the components used together with the Condair MN are observed (in particular
all safety instructions).

6For your safety
Danger that may arise from the Condair MN:
DANGER!
Risk of electrocution
The Condair MN's central unit runs on mains power. If the central unit is open, live parts may
be touched. Touching live parts may cause severe injury or death.
For this reason: Before starting work on the central unit, disconnect it from the mains power
supply (remove plug from socket).
Warning!
UV-C radiation
A UV lamp is built into the Condair MN's central unit. In principle this should pose no risks, as
it is installed in a radiation-proof housing. If the UV lamp is operated outside of this housing,
harmful UV-C radiation may be released. This may cause damage to the eyes and skin.
For this reason: the UV lamp must never be operated outside of the protective housing. The
central unit must be switched off and disconnected from the mains power supply (remove the
plug from the socket) before the central unit is opened.
Preventing unsafe operation
If it is suspected that safe operation of the optional KNX gateway and the Condair MN is no longer
possible, the Condair MN should immediately be shut down and secured against accidental power-
up. This can be the case under the following circumstances:
– if the optional KNX gateway and/or the Condair MN is/are damaged
– if the electrical installations are damaged
– if the optional KNX gateway and/or the Condair MN is/are no longer operating correctly
– if connections and/or piping are not sealed
All persons working with the optional KNX gateway and the Condair MN must report any alterations to
the devices that may affect safety to the owner without delay.
Prohibited modications to the unit
No modications must be undertaken on the optional KNX gateway and the Condair MN without the
express written consent of Condair.

7KNX Gateway
3 KNX Gateway
3.1 General information
The KNX Gateway BAOS 870 from Weinzierl is used to integrate the Condair MN into a KNX installa-
tion. The gateway will be installed by a service engineer from Condair. The KNX Integrator will thus nd
an already installed gateway.
KNX Gateway
Fig. 1: KNX gateway installed

8KNX Gateway
3.2 Connecting the KNX Gateway to a KNX network
KNX
+
-
+
-
KNX
KNX Gateway
Fig. 2: Connection of the KNX Gateway to a KNX network
The KNX Gateway is connected to the KNX network according to the diagram above.
3.3 Download the "MN Option KNX.KNXPROJ" project le
The settings on the gateway are not ofcially certied for the use of the Condair MN, for this reason a
corresponding project le ("MN Option KNX.KNXPROJ") must be downloaded from the Condair HumiLife
homepage (condairhumilife.com > Service > Download).
Note: Please check the actuality of the project in the download area of the Condair HumiLife homepage
(condairhumilife.com) before each commissioning.

9KNX Gateway
3.4 Importing the project le "MN Option KNX.KNXPROJ" into the ETS5
software
1. Start the ETS5 software on your labtop connected to the KNX network.
2. Open the project le "MN Option KNX.KNXPROJ" which you have previously downloaded from the
Condair HumiLife website.
3. After you have opened the project le "MN Option KNX.KNXPROJ" with the ETS5 software, the
device "KNX BAOS 82x 87x" appears. This device forms the interface between the Condair MN and
the existing KNX home automation system (see Fig. 3).
Fig. 3: Download the "MN Option KNX.KNXPROJ" project le
4. Drag or copy the interface from the MN Option KNX project into your existing project (see Fig. 4).
Fig. 4: Example of an existing project
5. Now you can create the group addresses according to the rooms or zones and link them with other
KNX components.
Note: The group addresses can be freely selected by the integrator, as certain addresses may
already be assigned to existing installations.

10 Communication table
4 Communication table
4.1 Data points
The following table shows which object functions can be linked with the KNX home automation via the
group addresses of the "MN option KNX.KNXPROJ":
Data point Object function Description Range Type
1Name Area 1 Name of zone 1 DPT 16
2Name Area 2 Name of zone 2 DPT 16
…Name Area [n] Name of zone [n] DPT 16
20 Name Area 20 Name of zone 20 DPT 16
32 System Name String Name of the MN Condair DPT 16
33 Humidity Area 1 Actual humidity value zone 1 0 - 100% DPT 09
34 Humidity Area 2 Actual humidity value zone 2 0 - 100% DPT 09
…Humidity Area [n] Actual humidity value zone [n] 0 - 100% DPT 09
52 Humidity Area 20 Actual humidity value zone 20 0 - 100% DPT 09
53 Temperature Area 1 Actual temperature value zone 1 100 +200°C DPT 09
54 Temperature Area 2 Actual temperature value zone 2 100 +200°C DPT 09
…Temperature Area [n] Actual temperature value zone [n] 100 +200°C DPT 09
72 Temperature Area 20 Actual temperature value zone 20 100 +200°C DPT 09
73 Setpoint Off Area 1 Humidication level 0 "Humidica-
tion Off" of zone 1
0 = inactive
1 = active
DPT 01
74 Setpoint Off Area 2 Humidication level 0 "Humidica-
tion Off" of zone 2
0 = inactive
1 = active
DPT 01
…Setpoint Off Area [n] Humidication level 0 "Humidica-
tion Off" of zone [n]
0 = inactive
1 = active
DPT 01
92 Setpoint Off Area 20 Humidication level 0 "Humidica-
tion Off" of zone 20
0 = inactive
1 = active
DPT 01
93 Setpoint Low Area 1 Humidication level 1 "Humidica-
tion Low" of zone 1
0 = inactive
1 = active
DPT 01
94 Setpoint Low Area 2 Humidication level 1 "Humidica-
tion Low" of zone 2
0 = inactive
1 = active
DPT 01
…Setpoint Low Area [n] Humidication level 1 "Humidica-
tion Low" of zone [n]
0 = inactive
1 = active
DPT 01
112 Setpoint Low Area 20 Humidication level 1 "Humidica-
tion Low" of zone 20
0 = inactive
1 = active
DPT 01
113 Setpoint Norm Area 1 Humidication level 2 "Humidica-
tion Mid" of zone 1
0 = inactive
1 = active
DPT 01
114 Setpoint Norm Area 2 Humidication level 2 "Humidica-
tion Mid" of zone 2
0 = inactive
1 = active
DPT 01
…Setpoint Norm Area [n] Humidication level 2 "Humidica-
tion Mid" of zone [n]
0 = inactive
1 = active
DPT 01
132 Setpoint Norm Area 20 Humidication level 2 "Humidica-
tion Mid" of zone 20
0 = inactive
1 = active
DPT 01
133 Setpoint High Area 1 Humidication level 3 "Humidica-
tion High" of zone 1
0 = inactive
1 = active
DPT 01
134 Setpoint High Area 2 Humidication level 3 "Humidica-
tion High" of zone 2
0 = inactive
1 = active
DPT 01

11Communication table
Data point Object function Description Range Type
…Setpoint High Area [n] Humidication level 3 "Humidica-
tion High" of zone [n]
0 = inactive
1 = active
DPT 01
152 Setpoint High Area 20 Humidication level 3 "Humidica-
tion High" of zone 20
0 = inactive
1 = active
DPT 01
153 Auto Modus Area 1 1) Humidication level 4 "Auto
mode" of zone 1 (Control home
automation)
0 = inactive
1 = active
DPT 01
154 Auto Modus Area 2 1) Humidication level 4 "Auto
mode" of zone 2 (Control home
automation)
0 = inactive
1 = active
DPT 01
…Auto Modus Area [n] 1) Humidication level 4 "Auto
mode" of zone [n] (Control home
automation)
0 = inactive
1 = active
DPT 01
172 Auto Modus Area 20 1) Humidication level 4 "Auto
mode" of zone 20 (Control home
automation)
0 = inactive
1 = active
DPT 01
173 Setpoint Area 1 Humidication level of zone 1 0 = Off
1 = Humidication Low
2 = Humidication Mid
3 = Humidication High
4 = Auto mode
DPT 05
174 Setpoint Area 2 Humidication level of zone 2 0 = Off
1 = Humidication Low
2 = Humidication Mid
3 = Humidication High
4 = Auto mode
DPT 05
…Setpoint Area [n] Humidication level of zone [n] 0 = Off
1 = Humidication Low
2 = Humidication Mid
3 = Humidication High
4 = Auto mode
DPT 05
192 Setpoint Area 20 Humidication level of zone 20 0 = Off
1 = Humidication Low
2 = Humidication Mid
3 = Humidication High
4 = Auto mode
DPT 05
193 External Value Area 1 Setpoint setting by home automa-
tion in auto mode (humidication
level 4) of the zone 1
20 - 80% DPT 09
194 External Value Area 2 Setpoint setting by home automa-
tion in auto mode (humidication
level 4) of the zone 2
20 - 80% DPT 09
…External Value Area [n] Setpoint setting by home automa-
tion in auto mode (humidication
level 4) of the zone [n]
20 - 80% DPT 09
212 External Value Area 20 Setpoint setting by home automa-
tion in auto mode (humidication
level 4) of the zone 20
20 - 80% DPT 09
245 System Name Number Serial number of the Condair MN DPT 12
246 Number of Areas Number of existing zones 1 - 20 DPT 05
247 Filter Change Necessary Message "Filter Change Neces-
sary", the lter of the device is
exhausted and must be replaced
0 = OK
1 = Replacement required
DPT 01
248 Service Necessary Collective message "Service"
The unit needs servicing, contact
customer service
0 = OK
1 = Service required
DPT 01

12 Communication table
Data point Object function Description Range Type
249 Cloud Connection Error No network connection available 0 = OK
1 = Fault
DPT 01
250 System Error Collective message "Fault", con-
tact customer service
0 = OK
1 = Fault
DPT 01
1) The Auto Mode can only be selected via the KNX interface. If a zone is in Auto Mode, no other humidication level can be
selected in the display of the Condair MN. Resetting the auto mode (and thus activating the display input) is only possible
via the KNX interface by selecting a different humidication level (0 3).
4.2 Parameter
Adjustable interval times (parameters 1 to 6) for the corresponding object functions:
Parameter Name Description Standard value Range
1Setpoint Interval Transmission interval of the humidica-
tion levels and humidity setpoints
(Data points XY)
1
0 = Off (Standard)
1 = 10s
2 = 1min
3 = 5min
4 = 30min
5 = 2h
6 = 8h
7 = 24h
>7 = Off
2Humidity Interval Transmission interval of the actual humid-
ity values (Data points XY)
2
3Temperature Interval Transmission interval of the actual tem-
perature values
(Data points XY)
3
4 Area Name Interval Transmission interval of the zone names
(Data points XY)
2
5System Name Interval Transmission interval of the system
names (Data points XY)
1
6 System State Interval Transmission interval of the system status
(Data points XY)
1

Notes

Notes