Continental Refrigerator E-Access WI2427LF User manual

Continental E●Access Control Systems
Installation Instructions
for 1 Door Systems
Document Number: 100116-CAE
Installation Instructions for 1 Door Systems – November 2022 Page 1
Reference: WI242 LF

Table of Contents
Notifications
Approvals....................................................3
Notice.........................................................3
Introduction
Access Control Overview...........................4
System Overview........................................4
System Specifications
Installation of 1 Door Systems
Installation Check List.................................6
Locating the Controller for Installation........6
Mounting 1DC Systems
Controller Features – 1 Door Systems
Controller Inputs.........................................8
Controller Wiring Harnesses.......................9
Input Wiring..............................................10
14 Pin Reader Harness............................10
Controller Outputs & Power Input.............14
Output Wiring Requirements....................15
10 Position Power Harness......................15
Powering On and Connecting to a Network
Preparing for the Network.........................1
Connecting to the Network.......................19
Adding Clients to Systems........................19
Smart IP Finder........................................21
Trouble Shooting
Testing, Maintenance and Service
Parts List
Contact & Warranty Information
Installation Instructions for 1 Door Systems – November 2022 Page 2

Notifications
Copyright
Copyright © 2022, all rights reserved. No part of this document may be reproduced, copied,
adapted or transmitted in any form without written permission.
Approvals
This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates and can radiate radio frequency energy and if not
installed and used in accordance with the manual, may cause harmful interference. Operation of
this equipment in a residential area is likely to cause harmful interference in which case the user
will be required to correct the interference at their own expense.
This Access Control System is compliant with Level I UL 294 listed devices and must be
installed in a secure, controlled location.
Notice
This manual contains information regarding the basic installation and configuration of the
browser-based Access Control System. It must be read and completely understood before
installation or operation.
It is intended that this unit will be installed by persons trained and qualified to install access
control systems and has the skills and knowledge working with electrical circuits and safety
codes. Important safeguards and instructions in this manual cannot cover all possible situations
and conditions that occur during installation and use and it must be understood that common
sense and caution must be exercised by the person(s) installing, maintaining and operating the
equipment.
Installations must conform to all national and local building and electrical codes.
This manual is for installing 1 Door Systems;
Model 1DC.
Installation Instructions for 1 Door Systems – November 2022 Page 3

ntroduction
Access Control Overview
Access Control is the selective restriction to a place or resource such as a property, building or
room to authorized persons and is a matter of who, where, and when. An access control system
is used to automate access control using credentials, credential readers, electric door locks and
other devices. Administrators configure the system to determine who is allowed to enter or exit,
where they are allowed to exit or enter, and when they are allowed to enter or exit. When access
is granted, the door is unlocked for a predetermined time and transaction is recorded. When
access is denied, the door remains locked and the attempted access is recorded. Administrators
can then run reports on the recorded transactions to review activity for selected dates and times.
System Overview
Controller models are available in variety of configurations starting from 1 Door models that
require a separate power supply to 2 & 4 Door models that include an integrated power supply
for the controller and door lock power. Most models can be ungraded after installation with
enhanced features, such as enhanced reporting or more users, using software license keys. All
controllers include tamper and power fault inputs, in and out readers, request to exit and door
position inputs for each door and auxiliary inputs and outputs. All controllers are designed to be
connected to a network using an Ethernet RJ45 connector and configured using the integrated
web server.
Controllers can be configured as either a server or a client. All systems require a server
controller. Some systems have the ability to add additional client controllers to increase the
number of doors, inputs or outputs or control elevators. The software license key is used by the
controller to determine if it is a server or a client. After logging in, the license information about a
can be determined by clicking on the license icon at the bottom of the web page.
Certain models offer a mobile APP that can be used to setup and configure, view logs, lock and
unlock doors and activate threat levels. In addition, some systems also offers a cloud service
that provides a portal where a users or dealer can log into and manage one or many systems
securely.
Client controllers communicate with the server controller via the local area network and are
configured through the server using a web browser on PC connected to the network. Once the
server or client controller is configured, they will function without a network connection or the
PC. The network and PC is only required for setup, configuration and reporting.
Installation Instructions for 1 Door Systems – November 2022 Page 4

System Specifications
General Specifications
Operating System Embedded Linux
Transactions > 60 per Second
Power Requirements (excluding door locks) Regulated 12VDC @ 2A, Class 2 (not supplied)
Operating Temperature 50ºF to 95ºF (10ºC to 35ºC)
Plastic Enclosure Size (W x H x D) 3.2 x 3.0 x 1.3 in (81 x 8 x 32 mm)
Metal Enclosure Size (W x H x D) 4.25 x 4.25 x 2.0 in (108 x 108 x 50mm)
Model 1DC & 1DM
Standby Power Requirement 350mA @ 12V
Number of Doors 2 Total, One In & One Reader
Readers (Wiegand) 2 Total, One In & One Out Reader
Reader Power 300 mA @ 12V Max per Reader
600 mA @ 12V Max per System
Request to Exit (REX) Input 1
Door Position (status) Input 1
Auxiliary Input 1
Tamper Digital Input 1
Power Fault Digital Input 1
Door Lock Output 1 Form C Relay, 24V @ 1.0A
Auxiliary Output 1 Form C Relay, 24V @ 1.0A
UL294 7th Edition Rating
Destructive Attack Line Security Endurance Standby Power
Single Point
Locking Device
with Key Locks
Level I Level I Level IV Level I Level I
Installation Instructions for 1 Door Systems – November 2022 Page 5

nstallation of 1 Door Systems
nstallation Check List
The list below provides a logical sequence for installing a system. This list cannot cover all
possible situations and conditions that occur during installation and use and it must be
understood that common sense and caution must be exercised by the person(s) installing,
maintaining and operating the equipment.
✔Calculate the systems power requirement by adding up the power required
for each device connected to the system to make sure the required power
can be provided by the system.
✔Mount the controller in a secure, controlled location
✔Connect the inputs and outputs
✔Connect the readers
✔Connect the door locks and auxiliary outputs
✔Connect power to the controller using a dedicated12 VDC, 2 AMP UL294B
listed power supply. Connect the power supply to an unswitched, grounded
outlet
✔Obtain an IP address, Subnet Mask, DNS and other information from the
network administrator
✔Configure the controller's network settings
✔Connect the controller to the local area network and apply license
✔Add optional license keys to upgrade features such as more doors, cloud-
based management, etc.
✔Turn on services such as mobile app, cloud-based management, backup,
time server, etc.
Locating the Controller for nstallation
Choose a centrally located, secure, clean and dry area near an AC power source. Avoid
mounting the controller within 6 feet of any equipment that may generate electrical interference.
NOTICE: The power supply used for the controller must only
be connected to an unswitched grounded 115 VAC outlet. If
an unswitched outlet is not available or within 5 feet of the
controller mounting location have a licensed electrician install
an outlet per local codes. All wiring must be in accordance with
the National Electrical Code NPFA 70 and all local codes. For
UL installations the maximum Ethernet cable length is 98.5
feet (30 meters).
NOTE: This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions: (1) this
device may not cause harmful interference and (2) this device
must accept any interference received including interference
that may cause undesired operation.
Installation Instructions for 1 Door Systems – November 2022 Page 6

Mounting 1DC Systems
Using the provided mounting bracket, the 1 door controller can be mounted vertically or
horizontally in a UL listed enclosure with an integrated tamper switch, that is located in a secure
location. The aluminum heat sink should face away from the mounting surface with a minimum
of 1 inch (25.4 mm) of clearance above the heat sink. The temperature in the mounting location
must be within the system's specified limits. When running wires through knockouts in
enclosures, install bushings or conduit connectors as needed to protect wires from damage.
1. Run all wires to the controller's location and label the wires according to their use.
2. Locate the enclosure for the 1 door controller on the wall and level. Mark the mounting
holes on the wall and remove the enclosure and install anchors appropriate for the type
of wall and mounting conditions.
3. DO NOT DR LL the mounting holes while the enclosure is in place on the wall. Dust and
debris from drilling will contaminate and damage the electronics.
4. Partially insert mounting screws into the top two mounting holes and hang the enclosure
on the screws. Check for level, insert the lower screws and tighten all four mounting
screws.
5. Using the provided mounting bracket as a template, locate the bracket in the enclosure
and mark the location of the mounting screws. The keyholes in the bracket are sized for
#6 pan head self taping screws. Drill the holes for the mounting screws and partly thread
the screws into the holes. Clean any debris from drilling to prevent damage to the
electronics. Place the controller into the mounting bracket and hang on the mounting
screws. Check for level and tighten the mounting screws.
6. Run the wires through the knockout holes and connect to the appropriate harnesses (see
following sections of the manual for wiring details).
. Connect the tamper switch to the controller's tamper inputs.
NOTICE: This equipment includes electronic components that
are sensitive to static electricity. Make sure to discharge by
touching an earth ground before handling this equipment.
NOTE: When locating the controller choose a centrally located
secure clean and dry area. Avoid mounting the controller within
6 feet (2 meters) of any equipment that generates electrical
interference.
Installation Instructions for 1 Door Systems – November 2022 Page
#6 Mounting
Screw
#6 Mounting
Screw
1 Door
Controller
Mounting
Bracket
1 Door
Controller

Controller Features – 1 Door Systems
The following shows the controller's features and wiring components.
Controller nputs
Controllers can monitor door position, request to exit and auxiliary (general purpose) inputs. All
inputs are assigned default states that can be modified as needed through the user interface.
The table below shows the default state for each of the inputs.
nput Type Default State
Door Position (status) Inputs Disabled
Request to Exit Inputs Normally Open, Momentary, Unsupervised
Auxiliary Inputs Normally Open, Momentary, Unsupervised
Tamper Normally Open, Momentary, Unsupervised
Power Fault Normally Open, Momentary, Unsupervised
Installation Instructions for 1 Door Systems – November 2022 Page 8
HEAT SINK
ETHERNET
*HARDWARE
RESET
*IP RESET
*FACTORY
DEFAULT
POWER
HARNESS
CONNECTOR
READER
HARNESS
CONNECTOR
USB – FOR
DATA BACKUP
DEVICE ONLY

nput Circuit Configurations
The table below shows the different input configurations. These types can be independently
configured for each input by the user.
Unupervised Unsupervised
Normally Open Normally Open
Note: Use 1K Ohm Resistor
Normally Closed Normally Closed
Controller Wiring Harnesses
The controller is provided with two plug-in wiring harnesses for connecting field wiring. The
harnesses are color coded and marked with labels to indicate the proper connection for field
wiring.
The Minimum Cable Specifications for the wiring of inputs is
22 AWG Belden or equivalent with a maximum distance of
2000 feet (610 meters).
NOTE: All wiring shall conform with the National Electrical
Code NPFA70 and local building codes.
Installation Instructions for 1 Door Systems – November 2022 Page 9

nput Wiring
All inputs may be configured for normally open or normally closed contacts. Door position,
request to exit and auxiliary inputs may also be configured with for supervision to detect if wiring
to the contact is broken or cut. Wires must not be route in parallel with or in the same
con uit with any high voltage AC wiring.
14 Pin Reader Harness
nput Power
PIN Color Description
1RED +12 VDC Power for In & Out Readers
3BLUE LED, In & Out Readers
5ORANGE Buzzer, In & Out Readers
GREEN D0, In Reader
9WH TE D1, In Reader
11 GREEN D0, Out Reader
13 WH TE D1, Out Reader
2BLACK Ground, In & Out Readers
Door nputs
14 PURPLE Door Position Input
12 BLACK Ground
10 YELLOW Request to Exit Input
System nputs
8GRAY AUX Input
6BROWN Tamper
4GRAY Power Fault
12 BLACK Ground
Installation Instructions for 1 Door Systems – November 2022 Page 10

Request to Exit (REX) nput
A REX input activated the door output to unlock a door. A REX device can be a press to exit
button, motion detector or other device mounted on the secured side of an entrance. REX
features may be modified in Device Settings for Doors and can be set to normally open (NO),
normally closed (NC) or monitored using either a series or parallel resistor. For applications
where a manual unlocking device is used, such as an exit bar, REX activating the door output
can be disabled.
Request to Exit Wiring
1. Disconnect power from the controller.
2. Determine if your REX device is normally open
or normally closed (refer to the instructions
provided by the REX manufacturer).
3. Connect the REX device as shown.
4. After power is applied to the controller, make
sure to configure the controller in Device
Settings for Doors and select the appropriate REX input type.
5. After power is applied to the controller, verify the input is properly working.
Door Position nput
Monitors if the door is open or closed. The door switch (typically a magnetic reed switch, not
provided) will change state when the door is opened or closed. To use this feature, it must be
enabled in Device Settings for Doors. It can be set to normally open (NO), normally closed (NC)
or monitored using either a series or parallel resistor.
Door Position Wiring
1. Disconnect power from the controller.
2. Determine if your door position switch is normally
open or normally closed (refer to the instructions
provided by the switch manufacturer).
3. Connect the door position switch as shown.
4. After power is applied to the controller, make sure to
configure the controller to use the door position
switch in Device Settings for Doors and select the appropriate door contact type.
5. After power is applied to the controller, verify the input is properly working.
Auxiliary nput
Auxiliary inputs are used for general purposes and can be connected to devices such as alarms,
detectors and devices that have a switched output. These inputs can be set to normally open
(NO), normally closed (NC) or monitored using either a series or parallel resistor and these
features may be modified in Device Settings for Aux Inputs.
Auxiliary inputs must be programmed to produce a defined action, such as activating an
auxiliary output, using Event Actions.
Installation Instructions for 1 Door Systems – November 2022 Page 11

Auxiliary nput Wiring
1. Disconnect power from the controller.
2. Determine if device you are connecting to the
Auxiliary input is normally open or normally closed
(refer to the instructions provided by the device
manufacturer).
3. Connect the device to the Auxiliary input as shown.
4. After power is applied to the controller, make sure to configure the controller in Device
Settings for Doors and select the appropriate Auxiliary input type.
5. After power is applied to the controller, verify the input is properly working.
Tamper
The tamper input may be used to monitor access to the access control system. This input can
be set to normally open (NO) or normally closed (NC) in Device Settings for Controllers.
Typically a tamper switch is mounted inside the enclosure containing the access control system
in such a way that when the enclosure is opened, the switch is activated.
The access control system can be programmed using Event Actions to perform a system
backup, activate an auxiliary output or send an email notification when a tamper input is
detected.
Tamper nput Wiring
1. Disconnect power from the controller.
2. Determine if device you are connecting to the Tamper
input is normally open or normally closed (refer to the
instructions provided by the device manufacturer).
3. Connect the device to the Tamper input as shown.
4. After power is applied to the controller, make sure to configure the controller in Device
Settings for Controllers and select the appropriate Tamper input type.
5. After power is applied to the controller, verify the input is properly working.
Power Fault
The power input may be used to monitor the power supply connected to the access control
system. This input can be set to normally open (NO) or normally closed (NC) in Device Settings
for Controllers. Typically power supplies designed for access control will have a switched output
that is activated when main power is lost and changed to battery backup.
The access control system can be programmed using Event Actions to perform a system
backup, activate an auxiliary output or send an email notification when a power input is
detected.
Installation Instructions for 1 Door Systems – November 2022 Page 12

Power Fault nput Wiring
1. Disconnect power from the controller.
2. Determine if device you are connecting to the
Power Fault input is normally open or normally
closed (refer to the instructions provided by the
device manufacturer).
3. Connect the device to the Power Fault input as shown.
4. After power is applied to the controller, make sure to configure the controller in Device
Settings for Controllers and select the appropriate Power Fault input type.
5. After power is applied to the controller, verify the input is properly working.
Readers
The controller can be connected to Wiegand type readers or keypads. Each door on the
controller supports a primary (entrance) In Reader and a secondary (exit) Out Reader.
The maximum power available through the controller for an individual reader is 300mA @
12VDC with a combined maxim for the controller of 600mA. Excee ing the maximum power
for an in ivi ual rea er or for the controller may amage the controller, voi the warranty
an will cause erratic operation. Refer to the manufacture's documentation to determine the
reader's power requirements. Wires must not be route in parallel with or in the same
con uit with any high voltage AC wiring.
The Minimum Cable Specifications for readers is a Belden shielded twisted
6 conductor plus ground cable 22 AWG.
For UL installations, the maximum cable length is 98.5 feet (30 meters).
Note: Use UL294 listed readers for all installations. All wiring shall conform with
the National Electrical Code NPFA70 and local building codes.
Installation Instructions for 1 Door Systems – November 2022 Page 13

Reader Wiring
1. Disconnect power from the controller.
2. Connect the color coded wires from the reader to the appropriate wires on the reader 14
pin harness as shown. Refer to manufacture's instructions for exact color codes for each
connection.
3. Remove excess shield from the reader cable to prevent interference with the controller's
electronics or other electrical circuits. Tape off any exposed shield with electrical tape.
4. Reader shields must be grounded per the manufacture's requirements.
5. Make sure to properly ground the reader shield.
6. After power is applied to the controller, verify the reader is properly working.
n & Out Reader Wiring
14 Pin
Reader
Harness
Color Description Typical N Reader
Wire Color
Typical Out Reader
Wire Color
12 Black Ground Black Black
13 White Out Reader, D1 X White
11 Green Out Reader, D0 X Green
9White In Reader, D1 White X
Green In Reader, D0 Green X
5Orange Buzzer Control BUZ* BUZ*
3Blue LED Control LED* LED*
1Red 12 VDC Red Red
*Wire Color Varies By Manufacturer. Check Reader Manual for Correct Color
Controller Outputs & Power nput
The controller has door output and auxiliary output relays that may be activated in response to
reader activity, time schedules or event actions. The outputs are assigned default features that
can be configured in Device Settings for Doors or Auxiliary Outputs. The table below shows the
default state for each type of output.
NOTE: Relays are configurable in the controller's U . Activation time, state and output
can be modified as required by the installation.
Output Default State Default Response
Door Output Not Energized, Single Pulse 3 second activation time in response to
valid access credentials
Auxiliary Output Not Energized, Single Pulse None. Must be configured in Device
Settings or Event Actions
Installation Instructions for 1 Door Systems – November 2022 Page 14

Output Wiring Requirements
The wire used must be of the proper gauge for the load current and distance from the controller
to the load. Wires must not be route in parallel with or in the same con uit with any high
voltage AC wiring and all wiring shall conform with the National Electrical Code, NPFA 0 and
local building codes. The table below shows recommendations for wire gauge based on load
and distance from the controller. Use a minimum size of UL listed 18 AWG to a maximum
distance of 98.5 feet (30 meters).
10 Position Power Harness
nput Power
PIN Color Description
10 BLACK Ground
9RED +12 VDC @ 2A
Door Output
3Gray Normally Closed Dry Relay Contact
5BLUE Common Relay Contact
Green Normally Open Dry Relay Contact
Auxiliary Output
4Gray Normally Closed Dry Relay Contact
6WH TE Common Relay Contact
8Green Normally Open Dry Relay Contact
2BLACK Ground
1BLACK Ground
Power 12 VDC & GND
The Power Input requires a dedicated Class 2, 12 VDC power supply. For UL installations, only
use a UL294 listed supply that has an indicator light that is illuminated when AC power is
present, with a rating of 12 VDC @ 2A.
NOTICE: A 12 VDC power supply must be used. Incorrect voltage
will damage the product and void the warranty.
CABLE SPECIFICATIONS: Use a minimum size of UL listed 18
AWG 2 conductor at a maximum distance of 4 feet (1.2 meters).
NOTE: Power supplies must be plugged into a dedicated
receptacle that is not controlled by a switch.
Power Wiring
1. Connect the power supply +12V and -12V terminals to 10
pin power harness as shown.
2. Power should only be applied to the system when all
connections are secured and tested, and when instructed
to apply power.
NOTE: When 12V power is applie to the controller, a blinking LED in icator next to the
14 pin rea er harness will be visible.
Installation Instructions for 1 Door Systems – November 2022 Page 15

Door Lock Wiring
Door outputs can be configured to operate in a fail safe or fail secure mode. Connect the door
locking device to the door output connector as shown below. Refer to the manufacture's
specifications to determine the correct operating voltage, current and configuration. Use a power
supply dedicated for door lock use. On models that include power for the door locks, the
built in power supply may be used to power 12V or 24V DC door locking devices.
Fail Secure DC Door Strike
Without power, the door strike is locked.
Fail Safe DC Door Strike
Without power, the door strike is
unlocked.
*Bidirectional TVS, Diode or Equivalent Transient Protection Device. mages
shows non-polarized bidirectional TVS that is supplied with the controller.
Installation Instructions for 1 Door Systems – November 2022 Page 16

Powering On and Connecting to a Network
Controllers must be located in a secure area and connected to a network that is protected by a
security system (firewall, etc.). Before connecting the controller to the network, obtain the
following information from you network administrator. Note: a Static IP address should be used
when a controller is configured as a server controller. Client controllers may use DHCP.
✔IP address
✔Subnet Mask
✔Gateway
✔DNS 1 and DNS 2
Preparing for the Network
In most cases, the controllers IP address will have to be changed to allow the controller to be
recognized by the local network. The controller's IP address is changed as follows.
1. Connect a programming computer directly to the Ethernet port of the controller. A
standard CAT-5 cable is used for direct connection. A crossover cable is not required.
2. Assign a static IP address to the computer of 192.168.0.10. For instructions on how to
change the static IP address of a Windows computer visit:
https://support.microsoft.com/en-us/help/15089/windows-change-tcp-ip-settings
3. The factory default IP address of the controller is 192.168.0.250. Open a web browser,
such as Google Chrome, and enter the default IP address into the address bar.
TIP: As an alternative to directly connecting a cable the Smart IP Finder
utility can be used to change the controller's IP address. See the section
below on how to use the utility.
4. The controller's login page is displayed as shown. To login enter the
default User ID: admin and default PW: admin NOTE: After you
login with a min/a min, as an a e security feature, you will be require to reset
the passwor .
5. Controllers can be licensed as a server or a client.
After first time login, the license page is is
displayed. To get a license key, first click on the
Edit button. On the next page, click on A, the Get
License Key for a SERVER or click on B, the Get
Client Key for a CL ENT. Click OK to confirm and the license key will be auto populated.
Finish by clicking C, Apply License Key and the controller will restart.
NOTE: The controller needs to access the Internet to obtain a license key.
Installation Instructions for 1 Door Systems – November 2022 Page 1

6. When the controller is licensed for a server, after logging in and reviewing the EULA, the
system configuration Wizard is started. You must scroll to the bottom to accept and
proceed. The Wizard is a guide that can be used to collect the basic information required
to set up a system.
Wizard Starting Page
. The network configurations may be accessed through the Sitemap by first clicking the
icon at the bottom of the page, then clicking IP Address under Network Settings.
Accessing the Site Map
8. After entering the network information, click Save & Reboot and the controller will reboot.
Typically rebooting will take less than 2 minutes.
Network Settings Page
9. After disconnecting the programming computer, the controller is ready for the local
network.
NOTE: System data may be lost if the controller is powered down
without performing Save Data.
Installation Instructions for 1 Door Systems – November 2022 Page 18

Connecting to the Network
Plug the Ethernet cable into the port on the controller and connect to the local area network as
shown below. If the network connection is functioning properly the LAN LED's on the controller
will blink. Computers connected to the local network will be able to access the system using the
IP address of the controller.
The Minimum Cable Specifications network connection is
CAT 5 or better with an RJ-45 connector wired straight through
to a network switch or router.
Note: For UL installations the maximum Ethernet cable length
is 98.5 feet (30 meters).
NOTE: LAN connection is only required for monitoring reporting and configuration.
Once the system is configured it will operate without a LAN connection.
Adding Clients to Systems
Some systems have the ability to add additional controllers to increase the number of doors,
inputs or outputs or control elevators. Clients are configured through the system's server, but
must first be linked to the server.
Setting the Client's Network
1. Connect a programming PC directly to the controller as described in the section
Preparing for the Network.
2. Login using the default ID: admin and default PW: admin NOTE: After you login with
a min/a min, as an a e security feature, you will be require to reset the
passwor .
3. After login, the client's network page is displayed. Click Edit.
4. Change the IP address of the client controller. It is recommended to set this to DHCP.
5. Enter the IP address of the server controller and the server's port number (the default
port number is 20000).
6. Enter the password and click Save.
Installation Instructions for 1 Door Systems – November 2022 Page 19

Linking the Client to the Server
1. Login to the system's server.
2. After logging in, browse to the Site Management and select Client Management.
3. The client will appear in the client management list. Click on the button to connect
the client to the server.
Client Management
NOTE: After you connect the client to the server, the client's passwor will be
reset to match the server's passwor
Installation Instructions for 1 Door Systems – November 2022 Page 20
Table of contents
Popular Control System manuals by other brands

Swegon
Swegon SILVER C instructions

UWE
UWE Viper 2000 installation instructions

ECOFOREST
ECOFOREST ecoSMART e-source USER, INSTALLER AND TECHNICAL SERVICE MANUAL

RuiDa
RuiDa RDC6585G manual

Franke
Franke DVS SH07-020 Installation & operating instructions

Toshiba
Toshiba TOSDIC-CIE DS Installation and wiring manual