Contrec 500 Series User manual

Model 515 Flow Computer
Operation Manual
Application BC01
Dual Stage Batch Controller
for
Volumetric Frequency or Analog Flowmeters
23 August 2019

Model 515 Flow Computer - Operation Manual
© Contrec Ltd 2019
The instructions given herein cover the general description, installation, operation and maintenance of the subject
equipment. Contrec Ltd reserves the right, without prior notice, to make engineering refinements that may not be
reflected in this manual.
Should any questions arise which cannot be answered specifically by this manual, they should be directed to
Contrec Ltd for further detailed information and technical assistance.
Contrec Ltd will not accept any liability for either direct or consequential damages resulting from the use or
misapplication of the contents of this manual.
Part of the software embedded in this product is eCos - Embedded Configurable Operating System, a trademark of
Red Hat. Portions created by Red Hat are Copyright © 1998, 1999, 2000 Red Hat, Inc.
(http://www.redhat.com). All rights reserved
The software in this product was in part provided by Red Hat and any express or implied warranties, including, but
not limited to, the implied warranties of merchantability and fitness for a particular purpose are disclaimed. In no
event shall the author be liable for any direct, indirect, incidental, special, exemplary, or consequential damages
(including, but not limited to, procurement of substitute goods or services; loss of use, data, or profits; or business
interruption) however caused and on any theory of liability, whether in contract, strict liability, or tort (including
negligence or otherwise) arising in any way out of the use of this software, even if advised of the possibility of such
damage.
Contrec Ltd
Riverside, Canal Road, Sowerby Bridge,
West Yorkshire HX6 2AY UNITED KINGDOM
Tel: +44 1422 829944
Email: [email protected]
Website: www.contrec.co.uk
Contrec Systems Pty Ltd
5 Norfolk Avenue Ringwood, Melbourne 3134 AUSTRALIA
Tel: +61 4 413 505 114
Email: [email protected]
Contrec - USA, LLC
916 Belcher Drive Pelham AL 35124 USA
Tel: +1 (205) 685 3000 Fax: +1 (205) 685 3001
Email: [email protected]
Publication No: 515-BC01-OM - 23 August 2019

515 BC01 - 23 August 2019 iii
Safety Notice
The information in this safety notice is for the prevention of injury to personnel and
damage to the instrument.
The manufacturer assumes no liability for injury or damage caused by misuse of the
instrument or for modifications made to the instrument.
Qualified Personnel
The instrument must be installed, operated and serviced by persons who have been properly
trained and authorised. Personnel must read and understand this manual prior to installation and
operation of the instrument.
Static Hazard
The 500 series flow computer uses high speed CMOS circuitry which is sensitive to static
damage. The user should observe accepted safety practices for handling electronic devices,
especially during servicing. Once the unit is installed, grounded and interconnected, the chances
of static damage are greatly reduced.
Voltage Hazard
Before connecting power to the instrument, ensure that the supply voltage for the AC or DC
input is suitable. The AC voltage rating is as stated on the instrument rating plate. Personnel
should take all due care to avoid electric shock. For safe operation it is essential to connect a
mains safety earth to the A.C. power inlet. Do not operate at altitudes above 2000m.
Welding Hazard
Do not perform electric welding in close proximity to the instrument or its interconnecting
cables. If welding in these areas must be performed, disconnect all cables from the instrument.
Failure to do so may result in damage to the unit.
Moisture Hazard
To avoid electrical faults and corrosion of the instrument, do not allow moisture to remain in
contact with the instrument.
Disconnection Device
When powered from a mains supply this unit requires the provision of a suitable mains isolation
device to be accessible near to the installed instrument.
515 BC01 - 23 August 2019

i v 515 BC01 - 23 August 2019
Instrument Disposal
Contrec instrumentation should not be thrown into the general waste system.
If within EU member states, this instrument should be disposed of according to
the guidelines set by the WEEE (Waste Electrical and Electronic Equipment)
directive 2012/19/EU. If outside of the EU, this equipment should be
responsibly disposed of according to local and national regulations for EEE
(Electrical and Electronic Equipment).
By not discarding of this product along with other house hold waste you are
preserving natural resources and reducing waste sent to landfill and incinerators.
Remove batteries and dispose of separately (see Disposal of Batteries) before disposal of
Contrec instrumentation.
Disposal of Batteries
Batteries have an environmental impact. Safe and responsible disposal should
be undertaken.
Batteries have an environmental impact, safe and responsible disposal should
be undertaken.
In all EU member states, as per Directive 2006/66/EC, batteries must not be
thrown away with general waste. Contact your local environmental authority
for information regarding disposal or recycling of used batteries, alternatively
they can be returned directly to Contrec Ltd. for disposal.
Please Contact Contrec Ltd before returning batteries for disposal.

v
1 Introduction
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Analog Input Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Displayed Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Main Menu Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Isolated Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Relay Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Software Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 Specifications
Specification Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3 Installation
Panel Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Rear Panel Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Terminal Designations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Frequency Input Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Analog Input Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Logic Input Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4-20 mA Output Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Digital Output Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Control Relays (Alarms) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
RC Network for Interference Suppression . . . . . . . . . . . . . . . . . . . . . . 16
Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
COM-1 RS-232 Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
COM-2 RS-485 Port (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Earthing and Shielding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4 Operation
Front Panel Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Default Variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Status LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Front Panel Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Main Menu Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Detail and Basic Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Contents
515 BC01 - 23 August 2019

v i 515 BC01 - 23 August 2019
Setting the Batch Preset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Data Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Model Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Batch Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Starting a Batch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Stopping a Batch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Resetting a Batch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Printing a Delivery Docket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Logic Input Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Batch Flow Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Batch Control Processes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5 Instrument Calibration
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Calibration View Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Calibration Set Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Changing the Instrument Settings . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Program Backup & Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Backup via 500 Series Program Manager . . . . . . . . . . . . . . . . . . . . . . 33
Printing Configuration Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Upload and Clone of Application Software . . . . . . . . . . . . . . . . . . . . . 33
Calibration Menu Tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Instrument Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Units of Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Time Settings and Data Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
General Setup Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Test Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
System Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Warning Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6 Communications
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Hardware Interconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Protocols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Simple ASCII Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Requests Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Instrument Responses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Corrupted or Invalid Requests . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Modbus RTU Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
List of Data Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Printer Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Types of Printouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74

515 BC01 - 23 August 2019 vii
Printer Data Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Appendix A Glossary
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Appendix B Model Numbers
Product Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Custom Version Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Application Information Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Appendix C Units of Measurement
Available Units of Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85

viii 515 BC01 - 23 August 2019

i x515 BC01 - 23 August 2019
List of Figures
1 Typical Application Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Rear Panel Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3 Externally Powered Voltage Transmitter . . . . . . . . . . . . . . . . . . . . . 12
4 Internally Powered Voltage Transmitter . . . . . . . . . . . . . . . . . . . . . 12
5 Externally Powered Current Loop . . . . . . . . . . . . . . . . . . . . . . . . . 13
6 Internally Powered Current Loops . . . . . . . . . . . . . . . . . . . . . . . . 13
7 Logic Inputs Connection Diagram . . . . . . . . . . . . . . . . . . . . . . . . 14
8 Output 4-20 mA Connection Diagram . . . . . . . . . . . . . . . . . . . . . . . 14
9 Output Pulse Connection Diagram . . . . . . . . . . . . . . . . . . . . . . . . 15
10 Relay Connection Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
11 RS-485 Interface Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
12 Batch Operation with Manual or Automatic Reset . . . . . . . . . . . . . . . . 28
13 Batch Operation with Automatic Restart . . . . . . . . . . . . . . . . . . . . . 28
14 Calibration Menu Tree Sheet 1 . . . . . . . . . . . . . . . . . . . . . . . . . . 34
15 Calibration Menu Tree Sheet 2 . . . . . . . . . . . . . . . . . . . . . . . . . . 35
16 RS-232 Cable Connections to a Computer . . . . . . . . . . . . . . . . . . . . 60
17 RS-485 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

x 515 BC01 - 23 August 2019

1
Chapter 1
Introduction
Features
•Caters for volumetric flow inputs from frequency or analog flowmeters
•Single or Dual stage control
•Quick access to common batch quantities
•No-flow, leakage and overflow error detection
•Remote RUN/STOP/RESET & BATCH SET functions
•Allows for square law and non-linear correction
•Storage of 1000 transactions with time and date stamp
•Selection of Detail or Basic main menu to suit operator and application
•Selection of second language and user tags
•Pulse width and scaling of pulse output
•4-20 mA retransmission
•Selectable protocols on serial ports including Modbus RTU and Printer
output
•Front panel adjustment of 8-24 V DC output voltage
•Backlit display with LCD backup
Overview
The 515 BC01 application is a dual stage batch controller for reliable
measurement of preset quantities using a volumetric frequency or analog
input. Used as a single or dual stage controller it is suitable for fast batch
applications.
It provides the operator with clear local readout and can be controlled via
communications in more automated systems. There is quick access to
commonly used preset values directly from the front panel if access has
been authorized. Overrun compensation caters for system delays such as
valve closure for precise quantities.
515 BC01 - 23 August 2019

Introduction
2 515 BC01 - 23 August 2019
The instrument is compatible with a wide range of flowmeter outputs,
including millivolt signals, reed switches, pulse, Namur proximity switches
and analog signals. Inputs can be scaled, filtered and have non-linear
correction applied. Square law and cutoff points can also be applied to the
analog input.
Calculations
If using the frequency input, the total and flowrate are derived from
accurately measured frequency and the number of received pulses.
volume = pulses / k-factor
volume flow = frequency / k-factor
If using the analog input, to derive the flow rate the input is normalised to a
value (A) between 0 and 1.
volumeflow = (Vf
max-Vf
min)A+Vfmin
Automatic overrun compensation calculates the new valve closure point to
ensure correct delivery by averaging the overrun amount from the last three
complete batches.
The overrun compensation value is valid for a new preset value provided the
stored overrun is less than 20% of the new preset.
Analog Input Scaling
The analog inputs in this instrument are scaled by the following general
formula:
where:
Correction Type
•LINEAR: when the instrument is not required to apply
correction
•NON-LINEAR: when the instrument applies correction from
the points in the correction table
•SQUARE when the transmitter does not have square
root extraction and it must be applied by the instrument.
volume volumeflow t
=
Pmin = minimum point (equivalent to offset)
Pmax = maximum point (Pmax – Pmin is equivalent to span)
A* = normalised signal (0 to 1) with correction applied for a flow input
f
A Pmin Pmax Pmin–A*+=
A* A=
A* Ac
=
A* A=

Introduction
515 BC01 - 23 August 2019 3
Displayed Information
The front panel display shows the current values of the input variables and
the results of the calculations.
The instrument can be supplied with a real-time clock for storage of up to
1000 transactions with time and date stamps.
Main Menu Variables
Refer to Available Units of Measurement on page 84 for the list of
available units.
Communications
There are two communication ports available as follows:
•COM-1 RS-232 port
•COM-2 RS-485 port (optional)
The ports are available for remote data reading, printouts and for initial
application loading of the instrument.
Isolated Outputs
The opto-isolated outputs can retransmit any main menu variable. The type
of output is determined by the nature of the assigned variable. Totals are
output as pulses and rates are output as 4-20 mA signals. One output is
standard, a second output is available as an option.
Main Menu
Variables
Default
Units
Variable
Type
Volume L Total
Volume Flowrate L/min Rate

Introduction
4 515 BC01 - 23 August 2019
Relay Outputs
The relay outputs 1 and 2 are used to control the flow of product for each
delivery. These contacts are normally open and can be used to drive external
relays, valves, pump circuits etc. The advanced option provides another two
relays that can be used as fully programmable alarms for any rate type
variable.
Software Configuration
The instrument can be programmed to suit the particular application needs
and the flexible I/O can be assigned as required. Program settings can be
changed either via the front panel (depending on assigned access levels) or
via the 500 Series Program Manager (500-PM software).
The 500-PM software is a free comprehensive configuration tool and
resource centre that can be used to further tailored an instrument to suit
specific application needs including units of measurement, custom tags and
text, access levels and more.
The software is a Windows based program that is freely available from the
download section of the Contrec website. The program can be used to create
a custom version of an existing application to be saved for backup purposes
and/or to generate a PDF of configuration report for record keeping.
The instrument stores all set-up parameters, totals and logged data in non-
volatile memory with at least 30 years retention.
Figure 1 Typical Application Diagram
Main Flow
Control Valve
Frequency or
Analog Input
Bleed Flow
Relay 1 Relay 2
Control Valve
Example of
dual stage
batching
Volumetric
Flowmeter

Introduction
515 BC01 - 23 August 2019 5
Approvals
This instrument conforms to the EMC-Directive of the Council of
European Communities 2014/30/EU, the LVD safety directive 2014/35/EU
and the following standards:
•EN61326:2013 Electrical equipment for measurement, control and
laboratory use – EMC requirements: Industrial Environment.
•EN61010:2010 Safety requirements for electrical equipment for
measurement, control, and laboratory use.
In order to comply with these standards, the wiring instructions in Chapter
3 - Installation must be followed.
FCC Declaration
This equipment has been tested and found to comply with the limits for a
Class A digital device, pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the instruction manual, might
cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference, in
which case the user will be required to correct the interference at his own
expense.
Properly shielded and grounded cables and connectors must be used in order
to meet FCC emission limits. Contrec Ltd is not responsible for any radio or
television interference caused by using other than recommended cables and
connectors or by unauthorized changes or modifications to this equipment.
Unauthorized changes or modifications could void the user's authority to
operate the equipment.
This device complies with Part 15 of the FCC Rules. Operation is subject to
the following two conditions: (1) this device might not cause harmful
interference, and (2) this device must accept any interference received,
including interference that might cause undesired operation.

Introduction
6 515 BC01 - 23 August 2019

7
Chapter 2
Specifications
Specification Table
Operating Environment
Temperature -20 °C to +60 °C (conformal coating)
+5 °C to +40 °C (standard - no coating)
Humidity 0 to 95% non condensing (conformal
coating)
5% to 85% non condensing (no coating)
Power Supply 100-240 V AC (+/-10%) 50-60 Hz (+/-
10%) or 12-28 V DC
Consumption 6 W (typical)
Protection Sealed to IP65 (Nema 4X) when panel
mounted
Dimensions
(panel option)
147 mm (5.8") width
74 mm (2.9") height
170 mm (6.6") depth (behind the panel)
Display
Type Backlit LCD with 7-digit numeric display
and 11-character alphanumeric display
Digits 15.5 mm (0.6") high
Characters 6 mm (0.24") high
LCD Backup Last data visible for 15 min after power
down
Update Rate 0.3 second
Non-volatile Memory
Retention > 30 years
Data Stored Setup, Totals and Logs
Approvals
Interference compliance
Enclosure IECEx, ATEX and CSA approved
enclosures available for hazardous areas
Real Time Clock (Optional)
Battery Type 3 volts Lithium button cell
(BR2032 for extended temperature range)
(CR2032 for standard temperature range)
Battery Life 5 years (typical)
Frequency Input (General)
Range 0 to 10 kHz
Overvoltage 30 V maximum
Update Time 0.3 sec
Cutoff frequency Programmable
Configuration Pulse, coil or NPS input
Non-linearity Up to 10 correction points
Pulse
Signal Type CMOS, TTL, open collector, reed switch
Threshold 1.3 volts
Coil
Signal Type Turbine and sine wave
Sensitivity 15 mV p-p minimum
NPS
Signal Type NPS sensor to Namur standard
Analog Input (General)
Overcurrent 100 mA absolute maximum rating
(30mA for 4-20mA inputs)
Update Time < 1.0 sec
Configuration 4-20 mA, 0-5V and 1-5V input
Non-linearity Up to 20 correction points (some inputs)
4-20 mA Input
Impedance 100 Ohms (to common signal ground)
Accuracy 0.05% full scale (20 C)
0.1% (full temperature range, typical)
0-5 or 1-5 Volts Input
Impedance 10 MOhms (to common signal ground)
Accuracy 0.05% full scale (20 C)
0.1% (full temperature range, typical)
Logic Inputs
Signal Type CMOS, TTL, open collector, reed switch
Overvoltage 30V maximum
515 BC01 - 23 August 2019

Specifications
8 515 BC01 - 23 August 2019
Important: Specifications are subject to change without notice.
Printer protocol is available only if RTC option is installed.
Relay Output
No. of Outputs 2 relays plus 2 optional relays
Voltage 250 volts AC, 30 volts DC maximum
(solid state relays use AC only)
Current Maximum 3 A EMR, 1A SSR
Communication Ports
Ports COM-1 RS-232 port
COM-2 RS-485 port (optional)
Baud Rate 2400 to 19200 baud
Parity Odd, even or none
Stop Bits 1 or 2
Data Bits 8
Protocols ASCII, Modbus RTU, Printer*
Transducer Supply
Voltage 8 to 24 volts DC, programmable
Current 70 mA @ 24 V, 120 mA @ 12 V maximum
Protection Power limited output
Isolated Output
No. of Outputs 1 configurable output (plus 1 optional)
Configuration Pulse/Digital or 4-20 mA output
Pulse/Digital Output
Signal Type Open collector
Switching 200 mA, 30 volts DC maximum
Saturation 0.8 volts maximum
Pulse Width Programmable: 10 , 20, 50, 100, 200 or
500ms
4-20 mA Output
Supply 9 to 30 volts DC external
Resolution 0.05% full scale
Accuracy 0.05% full scale (20C)
0.1% (full temperature range, typical)

9
Chapter 3
Installation
Panel Mounting
The instrument should be located in an area with a clean, dry atmosphere
that is also relatively free of shock and vibration.
The standard mounting procedure is panel mounting in a cutout that is
139 mm wide by 67 mm high. Two side clips secure the unit into the panel.
shows the panel mounting requirements for the 500 Series Instrument.
500 Series Instrument Panel Mounting
145 mm
Side View
22 mm
70 mm
67 mm
139 mm
25 mm
66 mm
Min. 189 mm
Panel Cut-out
Front
Panel
74 mm
Mounting Clip
138 mm
147 mm
Rear Connectors Top View RS232
Port
515 BC01 - 23 August 2019

Installation
1 0 515 BC01 - 23 August 2019
Electrical Connection
Rear Panel Connections
Figure 2 shows the connections on the rear panel of the instrument.
Figure 2 Rear Panel Connections
Terminal Designations
RS232 Port
CAUTION
MAINS
E N A
AC MAINS
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35
RC R1 R2 R3 R4
RELAYS
+ - G 1+2+3+4+C- + - + -
RS485 LOGIC INPUT OUT1 OUT2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
FINP SG EXC V AINP1 AINP2 AINP3 AINP4 Vo G Vi SH
1+2+-1+2+3++-+-+-+-+-+E
Terminal Label Designation Comment
1 FINP 1+ Frequency Input 1+ Volumetric Flow Input
2 FINP 2+ Frequency Input 2+ Not used
3 SG - Signal ground
4 EXC V 1+ Excitation Term 1+ Not used
5 EXC V 2+ Excitation Term 2+ Not used
6 EXC V 3+ Excitation Term 3+ Not used
7AINP1 + Analog Input ch 1 (+) Not used
8 - Analog Input ch 1 (-)
9AINP2 + Analog Input ch 2 (+) Not used
10 - Analog Input ch 2 (-)
11 AINP3 + Analog Input ch 3 (+) Volumetric Flow Input
12 - Analog Input ch 3 (-)
13 AINP4 + Analog Input ch 4 (+) Not used
14 - Analog Input ch 4 (-)
15 Vo + 8-24 volts DC output Overload protected
16 G - DC Ground
17 Vi + DC power input DC power in 12-28V
18 SH E Shield terminal
E
AC
MAINS
E Mains ground AC power in 100-
240VAC
N N Mains neutral
A A Mains active
19 RS485
COM-2
port
+ RS485 (+)
Optional RS485 port20 - RS485 (-)
21 G RS485 ground
22
LOGIC
INPUTS
1+ Switch 1 Remote Run
23 2+ Switch 2 Remote Stop/Reset
24 3+ Switch 3 Remote Set
25 4+ Switch 4 CAL Switch – In field
access protection
26 C- Signal ground
27 OUT1 + Output ch 1 (+)
28 - Output ch 1 (-)
29 OUT2 + Output ch 2 (+) Optional output
30 - Output ch 2 (-)
31
RELAYS
RC Relay common
32 R1 Relay 1 Single Stage Control
33 R2 Relay 2 Dual Stage Control
34 R3 Relay 3 Optional relays
35 R4 Relay 4
RS232 COM-1 port 9-pin serial port
Terminal Label Designation Comment
Other manuals for 500 Series
2
This manual suits for next models
1
Table of contents
Other Contrec Controllers manuals

Contrec
Contrec 505 BC01 User manual

Contrec
Contrec 424 User manual

Contrec
Contrec 515 User manual

Contrec
Contrec 114D User manual

Contrec
Contrec 505 Series User manual

Contrec
Contrec 414Q User manual

Contrec
Contrec 515 User manual

Contrec
Contrec 414L Reference manual

Contrec
Contrec 515 User manual

Contrec
Contrec 214D User manual
Popular Controllers manuals by other brands

Bullgenius
Bullgenius Bullmax user manual

Franke
Franke AQUA3000OPEN ZA3OP0023 Installation and operating instructions

Profelmnet
Profelmnet 3414 quick start guide

SMC Networks
SMC Networks e-Rodless E-MY2 Series Operation manual

Ekinex
Ekinex EK-HH1-TP manual

Fisher
Fisher FIELDVUE DVC2000 Instruction manual supplement