8 / 12
Siemens RXB39.1 – Room controller CM2N3875en_04
Building Technologies 2013-06-16
Technical data
Power supply Operating voltage
C 230 V +/-10 %
Rated voltage
C 230 V
Frequency 50/60 Hz
Power consumption with connected field devices Max. 12 VA
Internal fuse Thermal, non-resetting
Operating data Control algorithm PI
Inputs (SELV)
Signal inputs D1 … D4 Quantity 4
(for volt-free contacts) Contact voltage DC 16 V
Contact current DC 5 mA
Contact transfer resistance Max. 100
Contact insulation resistance Min. 50 k
Switch time: min. 20ms “ON”, min. 20ms “OFF”
Measured value input B1 Compatible temperature sensors LG-Ni 1000
Quantity 2
Measuring range 0 … 50 °C
Sensor current 0.5 mA
Resolution 0.1 K
Measuring error at 25 °C sensor temp. (without cable) max. 0.5 K
Outputs (SELV)
DC 0 … 10 V YC1, YC2, YC3 Quantity 3
Resolution 3 mV
ccuracy 100 mV
Output current Max. 1.5 mA
Supply output G (SELV) Voltage / Max. load
C 24 V / Max. 6 VA
Relay outputs
Q34 (fan release) Quantity 1 (N/O contact)
Relay type Monostable
Contact rating with AC voltage
Switching voltage Max. AC 250 V, min. AC 19 V
Nominal current, resistive/inductive Max. AC 5(4) A (cos = 0.6)
Making current 200 ms half-time Max. 20 A
Switching current at AC 19 V Min. AC 10 mA
Contact rating with DC voltage
Switching voltage Max. DC 250 V, min. DC 5 V
Switching current at DC 5 V Min. DC 100 mA
Switching capacity Max. 20 W
Inductive load L/R Max. 7 ms
External fuse (essential!) Max. 10 A
Q14 (heater release) Quantity 1 (N/O contact)
Relay type Monostable
Contact rating with AC voltage
Max. admissible load (resistive only) Max. 1.8 kW
External fuse (essential) Max. 10 A
Ports/interfaces
Interface to room unit Number of room units connectable 1
Interface type for room unit
for ETS / ACS
PPS2
KNX bus
PPS2 baud rate 4.8 kbit/s
Baud rate on the KNX bus 9.6 kbit/s
KNX bus Interface type Electrically isolated
Bus current 5 mA
Baud rate bus 9.6 kbit/s
Bus topology Refer to Engineering, page 6