APPLICATION GUIDE
11
3. Alarm Verification Feature
When this is set any detector that enters a fire condition will show on the panel but no sounder program will be
activated, a 30 sec timer will start. At the end of the 30 sec, if the detector is still at alarm level the sounders will
activate. If during this time the detector has dropped below the alarm level then the panel will not go to alarm. This is
particularly useful to prevent false alarms from detectors where the smoke is from other sources other than a fire i.e.
smoking in bedrooms.
On later version software the AVF length can be timed from standard or long delay (45 secs) and when in UL 864
9th edition mode a shorter time (15 secs) has also been added. (see page 19) A further option includes the addition
of AVF on specific zones.
4. Auxiliary Board
Extra boards or additional features for other markets can be installed within the CF3000 / DF6000 / FX6000. These
include Extinguisher and Fire brigade boards to enable the control of other services within buildings in Germany.
Australian Mode creates a re-configured display screen when class change is shorted. In this mode a key-switch
device is installed on the front door of the CF3000 / DF6000 / FX6000 panel which can only be operated by the
Australian fire brigade (this key-switch shorts the class change). Address or zone text for the alarm can be viewed on
the screen depending on how the screen is configured. (See page 19)
The re-configured screen gives the Fireman controls to; silence the alarms, mute buzzer and reset the panel without
having access to the pass-code. Swedish mode is very similar except that the panel must be in Swedish language for
this feature to be operational.
5. HMO Mode
This feature has been added to accommodate BS 5839 Part 6 – Fire Alarm Installations in Dwellings. BS 5839 part
1 does not cover private dwellings, however, a landlord is required under this to protect all common areas within his
building, and generally this would be designed as L3 coverage with a detector and sounder in the lobby area of the
flat. Mains smoke detection would then be installed within the living accommodation to provide protection, but
preventing a false alarm in a flat evacuating the whole building.
There are 3 settings within the HMO menu:
•Class Change:
this is the controller of HMO mode, when class change is set to ‘global alarm’ the mode is on. In this instance, if
there are any pulsing sounders adjacent to the zone in fire, then operation of class change will change them to
continuous. Setting class change back to ‘normal operation’ on the screen HMO will be turned off.
• HMO Zones:
This button allows the operator to select the zones required to be in HMO mode.
• Reset Timeout:
Detectors within the HMO zone can be set on a delay from 1 to 5 minutes. Essentially this is an extended version of
Alarm Verification (section 3 above), if smoke or heat puts a detector in fire, the panel and detector will indicate this,
but will not activate any outputs unless specifically programmed to do so. If the smoke or heat clears within the
timeout period then the panel will reset. If smoke or heat remains until the timeout period has elapsed, then the
programmed cause and effect will commence.
NOTE: Only Photoelectric Detectors and Heat detectors can be used with this mode Opto/Thermals will not
operate.
CF3000 / DF6000 / FX6000 Application Guide