i-on40
Page 16
Zone Types & Attributes
(Hint: You can select a zone type quickly by
keying the number shown in brackets after
the type’s name, for example:“05” to select
Alarm Abort, “02” to select Panic Alarm,
“11” to select External PSU A/C Fail. The
number does not appear on the keypad
display.)
Not Used (00)
The alarm system will not respond
when an event triggers this detector.
Panic Alarm (01).
Operating a device programmed as
‘Panic Alarm’ (PA) will start an audible
alarm. If a communications module is
fitted there may also be an alarm
transmission to the Alarm Receiving
Centre (ARC), depending on how you
have programmed the ARC Reporting
option. PA alarms operate whether
the system is set or unset.
Fire Alarm (02).
Smoke or heat detectors connected to
Fire Alarm zones cause the sirens to
give a pulsing fire signal. Fire alarms
operate whether the system is set or
unset, and will always trigger
communications, if a communications
module is fitted and enabled.
Normal Alarm (03).
A zone programmed as ‘Normal
Alarm’ will start an alarm when the
system is set. (See “Zone Attributes”
on page 17.)
24 Hour Alarm (04).
Activating this zone causes an alarm
whether the system is set or unset.
Final Exit (05).
Zones of this type must be the last
detector to be activated on exit, or
the first to be activated on entry. You
can use zones of this type to finally
set the system, or to start the entry
procedure.
Note: If you give a Final Exit zone any of
the Part Set attributes then you can
program that zone to behave like a Normal
Alarm zone if the user part sets the system.
Entry Route (06).
Use this zone type for detectors sited
between the Final Exit door/detector
and the keypad. If an ‘Entry Route’
zone is triggered when the system is
set, an alarm will occur. If the
entry/exit timer is running when an
Entry Route zone is triggered then no
alarm occurs until the entry/exit timer
expires.
Note: If you give an Entry Route zone one
of the Part Set attributes then you can
program that zone to behave like a Final
Exit zone if the user part sets the system.
Technical Alarm (07).
Use this zone type when you want to
monitor equipment, for example a
freezer, without raising a full alarm. If
a technical alarm zone is activated
(and the control unit correctly
programmed) then the control unit
starts communication and logs the
event.
If the technical alarm occurs while the
system is set, then system makes no
audible alarm. When a user unsets
the system the keypad shows an
alert.
If a technical alarm zone is activated
while the system is unset then the
system starts an alert immediately
and gives a brief tone from the
keypad every few seconds. When a
user enters a valid access code the
keypad stops the tone and displays
the zone causing the alarm.
When the user acknowledges the alert
by pressing Ythe control unit resets
the technical alarm ready for the next
event.
Key Switch Momentary (08).
Use this zone type to connect a
momentary keyswitch to a single
zone.
In a Part Setting system the
keyswitch can Full Set or unset.
In a Partitioned system you can
allocate the keyswitch to one or more
partitions.
Each time a user operates the
keyswitch the control unit changes
the current set state.
Key Switch Latched (09).
Use this zone type to connect a fixed
position keyswitch to a single zone.
In a Part Setting system the
keyswitch can Full Set or unset. As
with Momentary keyswitches, you can
allocate the zone to one or more
Partitions (see above).
When the user closes the keyswitch
contacts the control unit sets the
allocated Partition. When the user
opens the contacts the control unit
unsets the allocated Partition.