CORNING SCF-6 User manual

Corning Cable Systems
Standard Recommended Procedure (SRP) 003-544
Issue 6, May 2004
Page 1 of 26
SCF-6 and SCF-8 Open Ribbon System (ORS) Canister Splice Closures
p/n 003-544
SCF-8
Figure 1 — Splice Closures
SCF-6
Contents
Related Literature ...................................................................................................................2
Admonishments.......................................................................................................................2
1. Carton Contents ...............................................................................................................................3
2. Tools and Equipment Required .......................................................................................................4
3. Installing the Closure .......................................................................................................................4
3.1 Prepare the Express Cable ......................................................................................................4
3.2 Install Grounding Hardware (Armored Cable Only) ............................................................6
3.3 Install Express Strain-relief Hardware ................................................................................... 7
3.3.1 Strain-relief bracket(s) ................................................................................................7
3.3.2 Nonmetallic strength member ...................................................................................8
3.3.3 Metallic strength members ........................................................................................8
3.3.4 Large strength members ............................................................................................9
3.4 Install Cable into the End Cap Express Ports ........................................................................ 9
3.4.1 Prepare the end cap ....................................................................................................9
3.4.2 Apply sealing tape to the cable ................................................................................. 10
3.4.3 Using dummy plug ...................................................................................................11
3.4.4 Install cable ...............................................................................................................11
3.4.5 Close end cap halves .................................................................................................11
3.4.6 Install vented grounding plug ..................................................................................12
3.4.7 Complete frame assembly ........................................................................................12
3.5 Ground Armored Cable ........................................................................................................12
3.6 Prepare Drop Cable Port(s) ..................................................................................................12
3.7 Install Drop Port Cable into End Cap .................................................................................14
3.8 Strain-relieve Drop Ports .....................................................................................................14
3.9 Attach Strain-relief Bracket ..................................................................................................15
3.10 Tighten End Cap Compression Screw.................................................................................15
3.11 Attach Frame to End Cap .....................................................................................................16
3.12 Load the ORS .......................................................................................................................16
3.12.1 Route express fibers ..................................................................................................16
3.12.2 Route drop cable fibers ............................................................................................18
3.12.3 Route fibers to the splice plane ................................................................................18
3.13 Splice .....................................................................................................................................19
3.13.1 Prepare fibers for splicing ........................................................................................ 19
3.13.2 Splice fibers...............................................................................................................19

SCF-6 and SCF-8 Open Ribbon System (ORS) Canister Splice Closures
Page 2 SRP 003-544 • Issue 6 • May 2004
Revision History
Issue Date Reason for Change
6 05/2004 Illustrate redesigned fiber management frame and sealing ring
5 10/2002 Reference checklist and clarify sealing paste and lubricant application
4 01/2001 Add SCF8 instructions and power tool precautions
3 07/2000 Illustrate redesigned strain-relief brackets and add chemical and
installer precautions
2 11/1999 Add instructons to strain-relieve large diameter central strength
members
1 08/1999 Initial release
Related Literature
EVO-435-EN Specifications for Medium Mass Fusion Splice Canister Closure
SRP 206-286 Mechanical Endcap Canister Closure Sealing Checklist
SRP 001-284 Instruction, Splice Trays Using Heatshrink Splice Protectors
Admonishments
The precautionary terms used by Corning Cable Systems in its standard recommended procedures
conform to the guidelines expressed in the American National Standards Institute document (ANSI
Z235) for hazard alert messages. Alerts are included in this instruction based on the following:
DANGER indicates an imminently hazardous situation which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation which, if not
avoided, could result in death or serious injury.
CAUTION indicates a hazardous situation which, if not avoided, may
result in minor or moderate injury.
3.14 Splicing in Trays (Optional)..................................................................................................20
3.14.1 Select the buffer tube to be spliced. .........................................................................20
3.14.2 Store spliced trays. ....................................................................................................21
3.14.3 When splicing ribbon express cable:........................................................................21
3.15 Seal the Canister Closure .....................................................................................................21
3.15.1 Install seal .................................................................................................................21
3.15.2 Install the canister cover...........................................................................................22
3.16 Install a Flash Test Air Valve .................................................................................................23
3.16.1 Install valve stem.......................................................................................................23
3.16.2 Perform flash test .....................................................................................................24
3.16.3 Remove air valve ....................................................................................................... 24
3.17 Ground the Closure ..............................................................................................................24
4. Reentering the Closure .................................................................................................................. 25
5. Reopening the End Cap .................................................................................................................25
Customer Service and Information ...................................................................................... 26

SRP 003-544 • Issue 6 • May 2004 Page 3
SCF-6 and SCF-8 Open Ribbon System (ORS) Canister Splice Closures
1. CARTON CONTENTS
• (1) Tray stacker (Two in -02 configurations)
• (1) Dome cover
• (1) End cap
• (1) Clamping ring
• (1) Sealing ring
• (1) Frame assembly
• (2) Drop port hardware kit
• (2) Drop bracket
•(2)
7/16 x 1-inch hose clamp
• (2) Central member restraint cap
• (6) #8 Washer
• (4) Nylon lock nut
• (2) #10-32 Philips-head screw
• (2) Toothed washer
• (2) 18mm sealing grommet
• (2) 14mm sealing grommet
• (2) 10mm sealing grommet
• (2) Compression screw
• (1) Express port hardware kit
• (2) Express bracket
•(2)
3/4x 11/2-inch hose clamp
•(2)
7/16 x 1-inch hose clamp
• (2) Central member restraint cap
• (4) #8 Washer
• (4) Nylon lock nut
• (1) Accessory kit
• (1) Cleaning tissue
• (1) Sealing paste - labeled
“dichtpaste”
• (1) Sealing tape
• (2) 8-inch Ground wire
• (1) UCN Lubricant
• (1) Brush
• (5) Small cable ties
• (2) M6x40 hex-head screw
• (2) M6x90 hex-head screw
•(4)
1/4x 3/4x 1/16 washers
• (1) Vented grounding screw
• (1) Solid grounding plug
• (2) Grounding assemblies
• (1) Combination wrench tool, for
either the SCF-6 or SCF-8
Closure (Table 1)
A — Wrench for closing screw
B — Wrench for grounding screw
C — Maximum diameter for tape-wrapped cable in express ports
D — Maximum cable diameter for medium (21 mm) rubber sealing grommet
E — Maximum cable diameter for small (16.5 mm) rubber sealing grommet
F — Maximum cable diameter for large (25 mm) rubber sealing grommet
G — Wrench for compression screw
H — Endcap closing gauge
K — Minimum cable diameter for small (12 mm) rubber sealing grommet
L — Minimum cable diameter for smallest (8-11 mm) rubber sealing grommet
Table 1 — Combination Wrench Tool
A — Wrench for closing screw
B — Wrench for grounding screw
C — Maximum diameter for tape-wrapped cable in express ports
D — Maximum cable diameter for medium rubber sealing (14 mm)
E — Maximum cable diameter for small rubber sealing (10 mm)
F — Maximum cable diameter for large rubber sealing (25 mm)
G — Wrench for compression screw
H — End cap closing gauge
K — Minimum cable diameter for small rubber sealing (5 mm)
SCF-6 Combination Wrench
SCF-8 Combination Wrench

SCF-6 and SCF-8 Open Ribbon System (ORS) Canister Splice Closures
Page 4 SRP 003-544 • Issue 6 • May 2004
3. INSTALLING THE CLOSURE
NOTE: Fiber optic cable is sensitive to excessive pulling, bending and crushing forces. Consult the cable
specification sheet for the cable you are installing. Do not bend the cable more sharply than the
minimum recommended bend radius. Do not apply more pulling force to the cable than
specified. Do not crush the cable or allow it to kink. Doing so may cause damage that can alter
the transmission characteristics of the cable – the cable may have to be replaced.
WARNING: Do not install this unit or work with telephone wiring during a
lightning storm. Telephone lines can carry high voltages from lightning causing electrical
shock resulting in severe injury or death.
CAUTION: The wearing of safety glasses to protect the eyes from accidental injury is
strongly recommended when handling chemicals and cutting fiber. Pieces of glass fiber are
very sharp and can damage the cornea easily.
CAUTION: The wearing of safety gloves to protect hands from accidental injury is
strongly recommended when using sharp instruments.
3.1 Prepare the Express Cable
IMPORTANT: Typical lengths are illustrated. Since the actual application may vary, it is
recommended to route the buffer tubes as they will lie in the closure to determine
actual strip lengths before cutting fibers. Refer to routing illustrations, if necessary.
Step 1 Remove indicated length of cable sheath and armor (where applicable) according
to cable manufacturer’s instructions (Figure 2).
NOTE: Do not expose the bare fibers until after the cable has been placed in the closure end cap.
Step 2 Cut the central strength member of each cable to 15 cm (6 inches) from the sheath
using side cutters.
Step 3 If aramid yarn is present, leave an excess length of yarn (approximately 6 inches)
for additional strain-relieving.
IMPORTANT: To prevent damage to the fiber, remove all uncut express fiber from the tubing using
the universal access tool (p/n UAT2-000 - purchased separately).
2. TOOLS AND EQUIPMENT REQUIRED
The following tools and materials are required to complete this installation:
• Tape measure
• Scissors
• Side cutters
• Cable knife
•11/32-inch nut driver
•1/2-inch deep socket and ratchet
•3/8-inch nut driver
• Adjustable wrench
•5/16-inch nut driver (to install sheath
retention clamp)
•7/16-inch nut driver
• 10 mm socket and ratchet
• Flat-tip screwdriver
• Phillips-head screwdriver
• Permanent marker pen
• Paint marker pen
• Hand pump
• Air pressure gauge
• Torque wrench
• Vinyl tape
• Soapy water (to verify leaks)

SRP 003-544 • Issue 6 • May 2004 Page 5
SCF-6 and SCF-8 Open Ribbon System (ORS) Canister Splice Closures
Figure 2 — Express (Non-mid-span) Cable
Tray Slack
CABLE
CABLE CABLE
CABLE
Ribbon Cable for Express orDrop Cable
(non-mid-span)
Central Tube
18 cm (7 in.)
275 cm (108 in.)
Single Cable Mid-span in Express Ports
Central Tube Central Tube
18 cm (7 in.) 18 cm (7 in.)
365 cm (144 in.)
190 cm (75 in.)
Buffer Tubes
Tray Slack
CABLE
Single Fiber (with Buffer Tubes) Drop Cable
69 cm (27 in.)
260 cm (102 in.) 114 cm (45 in.)
SCF-6C28-ORS and SCF-8C28-ORS
SCF-6C22-ORS
Tray Slack
CABLE
CABLE CABLE
CABLE
Ribbon Cable for Drop Cable
(non-mid-span)
Central Tube
18 cm (7 in.)
244 cm (96 in.)
Single Cable Mid-span in Express Ports
Central Tube Central Tube
18 cm (7 in.) 18 cm (7 in.)
305 cm (120 in.)
183 cm (72 in.)
Buffer Tubes
Tray Slack
CABLE
Single Fiber (with Buffer Tubes) Drop Cable
56 cm (22 in.)
226 cm (89 in.) 127 cm (50 in.)
Cut line for drop cable
Cut line for drop cable

SCF-6 and SCF-8 Open Ribbon System (ORS) Canister Splice Closures
Page 6 SRP 003-544 • Issue 6 • May 2004
Figure 3 — Grounding Hardware
3.2 Install Grounding Hardware (Armored Cable Only)
Ground armored cables using the hardware in the accessory kit as shown in Figure 3. Additional
armored cables must also be grounded using a grounding kit purchased separately from your
customer service representative.
IMPORTANT: Do not install express cables until Section 3.4 or drop cables until Section 3.7.
1234
2.5cm(1in.)
1
Stop
Base Plate
2
5cm(2in.)
5
3
Extension
Bracket
Top Plate
4
Extension bracket not shown.
Extension bracket not shown.
Step 1 Cut a slit into opposite sides of the
outer sheath and armor about 2.5
cm (1 inch). To do this, score the
armor with a cable knife (being
careful not to damage the inner
sheath) and split the sheath by
flexing it.
Step 2 Position the grounding clamp base
plate under the armor. The stops of
the clamp should just touch the
outside of the armor and sheath.
Tap the sheath above the ground
clamp base to drive the teeth on the
plate into the cable sheath.
Step 3 Position the top plate and lock nut
on the outer sheath over the base
plate. Tighten with a 3/8-inch
wrench so that the teeth on the
upper plate are driven into the
sheath.
NOTE: When the cable has metal strength
members, attach the extension bracket to
the base plate as shown in the inset before
installing the top plate.
Step 4 Wrap the grounding clamp and
split portion of the cable sheath
with vinyl tape.
Step 5 Place the eyelet on the ground wire
over the stud on the base plate. Add
a second lock nut and tighten using
a 3/8-inch wrench.
NOTE: Ground lead will be attached to endcap in a
later step.

SRP 003-544 • Issue 6 • May 2004 Page 7
SCF-6 and SCF-8 Open Ribbon System (ORS) Canister Splice Closures
Figure 4 — Strain-relief Bracket
3.3 Install Express Strain-relief Hardware
Determine cable and strength member type and proceed accordingly:
• Strength members in single-tube cables must be separated by the restraint cap threaded
stud.
• Single strength members in loose tube design cables must be secured in the cap.
• Cables (central tube) with sheath-mounted GRP (Glass Reinforced Plastic) strength
members need only the strength member(s) on one side of the cable secured in the cap.
IMPORTANT: If the cable used is made with metallic strength members, use the grounding
hardware as for the armored cable, with the extension bracket to strain-relieve the
metallic strength members and ground them. Refer to Section 3.2.
3.3.1 Strain-relief bracket(s)
Install strain-relief bracket(s) onto the opposite side (180 degrees) from the grounding clamp, if
applicable:
Step 1 Place a hose clamp over the cable and bracket 18 mm (0.75 inches) below the
sheath end.
IMPORTANT: If grounding hardware is used, make sure the hose clamp does not overlap the ground
clamp.
0.75 inch
0.5 inch
Threaded Stud
Yarn
Hose Clamp
Tensioning Body
Mark
Cable
Step 2 Tighten the hose clamp in the
notch on the bracket with the
tensioning body on the hose
clamp on the same side of the
bracket as the threaded stud
(Figure 4). Tighten hose clamp
to a torque value of 10 in-lb for
nonarmored cable or 17 in-lb for
armored cable.
Step 3 Place a washer over the threaded
stud on the strain-relief bracket.
Step 4 Wrap the yarn (if present) twice,
clockwise, around the threaded
stud (Figure 4).
Step 5 Install a washer and nut and
tighten securely.
Step 6 Mark the cable in the location
shown in Figure 4.
Step 7 Repeat for the second cable,
when applicable.

SCF-6 and SCF-8 Open Ribbon System (ORS) Canister Splice Closures
Page 8 SRP 003-544 • Issue 6 • May 2004
3.3.2 Nonmetallic strength member
If strength member is nonmetallic:
Step 1 Trim the strength member flush with the top of the strain-relief bracket (Figure 5).
Step 2 Insert the restraint cap threaded stud
through the upper hole in the strain-
relief bracket capturing the strength
member between the two.
Step 3 With the nonmetallic strength
member behind the bracket, install a
nut on the restraint cap threaded stud
(Figure 5).
Step 4 Confirm buffer tubes are clear of the
strength elements. Tighten nut
securely.
Step 5 Repeat for the second cable, when
applicable.
3.3.3 Metallic strength members
If strength members are metallic:
Step 1 Bend them over the slots in the extension bracket as shown in the inset in Figure 6
and then trim excess strength member.
Step 2 Insert the restraint cap threaded stud through the upper hole in the strain-relief
bracket capturing the strength member between the two.
Step 3 Install restraint cap as shown in Figure 6.
Step 4 Install a washer and nut and tighten securely.
Step 5 Repeat for other cables, when applicable.
IMPORTANT: Confirm all buffer tubes are clear of the strength elements prior to securing the
restraint cap.
Restraint Cap
Strength Member
Figure 5 — Strength Member Strain-relief
Metallic Strength Members
Restraint
Cap
Yarn
Figure 6 — Metallic Strength Member Strain-relief

SRP 003-544 • Issue 6 • May 2004 Page 9
SCF-6 and SCF-8 Open Ribbon System (ORS) Canister Splice Closures
3.3.4 Large strength members
For cables with large strength members, use the supplied strain-relief kit, instead of the restraint
caps (Figure 7):
Figure 7 — Large Strength Member Strain-relief
Step 1 Slide the metal tube over the end
of the central member.
Step 2 Align the threads in the side of the
tube with the hole in the top of the
strain-relief bracket.
Step 3 Install the supplied screw through
the threaded hole in the tube.
Step 4 Tighten the screw.
Step 5 Trim the strength member flush
with the top of the strain-relief
bracket.
Figure 8 — Express Ports
Figure 9 — Endcap Standoffs
3.4 Install Cable into the Endcap Express Ports
NOTE: Installation is illustrated using the SCF-8 closure;
the procedure is the same for the SCF-6 closure.
3.4.1 Prepare the endcap
Step 1 Remove the frame from the end cap.
Step 2 Pull the end cap halves apart.
IMPORTANT: Do not use power tools to separate the
end caps.
NOTE: Use the two main cable ports in the center of the
end cap first (Figure 8). Use the drop ports as
needed.
Step 3 Beginning with the inside of the end
cap, apply sealing tape to the end cap
half containing the metallic standoffs
(Figure 9). Cut holes in the tape to
expose the standoffs.
IMPORTANT: It is imperative that the strain-relief
bracket have no contact with the tape.
Make sure the strain-relief tracks on
the inside of the end cap and the screw
holes are not obstructed by the sealing
tape.
SCF-6 End Cap
SCF-8 End Cap

SCF-6 and SCF-8 Open Ribbon System (ORS) Canister Splice Closures
Page 10 SRP 003-544 • Issue 6 • May 2004
Step 4 Starting at the mark shown in
Figure 10, wrap the tape
around the cable until it fills
the diameter “C” on the
combination wrench tool
(Figure 12a). Express ports
will accommodate cable with
a maximum diameter of 32
mm (1.2 inch); some cables
require only one wrap of
sealing tape to reach this
diameter. Always finish with a
complete wrap that overlaps
the starting point by 1/2inch
(Figure 12b).
3.4.2 Apply sealing tape to the cable
CAUTION: Isopropyl alcohol is flammable with a flashpoint at 54
°
F. It can cause
irritation to eyes on contact. In case of eye contact, flush eyes with water for at least 15
minutes. Inhaling fumes may induce mild dizziness. In case of ingestion, consult a
physician.
Figure 10 — Apply Sealing Paste
Figure 11 — Sealing Tape
AB
Figure 12 — Measure Sealing Tape Around Cable
Step 1 Clean the cable where the tape will be
applied using the provided alcohol pad.
Step 2 Beginning at the mark shown in Figure 10,
use wax-paper backing from the sealing tape
to spread the “dichtpaste” sealing paste
evenly around the cable in the area where
the sealing tape will be applied (Figure 10).
Wait for the sealing paste to dry.
Step 3 Cut and pull the strip of sealing
tape as shown in Figure 11. The
tape will stretch and thin before it
breaks.
NOTE: The combination wrench is used in several steps during the assembly process. Use only this
wrench for measuring and tightening components where indicated (Table 1).
Step 5 Repeat Section 3.4.1 and 3.4.2 for the other cable to be installed in the express
port, if applicable.
D
ICHTPASTE
0.5in.
10 mm
(.25 in.)
0.5 in.
C

SRP 003-544 • Issue 6 • May 2004 Page 11
SCF-6 and SCF-8 Open Ribbon System (ORS) Canister Splice Closures
Location for
Long Bolts
Location
for
Short
Bolt
Figure 15 — Close Endcap Halves
Figure 14 — Install Caple into Endcap
Strain-relief Tracks
Sealing Ring
Channel
Sealing Ring
Channel
Figure 13 — Dummy Plug
3.4.3 Using dummy plug
When the closure only has one cable installed in either endcap, use a dummy plug (purchased
separately) to fill the unused port. If using a dummy plug:
Step 1 Follow instructions in Section 3.4.2 to
apply sealing paste and tape to the dummy
plug.
Step 2 Install dummy plug with the closed end of
the plug flush against the outside of the
end cap (Figure 13).
3.4.4 Install cable
Step 1 Place one express port cable assembly on the taped end cap half (Figure 14) in the
center express port by inserting the strain-relief bracket in the tracks.
Step 2 Place the other express port cable assembly in the other express port on the
untaped end cap half by inserting the strain-relief bracket in the tracks.
3.4.5 Close end cap halves
IMPORTANT: Do not use power tools to tighten the end caps.
Step 1 Place the upper end cap segment
over the lower end cap segment.
Step 2 Install one short bolt and washer
on each side of the end cap
segment.
Step 3 Install two long bolts and washers.
Step 4 Alternately tighten the bolts to
close the end cap (Figure 15).
IMPORTANT: While tightening, ensure that
the feet of the strain-relief
bracket remain inside the
tracks. Do not use power tools to
tighten.

SCF-6 and SCF-8 Open Ribbon System (ORS) Canister Splice Closures
Page 12 SRP 003-544 • Issue 6 • May 2004
NOTE: Do not pull or stretch sealing
tape.
Step 7 Completely remove any
remaining sealing tape
inside the sealing ring
channel with the blade
of a screwdriver.
Vented
Grounding
Plug
Figure 17 — Ground End Cap
Step 5 Tighten the bolts until the end cap closing gauge (Section H) on the combination
wrench fits over the sides and center measuring points of the end cap (Figure 16).
Step 6 Cut excess sealing tape from the sealing ring channel (shown by dashed circles in
Figure 14) and strain-relief tracks using scissors or side cutters.
3.4.6 Install vented grounding plug
Install the vented grounding plug from the small, colored plastic bag:
Step 1 Apply a thin coat of UCN lubricant to the threads of the vented grounding plug.
Step 2 Install the vented grounding plug in the threaded insert on the inside of the end
cap finger-tight plus one half turn (approximately 40 to 60 in-lb).
3.4.7 Complete frame assembly
Reattach the frame assembly to the end cap.
3.5 Ground Armored Cable
Ground armored cable per local practices. Additional ground kits are purchased separately.
Step 1 Remove the small insert from the grounding plug and install a grounding wire.
Tighten the insert.
Step 2 Secure the other end of this grounding wire to the ground clamp post of one of the
main cables in the express ports.
Figure 18 — Open Drop Port
H
H
H
H
Figure 16 — End cap Closing Gauge
Step 3 Attach one end of a second grounding
wire to this ground clamp post.
Step 4 Attach the opposite end of the second
wire to the second expressed cable
(Figure 17).
3.6 Prepare Drop Cable Port(s)
Step 1 Choose a cable port to be used and open the
port using a hacksaw or a knife (Figure 18).
IMPORTANT: Use either or both of the middle ports on the
end cap first to make routing easier.

SRP 003-544 • Issue 6 • May 2004 Page 13
SCF-6 and SCF-8 Open Ribbon System (ORS) Canister Splice Closures
Refer to SRP 206-286 (Mechanical End Cap Canister Closure Sealing Checklist) to ensure all
critical steps in Sections 3.4 and 3.6 for sealing the closure have been performed accurately.
Step 2 Smooth the port opening using a cable knife as
shown in Figure 19.
Step 3 Place the combination wrench to determine
which size sealing grommet is required (Figure
20 and Table 2).
Figure 19 — Smooth Port Opening
Figure 20 — Sealing Grommet Size
Table 2 — Cable Diameter
Figure 21 — Washer Orientation
Step 4 Place a toothed washer onto the sealing
grommet and insert both into the opened
port from the strain-relief side of the end
cap (Figure 21). Verify correct placement
of toothed washer on grommet.
Cable
Cable
D
Cable
Cable
D
Greater than
or equal to: Less than:
18 mm AND Large
AND Medium
AND Small
5 mm
NOTE: Dimensions are for reference only.
Use SCF6 combination wrench to determine cable size.
Cable
Diameter
Range:
If Cable Diameter Is:
Cable is too small for sealing system.
Select
Grommet
Size
Wrench Gauge
"D"
Wrench Gauge
"E"
Wrench Gauge
"K"
Less than "K"
Wrench Gauge
"F"
Wrench Gauge
"D"
Wrench Gauge
"E"
Cable
Cable
D
Cable
Cable
D
Greater than
or equal to: Less than:
25 mm AND Large
AND Medium
AND Small
AND Smallest
8 mm
NOTE: Dimensions are for reference only.
Use SCF8 combination wrench to determine cable size.
Cable
Diameter
Range:
If Cable Diameter Is:
Cable is too small for sealing system.
Select
Grommet
Size
Wrench Gauge
"F"
Wrench Gauge
"D"
Wrench Gauge
"E"
Wrench Gauge
"K"
Less than "L"
Wrench Gauge
"D"
Wrench Gauge
"E"
Wrench Gauge
"K"
or equal to
Wrench Gauge
"L"
Toothed
Washer
Sealing Grommet

SCF-6 and SCF-8 Open Ribbon System (ORS) Canister Splice Closures
Page 14 SRP 003-544 • Issue 6 • May 2004
3.8 Strain-relieve Drop Port Cables
Install a drop port strain-relief bracket onto each drop port cable on the opposite side of the
cable (180 degrees) from the ground clamp, if applicable:
Step 1 Pull the cable approximately 12 inches away from the end cap to ease bracket
installation.
IMPORTANT: Secure the cable to the side of the
bracket opposite the threaded
stud.
Step 2 Place a hose clamp over the cable
and bracket 18 mm (0.75 inch)
below the sheath end.
IMPORTANT: If grounding hardware is used,
make sure the hose clamp does
not overlap the ground clamp.
Step 3 Tighten the hose clamp in the
notch on the bracket with the
tensioning body on the hose clamp
on the same side of the bracket as
the threaded stud (Figure 24).
IMPORTANT: If the cable used is made with
metallic strength members, use the
grounding connector as for the
armored cable, with the extension
bracket to strain-relieve the strength
member and ground it. Refer to
Sections 3.2 and 3.3.
3.7 Install Drop Port Cable into End cap
Step 1 Secure the sealing grommet and toothed washer with
the lock nut on the inside of the end cap.
Step 2 Use the combination wrench to tighten the nut until it
stops and is tight (Figure 22).
Step 3 Slide the compression screw over the cable.
Step 4 Slide the cable through the port (Figure 23).
A
A
Figure 22 — Lock Nut
Figure 23 — Compression Screw
Threaded
Stud
Yarn Bracket
Hose Clamp
Tensioning Body
Mounting
Screw
Restraint Cap
0.75 inch
Figure 24 — Drop Cable Strain-relief Bracket
Step 5 Prepare cable per Section 3.1. If the cable is armored, attach grounding hardware
as shown in Figure 3.
Tighten hose clamp to a torque value of 10 in-lb for nonarmored cable or 17 in-lb
for armored cable.
Step 4 Place a washer on the threaded stud located to the rear of the bracket.
Step 5 Wrap the yarn (if present) twice, clockwise, around the stud.
Step 6 Trim nonmetallic strength member flush with the top of the bracket.
Step 7 Install a second washer and nut and tighten securely.
IMPORTANT: Ensure that all buffer tubes are cleared from beneath the strength member prior to
tightening the restraint cap.

SRP 003-544 • Issue 6 • May 2004 Page 15
SCF-6 and SCF-8 Open Ribbon System (ORS) Canister Splice Closures
3.9 Attach Strain-relief Bracket
Attach the strain-relief bracket to the frame:
Step 1 Pull the cable back to the end cap.
Step 2 Center the cable over the port and slide
the attached screw on the strain-relief
bracket into the slot on the metal frame.
Step 3 Tighten the strain-relief bracket
mounting screw (Figure 25).
Step 4 Repeat Section 3.6 through Section 3.8
for all drop cables.
Refer to SRP 206-286 (Mechanical End Cap Canister Closure Sealing Checklist) to ensure all
critical steps in Sections 3.7 and 3.10 for sealing the closure have been performed accurately.
Figure 25 — Install onto Frame
H
D
EG
Figure 26 — Secure Tube to Frame
SCF-6
SCF-8
Cable Tie
IMPORTANT: When drop cable contains ribbon fiber,
secure the central tube to the frame using
a cable tie as shown in Figure 26.
3.10 Tighten End Cap Compression Screw
Secure compression screw into end cap. Tighten with the
combination wrench until the clicking sound stops or the
screw is butted against the end cap (Figure 27).
IMPORTANT: DO NOT overtighten the screw.
Figure 27 — Tighten Compression Screw

SCF-6 and SCF-8 Open Ribbon System (ORS) Canister Splice Closures
Page 16 SRP 003-544 • Issue 6 • May 2004
3.11 Attach Frame to End Cap
Step 1 Secure the end cap on the work
surface (table). An optional
installation bracket (purchased
separately) is available.
Step 2 Separate the ribbon fibers from
the drop port into two groups.
Step 3 Lay all the ribbon fiber from
the express ports in a bundle
between the two groups
(Figure 28).
Step 4 Hold the uncut express fibers in
one hand and the ORS frame in
the other hand.
Step 5 Carefully reposition the ORS
frame and secure it to the end
cap.
3.12 Load the ORS
WARNING: Never look
directly into the end of a fiber
that may be carrying laser light.
Laser light may be invisible and
can damage your eyes. Viewing it
directly does not cause pain. The
iris of the eye will not close
involuntarily as when viewing a
bright light. Consequently,
Express
Cable
Drop Cable Drop Cable
Clip “A”
serious damage to the retina of the eye is possible. Should accidental eye exposure to laser
light be suspected, arrange for an eye examination immediately.
WARNING: DO NOT use magnifiers in the presence of laser radiation. Diffused
laser light can cause eye damage if focused with optical instruments. Should accidental eye
exposure be suspected, arrange for an eye examination immediately.
IMPORTANT: Basic ribbon fiber routing requires Ribbon “A” spliced to Ribbon “B”. Ribbon “B”
will be routed to the side storage compartment and side of the splice plane opposite
from ribbon “A”.
3.12.1 Route express fibers
Step 1 Loop the express ribbon in the middle compartment of the ORS and temporarily
secure with tape.
IMPORTANT: DO NOT secure the uncut express slack in the plastic clip (“A”) on the interior of
the middle compartment. This clip is to secure the fibers from the express port that
are to be spliced as they are routed from the express compartment to the side storage
compartment.
Figure 28 — Load ORS Frame

SRP 003-544 • Issue 6 • May 2004 Page 17
SCF-6 and SCF-8 Open Ribbon System (ORS) Canister Splice Closures
Step 2 Determine the length
required and cut the express
fibers to be spliced.
Step 3 Open the first clip (“A”) in
the middle compartment.
Step 4 Route the cut express fibers
(that are to be spliced)
through the clip and into the
side storage area. Note the
counterclockwise path as
shown in Figures 29 and 30
for this particular side.
Step 5 Loop all the express ribbon
fibers (that are to be spliced)
from the express area and into
their respective side storage
areas.
NOTE: A loop of fiber slack can be stored in
the side storage areas with the loop
routed respectively for each side as
shown in Figure 29. The loop is
limited at the bottom by the metal
retaining bracket and at the top by
the plastic clip (“B”).
Figure 29 — Route Through Clip A
Clip “B”
Retaining Bracket
Figure 30 — Route Through Clip B
Cover
Express Cover
Step 6 Attach the express cover
once the fibers are routed
into the side storage area
(Figure 31).
Step 7 Leave the extra length of
fibers lying on the table.
Wrap the bundle
temporarily with tape.
Figure 31 — Attach Express Cover

SCF-6 and SCF-8 Open Ribbon System (ORS) Canister Splice Closures
Page 18 SRP 003-544 • Issue 6 • May 2004
3.12.2 Route drop cable fibers
Step 1 Route fiber from the drop port cable directly into the side storage compartment.
Step 2 When splicing to more than one drop cable, prepare the other side for routing per
Section 3.12.1.
IMPORTANT: Do not move fibers to the splice plane until both sides are routed.
3.12.3 Route fibers to the splice plane
Splice Plane Cover
Figure 32 — Remove Splice Plane Cover
Step 1 Carefully turn the closure
over until the splice plane is
on top. Remove the splice
plane cover (Figure 32).
Step 2 Take the bundle of fibers
wrapped in tape through the
side plastic clip (“B”) and
remove the tape.
Clip “C”
Step 3 Close the clip to secure the fibers
within it (Figure 33).
Step 4 Open the plastic clip on the splice
plane (Clip “C”) and lay the fibers
inside.
Clip “B”
Figure 33 — Clip B
Figure 34 — Clip C
Step 5 Carefully close Clip “C” (Figure 34).
Step 6 Lay the fibers all the way down the
splice plane on the side of the
organizer. Maintain a full loop of slack
in the storage area.
Step 7 Temporarily secure the fibers at the
bottom of the ORS with another piece
of tape (Figure 35).
Step 8 Repeat Section 3.12.2 for the drop
cable routed on the other side.
Clip “C”
Clip “B”
Clip “B”

SRP 003-544 • Issue 6 • May 2004 Page 19
SCF-6 and SCF-8 Open Ribbon System (ORS) Canister Splice Closures
3.13 Splice
IMPORTANT: Before cutting, make sure there is a complete loop of fibers in the side storage
compartment and the fibers lie neatly in the trough of the splice plane.
3.13.1 Prepare fibers for splicing
Step 1 To ensure the appropriate length of slack fibers, cut the fibers extending beyond
the bottom of the closure as shown in Figure 35.
Step 2 Remove the tape from the fibers.
Step 3 Remove the fibers from the top plastic clips (Clip “C”).
Step 4 Lay all fibers on the table.
Tape to Endcap
Step 5 Determine which two ribbon
fibers are to be spliced (one
from the left and one from the
right).
Step 6 Route them through the clip
again and into the bottom of
the closure. Do not close the
clip at this time.
Step 7 Bring the two fibers to the first
position in the organizer.
Step 8 Temporarily lay the fibers in
the organizer to determine the
required length.
Figure 35 — Cut Excess Fibers
Figure 36 — Splice Organizer
Step 9 Cut both fibers at the same time in the center of the organizer.
3.13.2 Splice fibers
Splice the fibers according to the instructions for the splicing equipment you are using:
Step 1 Insert the protected splice (heatshrink splice protectors are recommended) back
into the first slot in the organizer.
Step 2 Repeat from Step 5 in Section 3.13.1 for all required splices. Install splices into the
organizer consecutively (Figure 36).
SCF-6 SCF-8
NOTE: Each slot in the organizer accepts
two splices. Install the second
splice on top of the first splice
before proceeding to the next slot
in the organizer.
Step 3 Secure the spliced ribbons
in the clips (Clip “C”) on
the splicing plane
(Figure 34). Confirm the
fibers do not exceed the
minimum bend radius.

SCF-6 and SCF-8 Open Ribbon System (ORS) Canister Splice Closures
Page 20 SRP 003-544 • Issue 6 • May 2004
Step 4 Record splice information
appropriately on the splice label
and attach the splice plane cover
(Figure 37).
Step 5 Secure the plastic cover on
the side compartment using
the wing nuts as shown
(Figure 38).
Figure 37 — Splice Information Label
Figure 38 — Slide Cover Beneath Retaining Bracket
3.14 Splicing in Trays (Optional)
Splice trays (purchased separately) can be used when the drop cable is single-fiber cable with
buffer tubes or small central tubes. A ribbon strain-relief kit (p/n SCF-KT-RTK, purchased
separately) is required before the ribbon can be safely secured to a splice tray. Follow the
instructions provided with the kit.
Figure 39 — Mark Buffer Tube
3.14.1 Select the buffer tube to be spliced
Step 1 Remove the plastic cover from the
side compartment.
Step 2 Route the buffer tube on the
outside of the tray to make sure
there is a loop of fiber (Figure 39).
Step 3 Attach the buffer tube loosely to
the tray using a cable tie
(Figure 39).
Step 4 Mark the buffer tube with a
permanent marker 19 mm
(0.75 inches) from the cable tie.
Step 5 Remove the buffer tube beyond this mark in segments of approximately 304 mm
(12 inches).
Step 6 Prepare all splice trays in the same manner.
Step 7 Follow the instructions provided with the splice tray for detailed splicing
instructions.
IMPORTANT: Do not store buffer tube slack in the same area as the ribbon fibers. Damage to the
ribbon fibers can occur.
Other manuals for SCF-6
1
This manual suits for next models
1
Table of contents
Other CORNING Industrial Equipment manuals
Popular Industrial Equipment manuals by other brands

MÄDLER
MÄDLER Accuride DZ 5417 Installation guides

AVL Looms
AVL Looms E-Lift Installation and user manual

KWM Gutterman
KWM Gutterman PANTHER Operating and maintenance

GESTRA
GESTRA FPS 11 Original Installation & Operating Manual

Bosch
Bosch Rexroth WS200 operating instructions

ABB
ABB HT563760 Operation manual