CORNING Pretium User manual

STANDARD RECOMMENDED PROCEDURE 003-649 | ISSUE 5 | JANUARY 2009 | PAGE 1 OF 10
| PRETERMINATED SYSTEMS | CABLES | CONNECTORS | CABLE ASSEMBLIES | HARDWARE | TOOL KITS AND ACCESSORIES | TEST EQUIPMENT | SPLICE EQUIPMENT | FAN-OUT KITS | TRAINING |
=
Pretium™ Rack-mountable 1U
Housing Hardware
p/n 003-649, Issue 5
table of contents |
1. General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2. Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3. Product Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.1 Unpacking Stubbed Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.2 Removing the Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.3 Mounting the Housing into a Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.4 Installing Cable Entry Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.5 Securing the Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.6 Strain-relieving the Cable Strength Member . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.7 Grounding Armored Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.8 Installing Preconnectorized Cable into Connector Panels . . . . . . . . . . . . . . . . . . . . . . . 6
3.9 Installing Closet Connector Housing Pigtail Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.10 Installing Preconnectorized Cable into Connector Modules (Plug & Play™) . . . . . . . . . 8
3.11 Installing a Buffer Tube Fan-out Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.12 Closing the Housing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.13 Routing Patch Cords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4. Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
revision history |
Issue Date Reason for Change
5 01/2009 Added sections on installing pigtail modules and preconnectorized cable
into connector modules
4 05/2007 Added RoHS logo
3 11/2004 Update drawings with addition of removable bracket
2 03/2004 Corrected drawings in Figure 5
1 07/2003 Initial release
related literature |
LAN-538-EN Pretium Rack-mountable 1U Housing Hardware Product Specifications
LAN 539-EN Pretium Rack-mountable 1U Housing Hardware Ordering Guide

STANDARD RECOMMENDED PROCEDURE 003-649 | ISSUE 5 | JANUARY 2009 | PAGE 2 OF 10
=
admonishments |
The precautionary terms used by Corning Cable Systems in its standard recommended procedures
conform to the guidelines expressed in the American National Standards Institute document (ANSI
Z535) for hazard alert messages. Alerts are included in this instruction based on the following:
1. General
This document describes the installation of Pretium™-01U (Figure 1) Closet Connector Housing
Hardware. The unit fits into 19-inch utility racks and occupies one rack space. Factory stubbed units
are also available. Contact your customer service representative to order other mounting
configurations or to purchase accessories that are sold separately.
DANGER: indicates an imminently hazardous situation which, if not avoided, will
result in death or serious injury.
WARNING: indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury.
CAUTION: indicates a hazardous situation which, if not avoided, may result in
minor or moderate injury.
KPA-1191
Figure 1 — PCH-01U Housing
Dimensions
(H x W x D)
1.75 x 17 x 12 in.
(4.5 x 43 x 28.5 cm)
thgieWrebmuNtraP
)gk3.2(bl5U10-HCP
KPA-1192

STANDARD RECOMMENDED PROCEDURE 003-649 | ISSUE 5 | JANUARY 2009 | PAGE 3 OF 10
=
2. Components
The main components of the Pretium 1U hardware unit are illustrated in Figure 2. Cable and patch
cords can enter from either side of the housing.
3. Product Installation
3.1 Unpacking Stubbed Units
If you are installing a stubbed unit, follow the directions provided with the shipping container to
remove the stubbed unit from its packaging. Place the unit on a work surface to perform the
preliminary work before mounting the unit into a rack.
3.2 Removing the Cover
Removing the cover is optional but is recommended to ease installation
Step 1: Open front and rear doors.
Step 2: Locate the plunger fasteners at the front of the unit under the housing cover and pull out
to release the plungers (Figure 3).
Step 3: Lift stop latches and slide the cover toward the front until it is clear of the base. Set the
cover aside.
Cable Tie Locations
Mounting Bracket
Shown in Standard
5-inch Frontal
Projection Position
Radius Control Guides
Rear Tray
Stop Latch
Patch Cord Routing Guides
Front Tray
Stop Latch
Mounting
Bracket
Location for
3-inch
Removable Door
Lock Plug
Projection
From Rack
Removable Bracket
KPA-1193
Figure 2 — Components (Cover Removed for Clarity)
Plunger Fasteners
KPA-1194
Figure 3 — Remove Cover

STANDARD RECOMMENDED PROCEDURE 003-649 | ISSUE 5 | JANUARY 2009 | PAGE 4 OF 10
=
3.3 Mounting the Housing into a Rack
Attach the unit to the equipment rack using the four screws provided. Two screw are required per
side of the housing.
3.4 Installing Cable Entry Plate
Step 1: Determine location for cable entry into housing.
Step 2: Slide drawer back completely. The drawer must be in this position to prevent fiber
damage during drawer actuation.
Step 3: Install cable entry plate using the provided wing nut (Figure 4) at the location where the
cable will enter the housing.
Step 4: Install the strain-relief bracket to the side of the housing (Figure 4) at the location where
the cable will enter the housing.
3.5 Securing the Cable
NOTE: Fiber optic cable is sensitive to excessive pulling, bending, and crushing forces.
Consult the cable specification sheet for the cable you are installing. Do not
bend the cable more sharply than the minimum recommended bend radius.
Do not apply more pulling force to the cable than specified. Do not crush
the cable or allow it to kink. Doing so may cause damage than can alter the
transmission characteristics of the cable; the cable may have to be replaced.
The cable may be strain-relieved using the Universal Cable Clamp (UCC) or cable ties.
3.5.1 Using the UCC
Step 1: Attach the UCC clampshell to the strain-relief bracket as shown in Figure 5 to allow
installation of a second UCC if necessary.
Step 2: Follow installation instructions provided with the UCC kit to secure the cable. Allow room
on the bracket to strain-relieve the strength member, if necessary. Do not tighten yet to
allow for cable adjustment if necessary.
Step 3: Secure cable to cable entry plate using a cable tie. Do not tighten cable tie.
Cable Entry Plate
Strain-relief Bracket
KPA-1195
Figure 4 — Install Cable Entry Plate

STANDARD RECOMMENDED PROCEDURE 003-649 | ISSUE 5 | JANUARY 2009 | PAGE 5 OF 10
=
3.5.2 Using Cable Ties
If at least 10 m (33 ft) of outside plant cable is routed within an environmentally controlled building
where temperature fluctuation is minimal, securing the cable sheath is adequate strain-relief.
CAUTION: Wear safety glasses to protect your eyes from accidental injury when
handling chemicals and cutting fiber. Pieces of glass fiber are very sharp and can
damage the eye easily.
CAUTION: Wear safety gloves o protect hands from accidental injury when using
sharp instruments.
Step 1: Attach the cable to the strain-relief bracket with cable ties in two places as shown in
Figure 6.
Step 2: Allow room on the bracket to strain-relieve the cable strength member, if present.
Bracket Orientation for Top Cable Entry Bracket Orientation for Bottom Cable Entry
KPA-1196
Figure 5 — Strain-relieve Using UCC
Cable Ties
Yarn (If Present)
Strength Member
Flat Washer
U-shaped
Washer
KPA-1197
Figure 6 — Strain-relieve Strength Member

STANDARD RECOMMENDED PROCEDURE 003-649 | ISSUE 5 | JANUARY 2009 | PAGE 6 OF 10
=
3.6 Strain-relieving the Cable Strength Member
Step 1: Install the U-shaped washer and the flat washer on the strain-relief bracket using the
supplied Phillips-head machine screw (Figure 6).
Step 2: Place the yarn, if present, and the central member between the U-shaped washer and the
flat washer.
Step 3: Wrap yarn around the screw in a clockwise direction and under the U-shaped washer.
Step 4: Tighten the nut.
Step 5: Trim off the excess yarn and central member.
3.7 Grounding Armored Cable
• One grounding kit (p/n FDC-CABLE-GRND, purchased separately) is required to ground each
armored cable. Follow instructions provided with the grounding kit.
• Attach the other end of the ground wire to the equipment rack. The equipment rack must be
grounded to the primary building ground.
• Remove the paint from the frame at the grounding location to ensure metal-to-metal contact. It is
recommended to use an antioxidant on the bare metal to prevent corrosion.
• Or, attach the other end of the ground wire to a rack-mounted grounding bus bar, which is
grounded to the primary building ground.
3.8 Installing Preconnectorized Cable into Connector Panels
WARNING: Never look directly into the end of a fiber that may be carrying
laser light. Laser light is invisible and can damage your eyes. Viewing it directly
does not cause pain. The iris of the eye will not close involuntarily as when
viewing a bright light. Consequently, serious damage to the retina of the eye is
possible. Should accidental eye exposure to laser light be suspected, arrange for
an eye examination immediately.
WARNING: DO NOT use magnifiers in the presence of laser radiation. Diffused
laser light can cause eye damage if focused with optical instruments. Should
accidental eye exposure to laser light be suspected, arrange for an eye
examination immediately.
CAUTION: Isopropyl alcohol is flammable with a flashpoint at 54°F. It can cause
irritation to eyes on contact. In case of eye contact, flush eyes with water for at
least 15 minutes. Inhaling fumes may cause mild dizziness. In case of ingestion,
consult a physician.
Step 1: Remove the blank panels from the unit and replace with connector panels (purchased
separately).
Step 2: Install connectors into the adapters at the rear of the connector panels (Figure 7).
Step 3: Route cable slack around radius control guides.
IMPORTANT: Lift the tray stop latches and slide the drawer to the forward and back positions to
verify that the drawer slides in the grooves of the guides and that there is enough
fiber slack to prevent violating the minimum fiber bend radius of the cable.

STANDARD RECOMMENDED PROCEDURE 003-649 | ISSUE 5 | JANUARY 2009 | PAGE 7 OF 10
=
3.9 Installing Closet Connector Housing Pigtail Modules
Step 1: Remove the blank panels from the unit and replace with pigtail modules (purchased
separately).
Step 2: If you intend to splice inside the PCH-01U unit using the Splice Tray Kit (p/n PC1-SPLC-
04R), remove the radius control guides and install the splice tray kit per the instructions
provided with it. Route cable slack around kit and into the splice trays. Splice per the
instructions provided with the splice tray (Figure 8).
Step 3: If you intend to splice using an external splice housing, route slack around the radius
control guides and through the rear entry openings to the applicable splice housing above
or below the PCH-01U unit (Figure 9).
IMPORTANT: Lift the tray stop latches and slide the drawer to the forward and back positions to
verify that the drawer slides in the grooves of the guides and that there is enough
fiber slack to prevent violating the minimum fiber bend radius of the cable.
Cable Tie
KPA-1198
Figure 7 — Cable Slack Routing and Connector Installation
Cable Tie
KPA-2227
Figure 8 — Install Splice Tray Kit

STANDARD RECOMMENDED PROCEDURE 003-649 | ISSUE 5 | JANUARY 2009 | PAGE 8 OF 10
=
3.10 Installing Preconnectorized Cable into Connector Modules (Plug & Play™)
Step 1: Using a 6-32 hex nut driver, remove the radius control guides. (This is recommended
when cables enter from the right side of the housing.)
Step 2: Reinstall the nuts onto the radius guide studs to prevent fiber snags.
Step 3: Remove the blank panels from the unit and replace with connector modules (purchased
separately).
Step 4: Install MTP connectors into the MTP adapters at the rear of the connector modules
(Figure 10). Route fiber as shown and loosely secure with cable ties.
IMPORTANT: Lift the tray stop latches and slide the drawer to the forward and back positions to
verify that the drawer slides in the grooves of the guides and that there is enough
fiber slack to prevent violating the minimum fiber bend radius of the cable.
Cable Tie
KPA-2226
Figure 9 — Fiber Routing to External Splice Housing
Cable Tie
KPA-2245
Figure 10 — Install Plug & Play Modules

STANDARD RECOMMENDED PROCEDURE 003-649 | ISSUE 5 | JANUARY 2009 | PAGE 9 OF 10
=
3.11 Installing a Buffer Tube Fan-out Kit
Loose-tube fiber optic cable can be connectorized using Buffer Tube Fan-out (BTF) kits (purchased
separately).
Step 1: Terminate the fibers according to the instruction provided with the BTF kit.
Step 2: Slide drawer back completely and route buffer tube behind the flanges on the drawer and
secure with cable ties. Do not tighten cable ties. Route buffer tube around the radius
control guides.
Step 3: Secure the BTF body to the tray using a cable tie (Figure 11).
Step 4: Continue routing the fiber and install connectors into the adapters at the rear of the
connector panels.
3.12 Closing the Housing
Step 1: Lift up on stop latches and slide drawer toward the front of the housing to make sure
cable is not stressed. If necessary, readjust cable strain-relief to prevent stress on fibers.
Step 2: Slide drawer back to original position.
Step 3: If previously removed, slide the cover back in the retaining flanges on top of the housing.
Push the plunger fasteners to secure.
Step 4: Close the front and rear doors.
3.13 Routing Patch Cords
Install patch cords as specified on planning diagrams. Route patch cords through the routing clips on
either side at the front of the housing (Figure 12).
Provide enough patch cord slack to allow the connector panel tray to slide to the back and forward
positions without violating the minimum bend radius of the patch cord.
Record patch cord routing information on the identification (ID) label provided.
BTF Body
Flanges
KPA-1199
Figure 11 — Fan-out Fiber Routing

STANDARD RECOMMENDED PROCEDURE 003-649 | ISSUE 5 | JANUARY 2009 | PAGE 10 OF 10
Corning Cable Systems LLC √PO Box 489 √Hickory, NC 28603-0489 USA
1-800-743-2671 √FAX +1-828-325-5060 √International +1-828-901-5000 √http://www.corning.com/cablesystems
Corning Cable Systems reserves the right to improve, enhance, and modify the features and specifications of Corning Cable Systems’ products without prior notification.
Pretium and Plug & Play are trademarks of Corning Cable Systems Brands Inc. All other trademarks are the properties of their respective owners. Corning Cable Systems
is ISO 9001 certified.
©2003, 2004, 2007, 2009 Corning Cable Systems. All rights reserved. Published in the USA.
=
4. Maintenance
• Clean external components occasionally with a damp, nonabrasive cloth.
• Check internal components periodically for the following:
•Loose Parts: Check nuts, bolts and screws for looseness and tighten.
•Fiber Bends: Check fiber optic cable to make sure bends do not exceed the minimum bend
radius. Check cable for unnecessary strain. Check cable entries and exits for crimping or
crushing.
•Documentation: Check ID label to make sure it is clear and accurate.
Attach ID label here
Routing Clips
Patch Cords
KPA-1200
Figure 12 — Patch Cord Routing
Table of contents
Other CORNING Rack & Stand manuals
Popular Rack & Stand manuals by other brands

parktool
parktool PCS-10.2 instructions

Herman Miller
Herman Miller Canvas Office Landscape Installation and Disassembly

B-Tech
B-Tech BT899XL-FD Installation guide & parts list

MC Crypt
MC Crypt 31 13 04 operating instructions

Fromm&Starck
Fromm&Starck STAR ATFE 10 user manual

Klip Xtreme
Klip Xtreme KPM-312 manual