CRE Technology SCR2.0 User manual

www.cretechnology.com
SCR
2
.0
Synchroscope and synch check relay
User manual - Technical documenta
ti
on

www.cretechnology.com

A60 X2 9 0020 B EN user manual technical documentation www.cretechnology.com
Content
1PRESENTATION........................................................................................................................................................................5
2INSTALLATION..........................................................................................................................................................................6
2.1 Environmental Requirements..........................................................................................................................................6
2.2 Unpacking.......................................................................................................................................................................6
2.3 Preparation.....................................................................................................................................................................6
2.4 Mounting the Unit...........................................................................................................................................................6
2.5 Wiring the Unit................................................................................................................................................................6
3HUMAN-MACHINE INTERFACE.................................................................................................................................................9
3.1 LED display......................................................................................................................................................................9
3.2 Digital display................................................................................................................................................................10
4PROGRAMMING....................................................................................................................................................................11
5OPERATION ...........................................................................................................................................................................12
5.1 Power-up ......................................................................................................................................................................12
5.2 Status information ........................................................................................................................................................12
5.3 Synchronization checking ..............................................................................................................................................12
6OTHER FEATURES ..................................................................................................................................................................14
6.1 Dead Bus Enable............................................................................................................................................................14
6.2 Synchronization checking delay .....................................................................................................................................14
7MISCELLANEOUS ...................................................................................................................................................................15
7.1 Troubleshooting............................................................................................................................................................15
7.2 Declaration of conformity..............................................................................................................................................15
7.3 Technical specifications.................................................................................................................................................15

A60 X2 9 0020 B EN user manual technical documentation www.cretechnology.com
4
DOCUMENT CONTROL
Version
Date
Changed by
Details
A
July 22nd, 2014
A. Mesnard
First edition
B
Aug. 25th, 2014
A. Mesnard
Minor, chronogram completed

A60 X2 9 0020 B EN user manual technical documentation www.cretechnology.com
5
1PRESENTATION
The unit SCR2.0 is a metering and control module used in manual synchronization and protection panels. It
monitors the voltage and frequency of two power networks and shows the measured values on its 3-digit 7-
segment display. The 24-led circular synchroscope indicates the true instantaneous phase angle between the
networks.
It is powered by a battery.
It can check the synchronization between a generator and its busbar, or a generator busbar and mains.
The measured/calculated parameters are:
Generator phase-to-neutral voltage
Generator frequency
Busbar phase-to-neutral voltage
Busbar frequency
Busbar-generator frequency difference
Busbar-generator voltage difference
Busbar-generator phase difference
The unit is installer-friendly and user-friendly. In addition, programmable parameters give an extended
control over the operation. The programmed values are stored in a non volatile memory; thus all information
is retained even in the event of complete loss of power.
Designation: SCR 2.0 / A60 X2
WARNING
THIS UNIT DOES NOT CHECK THE PHASE SEQUENCE
First make sure the two AC supplies feature the same sequence of the phases
Failure to follow this instruction can damage the equipment

A60 X2 9 0020 B EN user manual technical documentation www.cretechnology.com
6
2INSTALLATION
The unit is designed for panel mounting, which provides user with access only to the front panel.
2.1 Environmental Requirements
Operating temperature: -20°C (-4°F) to 70°C (158°F)
Storage temperature: -30°C (-22°F) to 80°C (176°F)
Maximum humidity: 95% without condensation
2.2 Unpacking
Make sure the packaging contains:
the unit
two clamping sets packaged apart
a delivery bill
Unpack and keep the packaging in event of return.
Make sure the unit does not show scratches or visible defaults. Otherwise describe them on the bill.
2.3 Preparation
1. Cut out the panel to 92x92 mm minimum (3.6 in. x 3.6 in.)
2. Make sure the cut-out is smooth and clean
2.4 Mounting the Unit
Tool: cross-head screwdriver size 1.
To mount the unit:
3. Pass the unit through the panel
4. In the rear, insert the tab of a clamping set into the hole on one side of the unit, and screw the unit
against the panel
5. Repeat on the other side
6. Tighten equally on both sides
2.5 Wiring the Unit
Tool: insulated screwdriver Ø2.5 mm (0.1 in.), tightening torque: 0.8 Nm (7 lb-in) max.
Wires: 0.2…2.5 mm² (AWG 25 …14)
Accessories: 7-terminal cable connector, protective gloves, carpet if the floor is wet
WARNING
THE UNIT IS NOT PROTECTED
Use external fuses for Busbar phase: L1, Generator phase: L1, Battery positive: BAT(+).
Install the fuses as nearly as possible the unit, in a place easily accessible to the user. Fuse rating: 6A.
The disconnection device must NOT be fitted in a flexible cord.
Failure to follow this instruction may damage the unit

A60 X2 9 0020 B EN user manual technical documentation www.cretechnology.com
7
LOWER CONNECTOR: digital inputs and outputs, unit power supply
To check the connection, press the Lamp test button. (The led SYNCH OUT is not tested.)
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
The unit must only be installed and serviced by qualified electrical personnel
Apply appropriate personal protective equipment (PPE) and follow safe electrical
work practices
Turn off power before installing or removing fuses, and before installing the unit
Use a properly rated voltage sensing device to confirm the power is off
Do not use renewable link fuses in fused switch
Failure to follow this instruction will result in death or serious injury
l
l
!

A60 X2 9 0020 B EN user manual technical documentation www.cretechnology.com
8
UPPER CONNECTOR: phase L1 and neutral on both sides of the breaker
1. Make sure the cable connector is NOT plugged on the upper connector
2. Take on protective gloves
3. Connect the wires on the cable connector in accordance with the National Wiring Regulations
Term
Function
Technical data
Description
1
GENERATOR PHASE-L1
Generator phase input,
0-300VAC
Connect the generator phase there. The generator
phase voltage upper and lower limits are
programmable
2
unused
3
GENERATOR NEUTRAL
Input, 0-300VAC
Neutral terminal of the generator phase
4
unused
5
BUSBAR NEUTRAL
Input, 0-300VAC
Neutral terminal of the busbar phase
6
unused
7
BUSBAR PHASE-L1
Busbar phase input,
0-300VAC
Connect the busbar phase there. The busbar voltage
upper and lower limits are programmable
4. Plug the cable connector onto the upper connector
5. Lock the rear door.
DANGER
EXPOSED TERMINALS
Do not touch or use non-insulated tools near terminals L1 and N. These terminals are
unprotected and will expose the user to dangerous voltages
Failure to follow this instruction will result in death, serious injury or equipment
damage
l
l
!

A60 X2 9 0020 B EN user manual technical documentation www.cretechnology.com
9
3HUMAN-MACHINE INTERFACE
The information is displayed as follows:
3.1 LED display
The Synchronoscope shows the instantaneous phase difference between the generator voltage and the
busbar voltage.
When both networks are synched, the uppermost led at 12:00, marked 0º, is ON
When the generator frequency is higher than the busbar frequency, the synchroscope turns clockwise
When the generator frequency is lower than the busbar frequency, the synchroscope turns counter-
clockwise.
The Status shows the current status of the busbar and generator voltages and the synchronization checking
status.
The SYNCH OUT illuminates when the SYNCH CHECK relay output is ON.
SCR 2.0 indicates the nature of the displayed value by lighting one unit led in three (VAC, Hz or degree).
LED
Colour
Description
Synchroscope
Red or
amber
When both busbar and generator voltages are in range, the synchroscope illuminates.
Only one of the leds turns on at a time. The led indicates the phase difference between
the generator phase and the busbar phase.
Right-hand side illuminated: the generator phase is leading (in advance) the busbar
Left-hand side illuminated: the generator phase is lagging
Light cycling clockwise: generator frequency > busbar frequency
Light cycling counter-clockwise: generator frequency < busbar frequency
BUS status
Amber
ON when the busbar voltage is in range
GEN status
Amber
OFF if the generator voltage is out of range
Blinks if the generator voltage is in range, but SCR2.0 is waiting for a checking request
Steadily ON if the synchronization coupling is enabled
Output state
Amber
ON when the SYNCH CHECK relay is energized.
The synchronization checking can be initiated or terminated:
locally by pressing the SYNCH button
remotely via the SYNCHRONIZATION (CHECK) ENABLE input signal
The led SYNCH OUT is not energized by the Lamp test
Unit
Red
SCR2.0 selects VAC, Hz or Deg. depending on the position in the MENU

A60 X2 9 0020 B EN user manual technical documentation www.cretechnology.com
10
3.2 Digital display
The unit has a three-digit seven-segment display. It shows on request:
Readings (symbol, then value) in a sequence
Programmable parameters (number, then value) in a sequence
Scan the various readings using the MENU button. The sequence is:
U1: busbar phase-to-neutral voltage
U2 : generator phase-to-neutral voltage
dU: voltage difference between busbar and generator phases
F1: busbar frequency
F2: generator frequency
dF: frequency difference between busbar and generator
deg: phase difference between busbar and generator phases (degrees)
Hold down the button to display the value.

A60 X2 9 0020 B EN user manual technical documentation www.cretechnology.com
11
4PROGRAMMING
WARNING
RISK OF UNINTENDED EQUIPMENT OPERATION
Set the parameters to values that do not endanger your setup. We strongly recommend to
keep the parameter #9 to 1
Failure to follow this instruction can damage equipment
The program is used mainly to specify operational limits. To enter the program, press the MENU button for 5
seconds.
During programming, the unit still monitors and shows the statuses. Thus, the parameters can be modified
anytime, even while the generator is running.
When the MENU button is pressed, the display shows the parameter number, when it is released the display
shows the program parameter value. The first program number is “000”.
Press the MENU button to switch to next parameter. After the last parameter, the display cycles to the start.
Press the /keys to increase/decrease the value. Hold them down to increase/decrease the value by
steps of 10 units.
The program display goes off automatically after 20 seconds if no button or key is pressed.
#
Definition
Unit
Typical
Status or description
0
Busbar Voltage Low Limit
V
100
Under this limit, the busbar voltage is invalid (out of range)
1
Busbar Voltage High Limit
V
500
Over this limit, the busbar voltage is invalid (out of range)
2
Gen. Voltage Low Limit
V
180
Under this limit, the generator voltage is invalid (out of range)
Under this limit, the SYNCH CHECK relay cannot remain energized
3
Gen. Voltage High Limit
V
270
Over this limit, the generator voltage is invalid (out of range)
Over this limit, the SYNCH CHECK relay cannot remain energized
4
Frequency difference
Hz
1.0
If the frequency difference between the busbar and the generator
is above this limit, the synchronization is denied
5
Voltage difference
V
10
If the difference between the busbar and the generator voltages is
above this limit, the synchronization is denied
6
Phase difference
deg
5
If the phase difference between the busbar and the generator
voltages is above this limit, the synchronization is denied
7
Hysteresis Voltage
V
8
To prevent faulty decisions, you can set a hysteresis to the busbar
and generator voltage limits. Recommended value: 8 V.
For example, if the busbar voltage decreases, it goes out of range at
P_000, whereas it returns in range at P_000 + P_007.
8
Synchronization checking
delay
sec
3
Timer launched after the generator voltage is in range (set by
parameters P_002 and P_003) and the synchronization checking is
enabled. Refer to OTHER FEATURES.
9
Synchronization checking
after coupling
-
1
0: the SYNCH CHECK relay remains energized
1: the unit continues to check the synchronization

A60 X2 9 0020 B EN user manual technical documentation www.cretechnology.com
12
5OPERATION
CAUTION
RISK OF ERRONEOUS MEASUREMENTS
Ground the engine body
Failure to follow this instruction result in incorrect measurements
5.1 Power-up
The unit is designed for continuous operation powered by the generator battery voltage (12/24VDC). It shuts
offits displays after 1 mn if there is no voltage at the AC inputs and if no button is pressed.
It starts to monitor when a voltage is applied to either generator voltage input or busbar voltage input, or any
front panel button is pressed.
The synchroscope illuminates if both generator and busbar phase voltages are in range. Otherwise it turns off
to prevent the display of worthless information.
5.2 Status information
Refer to HUMAN-MACHINE INTERFACE.
5.3 Synchronization checking
The synchronization checking is ordered
either locally by pressing the SYNCH button
or remotely via the input signal SYNCHRONIZATION (CHECK) ENABLE
Then, the unit is allowed to close the relay output if the networks are synched.
Otherwise it does not close the relay even if the networks are synched.
For a quick checking after the generator start, connect the SYNCHRONIZATİON (CHECK) ENABLE input signal
to the battery negative. To let the generator stabilize (or even heat up if needed), program a pre-
synchronization delay (P_08). Refer to Synchronization checking delay.
The synchronization checking is not timed. The unit continues checking the synchronization until the
conditions are met or the process terminated with the SYNCH button or the SYNCHRONIZATION (CHECK)
ENABLE signal.
A closed to open transition on the SYNCHRONIZATION CHECK ENABLE input causes the SYNCH RELAY to de-
energize and the synchronization checking to terminate.
Positions:
Sync En. Contactor
SYN. EN.
closed
activated
open
de-activated
Once the SYNCH CHECK relay is energized, the synchronization checking goes on depending on the parameter
P_09. Set it to 1. It is of the responsibility of the panel builder to use a quickly closing circuit breaker.
On 0, the synchronization checking is disabled after closing the SYNCH CHECK relay, the relay output remains
energized even though the circuit breaker fails to close.

A60 X2 9 0020 B EN user manual technical documentation www.cretechnology.com
13
Term
mm
Function
Data
Description
8
BATTERY POSITIVE
+12 or 24VDC
(9.0 … 33.0 V)
Positive terminal of the DC supply. The unit operates
on both 12V and 24V battery systems.
9
BATTERY NEGATIVE
0VDC
Power supply negative connection.
10
DEAD BUS ENABLE
Input
If the signal is active, the unit is allowed to energize
the relay output even though the voltage level at the
busbar input is below the set limit. Refer to OTHER
FEATURES. To set the limit, refer to PROGRAMMING.
Programming.
11
SYNCHRON. (CHECK) ENABLE
Input
If the signal is active, the unit is allowed to close the
relay output when the conditions are met. Otherwise
it does not energize the relay.
12
unused
13
SYNCH CHECK RELAY normally
closed
Breaking
capacity: 16A/
250VAC
These outputs energize the circuit breaker. If the
generator voltage is out of range, or if the voltage,
frequency or phase differences between generator
and busbar are not in range, it is not energized.
If the busbar is not powered up, use the DEAD BUS
ENABLE input signal. Refer to OTHER FEATURES.
14
SYNCH CHECK RELAY common
15
SYNCH CHECK RELAY normally
open
The unit checks the synchronization only when both generator and busbar phase voltages are in range and
the synchronization is enabled either with the SYNCH (CHECK) ENABLE signal or the SYNCH button.
If both busbar and generator phase voltages are in range, the synchroscope illuminates. The synchroscope
shows the phase difference between busbar and generator.
The synchronization checking is the verification of the following conditions:
the busbar phase voltage lies between limits set by P_00 and P_01
the generator phase voltage lies between limits set by P_02 and P_03
the frequency difference between the busbar and generator does not exceed the limit set by P_04
the voltage difference between the busbar and generator does not exceed the limit set by P_05
the phase difference between the busbar and generator does not exceed the limit set by P_06
If they are met for 4 consecutive busbar cycles, the SYNCH CHECK relay is immediately energized.

A60 X2 9 0020 B EN user manual technical documentation www.cretechnology.com
14
6OTHER FEATURES
6.1 Dead Bus Enable
It may be required to couple a generator to an unpowered bus (dead bus). This is especially the case for
multi-generator synchronization systems, where one of the generators must feed the busbar to serve other
generators as a reference for synchronization.
When active, the DEAD BUS ENABLE input signal causes SCR2.0 to energize the SYNCH CHECK relay when all
the following conditions are met:
synchronization checking requested (either via input or button)
the generator phase voltage is within limits set by P_02 and P_03
the busbar voltage is below the limit set by P_00.
If the busbar voltage is above this limit, the SYNCH CHECK relay output is not energized even if the DEAD BUS
ENABLE signal is active.
Positions:
Dead bus Contactor
DEAD BUS
closed
activated
open
de-activated
6.2 Synchronization checking delay
To let the generator stabilize (or even heat up if needed), program a pre-synchronization delay (P_08).
When the generator voltage is in range, the unit is allowed to run this delay; at expiry, the synchronization
checking can be accepted.
Default factory setting: 3 seconds. If no delay is requested, set the parameter to 0.
Example of remote/local request of synchronization checking:

A60 X2 9 0020 B EN user manual technical documentation www.cretechnology.com
15
7MISCELLANEOUS
7.1 Troubleshooting
AC voltages or frequency displayed on the unit are not correct (voltage accuracy: ± 3 V):
Check the proper engine body grounding
If there are faulty measurements only when the engine is running, there may be a faulty charging
alternator or voltage regulator on the engine. Disconnect the charging alternator connection of the engine
and check if the error persists
If there are faulty measurements only when mains are present, the battery charger may be failed. Turn off
the battery charger fuse and check.
The unit is inoperative:
The unit may be in sleep mode. Press any button to wake it up
Measure the DC supply voltage between terminals 8 and 9 at the rear of the unit. If they are in range, turn
all the fuses off, then turn all the fuses on, starting from the DC supply fuse. Finally test the unit again.
Lock the rear door.
The digital display test shows only 1: check the power supply.
If you return the unit, attach an RMA (available on the website).
7.2 Declaration of conformity
The unit conforms to the following EEC directives
73/23/EEC and 93/68/EEC (low voltage)
89/336/EEC, 92/31/EEC and 93/68/EEC (electro-magnetic compatibility)
Standards:
EN 61010 (safety requirements)
EN 50081-2 (EMC requirements)
EN 50082-2 (EMC requirements)
The CE mark indicates that this product complies with the European requirements for safety, health, and
environ- mental and user protection.
7.3 Technical specifications
Features:
24-led circular synchroscope
Programmable ΔV, Δf, Δθ and parameters
Front panel programming
DANGER
EXPOSED TERMINALS
Do not touch or use non-insulated tools near terminals L1 and N. These terminals are
unprotected and will expose the user to dangerous voltages
Failure to follow this instruction will result in death, serious injury or equipment
damage
l
l
!

A60 X2 9 0020 B EN user manual technical documentation www.cretechnology.com
16
Voltage inputs: 1 phase of generator and 1 phase of busbar
Synch check & dead bus enable input
Auto power off
Plug-in connection system for easy replacement
Measurements:
Busbar voltage: 300 VAC max. (Ph-N)
Busbar frequency: 50/60 Hz
Generator voltage: 300 VAC max. (Ph-N)
Generator frequency: 0-100 Hz
Other electrical data:
Digital inputs: 0V (active inputs), withstand 30VDC
DC Supply Range: 9.0 to 33.0 VDC
Current Consumption: 100 mA (standby), 150 mA (all LEDs lit, Synch Check relay de-energized)
Synch Check relay breaking capacity: 16 A / 250VAC
Casing:
Dimensions: 102x102x57 mm (4 in. x 4 in. x 2.3 in.) (width x height x in-panel depth)
Mounting: Front panel
Weight: 170 g (approx.)
Material: High temperature ABS (UL94-V0, 100°C)
Protection: IP65 from front panel, IP30 from the rear

A60 X2 9 0020 B EN user manual technical documentation www.cretechnology.com
17
CRE TECHNOLOGY
130 allée Charles-Victor Naudin
Zone des Templiers
Sophia-Antipolis
06410 BIOT
FRANCE
Phone: +33 (0)4 92 38 86 82
Fax: +33 (0)4 92 38 86 83
Website: www.cretechnology.com
Email: info@cretechnology.com
Technical support: +33 (0)4 92 38 86 86 (office hours: 8.30AM - 12AM / 2PM - 6PM GMT +1) Email:
support@cretechnology.com
SKYPE: support-cretechnology.com (voice only)
A worldwide coverage:
Check our entire distributors list around the world on www.cretechnology.com, button «DISTRIBUTORS».
Head Office: FRANCE
Official Distributors
Agents

A60 X2 9 0020 B EN user manual technical documentation
18
www.cretechnology.com
CRE TECHNOLOGY has provided the engine
and generator industry for over 25 years with
standard products and dedicated solutions for
engine control, generator protection and
paralleling.
All application fields where power is the core
resource of performance are covered by CRE
TECHNOLOGY. The company is a reference in
the industrial, marine and defense
businesses.
Our very strong situation allows us to invest,
feeding our ambition to be always more
advanced, always closer to you. The coming
years will see the broadening of our
distribution network and of our innovative
products portfolio.
BECOME A CRE TECHNOLOGY DISTRIBUTOR
YOUR ACCOUNT & YOUR PRICES
By creating your account, you’ll have access
to all your personal data. All the prices of the
new CRE TECHNOLOGY website correspond to
your business rates.
GET INFORMATION THE WAY YOU WANT IT
Fill your cart by choosing the products you
want and get all the information you need.
EVERYWHERE WITH YOU
The new CRE TECHNOLOGY website is
designed to be responsive to smartphones
and touch tablets.
It allows you to consult the documents
related to the CRE TECHNOLOGY’s ranges of
products.
Table of contents