CSI LV-019 User manual

Signature 2 Series
pg. 2
:
Main Menu
1. To enter Main Menu, press the Menu/Enter button.
(Time of Day will flash)
2. To set the Time of Day, press the Set/Change button.
(First digit will flash) Example [12:00]
- To change digit value, press the Set/Change button.
- To accept the digit value, press the Menu/Enter button.
- Next digit will flash to begin setting.
- Once the last digit display is accepted, all digits will flash.
3. To set A.M. or P.M., press the Menu/Enter button.
- To change digit value, press the Set/Change button. Example [ A ]
- To accept the digit value, press the Menu/Enter button.
- Once A.M. or P.M. is accepted, the next menu item will flash.
4. To set the Number of Days between Regeneration or Backwash Cycles (A), press the
Set/Change button.
- Repeat instructions from step (2). Example [ A - 07 ]
Notes: 1) Maximum value is 29.
2) If value set to 0, Automatic Regeneration will never occur.
3) Default setting is 4 days for softeners and 6 days for filters.
4) On metered models, an “H” will appear to enter Compensated
Hardness in grains per gallon (gpg). Example [ H – 20]
5) Default setting is 25 gpg.
5. To set the Number of Days between Air Draw Cycles (d), press the Set/Change Button
- Repeat instructions from step (2) “Used on Nitro & Nitro Pro Filters Only” Example [ d – 01 ]
Notes: 1) Maximum value is 29.
2) If value set to 0, air draw is turned off, but an air cycle will still be completed when
backwash cycle occurs. If the Number of Days between Air Draw Cycles is set to
a higher number of days than the Number of Days between Backwash Cycles, it
will have no effect. In order to turn off all cycles, both the Days between Backwash
and Days between Air Draw Cycles must be set to 0.
3) Default setting is 1 day.
6. To Exit Main Menu, press the Menu/Enter button.
Note: If no buttons are pressed for 60 seconds, the Main Menu will be exited automatically.
SET
CHANGE
MENU
ENTER
Menu/Enter
Button
Set/Change
Button

Signature 2 Series
pg. 3
Normal Operation
1. Home Display
- Alternates between the display of Time of Day and Number of Days until the Next Regeneration.
- Days Remaining until the Next Regeneration will count down from the entered Regeneration Day
Override Value until it reaches 1 day remaining.
- A Regeneration Cycle will then be initiated at the next designated regeneration time.
- Metered models alternate the Time of Day and Gallons left until the next Regeneration. The meter
will count down to zero (0000) and then regenerate at the scheduled time set.
2. Battery Back-Up (Uses a standard 9-volt alkaline battery.)
- Installing the battery
- Features of Battery Back-Up
Maintains the Time of Day during power failures.
Notes: 1) During power failures, the display is turned off to conserve battery power. However, to confirm that
the battery is working, press either button and the display will turn on for five (5) seconds.
2) If power failure occurs while system is regenerating, the Signature Series II will motor to a shut off
position to prevent constant flow to drain. Note: Depending upon system pressure and other
factors, it is possible to observe a reduced flow to drain during this step. After power is restored,
the Signature Series II will return and finish the cycle where it left off prior to the power interruption.
3) When used without battery back-up, the unit acts like a standard valve. When a power failure
occurs, the unit stops at its current point in the regeneration position and then restarts at that point
when the power is restored. However, the time will be offset by the increment of time the unit was
without power.
Electronic Connections
P = Power Supply
B = Powered in Backwash Cycle Only
S = Powered in Entire Regeneration
Cycle
P B S

Signature 2 Series
pg. 4
Starting Extra Regeneration Cycle
1. To Start Delayed Extra Cycle Example [ 1 ]
- If Days Remaining Until Next Regeneration does not read ‘1’, press and hold the
Set/Change button for 3 seconds until the display reads ‘1’, or ‘0000’ on metered models.
- Regeneration cycle will initiate at the next designated regeneration time.
2. To start Immediate Extra Cycle First complete above step.
- With Days Remaining Until Next Regeneration at ‘1’ or ‘0000’,
- Press and hold the Set/Change button.
- After 3 seconds, the regeneration cycle will begin.
3. To Fast Cycle thru regeneration First complete above 2 steps.
Note: Fast Cycle is not necessary unless desired to manually step through each cycle step.
- Press and hold the Set/Change button for 3 seconds to advance to the next cycle step.
Softeners
Default (min.)
Filters
Default
(min.)
Step 1 : Backwash
10
Step 1 : Backwash
10
Step 2 : Brine & Rinse
60
Step 2 : Rest
5
Step 3 : Rapid Rinse
10
Step 3 : Rapid Rinse
10
Step 4 : Brine Refill
Set for full sal
ting
Step 4 : Not Used
0
Nitro
Default (min.)
Nitro Pro
Default
(min.)
Step 1 : Air Release
6
Step 1 : Air Release
6
Step 2 : Backwash
10
*
Step 2 : Oxyclean NP Injection
15 sec.
Step 3 : Rest
5
Step 3 : Short Rinse
1
Step 4 :
Air Replenish
1
2
Step 4 : Rest
20
Step 5 :
Rapid Rinse
1
0
Step 5 : Backwash
10
Step 6 : Rest
5
Warning:
On
NITRO PRO
System, if “J”
Program is used, the Oxyclean NP must be
used to avoid any warranty issues.
Step 7 :
Air Replenish
1
2
Step 8 :
Rapid Rinse
1
0
Note:
Depending upon system pressure
and other factors, it is possible to observe
flow to drain in the rest cycles.
*Only if “J” program (Oxyclean NP Option) is
activated.

Signature 2 Series
pg. 5
Nitro Only Backwash Cycle Step Explanation
Step 1: Air Release Step
For approximately 6 minutes
- Not programmable
Step 2: Backwash Step
- Default of 10 minutes
Step 3: Rest Step
- Default of 5 minutes
Step 4: Air Replenish Step
- Default of 12 minutes
Example:
Step 5: Rapid Rinse Step
- Default of 10 minutes
Notes:
- When the valve is between positions, the display will flash the number of the step it is moving towards.
- The default time at which regeneration will occur is 2:00 a.m. for softeners and 12:00 a.m. for filters.
New feature: The motor’s run direction during a particular regeneration cycle step is indicated by
the rotation direction of the last 2 digit displays.
5-

Signature 2 Series
pg. 6
Nitro Pro Only Backwash Cycle Step Explanations
(With “J” Program Activated – Oxyclean NP Option)
Step 1: Air Release Step
For approximately 6 minutes
- Not programmable
Step 2: Oxyclean NP Injection
For 15 seconds
- Not programmable
Step 3: Short Rinse Step
For 1 minute
- Not programmable
Step 4: Rest Step
For 20 minutes
- Not programmable
Step 5: Backwash Step
- Default of 10 minutes
Step 6: Rest Step
- Default of 5 minutes
Example:
Step 7: Air Replenish Step
- Default of 12 minutes
Step 8: Rapid Rinse Step
- Default of 10 minutes
Note: Depending upon system pressure and other factors, it is possible to observe flow to drain in the rest
cycles.
Notes:
- When the valve is between positions, the display will flash the number of the step it is moving towards.
- The default time at which regeneration will occur is 2:00 a.m. for softeners and 12:00 a.m. for filters.
New feature: The motor’s run direction during a particular regeneration cycle step is indicated by
the rotation direction of the last 2 digit displays.
5-

Signature 2 Series
pg. 7
Final Set-Up
With proper valve operation verified (Softeners only):
1. Add water to the top of the air check. Manually step the valve to the Brine Cycle (position 2) and
allow the valve to draw water from the brine tank until it stops. Note: The air check will check at
approximately the midpoint of the screened intake area.
2. Next, manually step the valve to the Brine Refill position and allow the valve to return to Service
automatically.
3. With the valve in Service, check that there is about 3 to 5 inches of water level above the grid in the
brine tank, if used.
4. Fill the brine tank with salt to complete set-up. The control will run automatically.
Error Codes
There are four (4) error codes which could indicate a possible problem with the control valve:
Error 2 - Homing slot expected. Valve will begin searching for home.
(Normal operation continues.)
Error 3 - Encoder is not sending a signal.
(Valve requires service to continue.)
Error 4 - Unable to find homing slot.
(Valve requires service to continue.)
Error 5 - Motor overload (stalled position or shorted motor).
(Valve requires service to continue.)
Error 5 Explanation: The unit thinks the motor is locked. This can only happen when the valve is running
the motor, it is not seeing any encoder slots, and the motor is overloaded. This usually alerts the
presence of foreign debris inside the valve clogging the system.

Signature 2 Series
pg. 8
Master Programming Mode
To enter Master Programming Mode, press and hold both buttons for 5 seconds.
Note: All Master Programming functions have been preset at the factory. Unless a change is desired, it is
NOT necessary to enter Master Programming Mode.
1. Regeneration Type (t) N/A for Nitro / Nitro Pro
- This display is used to set the Regeneration Type. This option setting is identified by the letter “t” in the
left digit. There are two possible settings:
- Timeclock / Filter Delayed – The control will determine that regeneration is required when the set
regeneration time has been reached. The regeneration frequency setting will determine which days a
regeneration cycle will be initiated. Example ( t - - c ).
- Meter Delayed (Demand) – The control will determine that regeneration is required when the available
volume of softened water drops to or below zero. Regeneration is to begin at the scheduled time set.
Example ( t - - d ).
● The Set/Change button will adjust this value. To accept the digit value, press the Menu/Enter
button.
2. Regeneration Day Override (A) – Meter (Demand) Mode Only – Softeners Only
- Press Menu/Enter button. This display is used to set the maximum amount of time (in days) the unit
can be in service without regeneration. This option setting is identified by the letter “A” in the left digit.
Regeneration will begin at the scheduled time. A setting of zero will cancel this feature.
- Example: Override every 7 days (A-07), default setting, or cancel setting (A-00). Maximum is 29.
3. To Set Regeneration Time ( r ) Example [ r 12A ]
- The time of day at which regeneration may take place is designated by the letter “r”.
- The first display digit indicates A.M. or P.M. To change the value, press the Set/Change button.
- Press Menu/Enter button to accept the value and move to the next digit.
- The second and third display digits indicate the hour at which the regeneration will occur.
- Change the digits with the Set/Change button and accept with the Menu/Enter button.
- After the entire display flashes, press the Menu/Enter button to move to the next menu item.
4. To Activate Oxyclean NP Program (Nitro Pro Only)
- “J” program is selectable either off – 0 (default setting) or on – 1.
- To activate the non-adjustable cycles for the Oxyclean NP, select J-1 with the Set/Change button and
enter with the Menu/Enter button.

Signature 2 Series
pg. 9
5. To Set Regeneration Cycle Step Times Softeners/Filters Only (1) (2) (3) (4) Example [ 3 – 20 ]
- The next 4 displays set the duration of time in minutes for each backwash cycle step.
- The step number which is currently modifiable is indicated on the far left of the display screen.
- The number of minutes allotted for the selected backwash step is displayed on the far right.
- Change the digit values using the Set/Change and Menu/Enter buttons as described above.
5. To Set Backwash Cycle Step Times Nitro (2) (3) (4) (5) / Nitro Pro (5) (6) (7) (8) Example [ 3 – 20 ]
- The next 4 displays set the duration of time in minutes for each backwash cycle step.
- The step number which is currently modifiable is indicated on the far left of the display screen.
- The number of minutes allotted for the selected backwash step is displayed on the far right.
- Change the digit values using the Set/Change and Menu/Enter buttons as described above.
Note on Air Draw Cycle (4): Nitro Filter Only (7) Nitro Pro Only
The longer the unit is set to remain in the Air Draw cycle (4), the more air is drawn into the system. A
default setting of 12 minutes draws air down to the level of a normal media bed height and then returns
the unit to the home display. If the system needs more air, increase the time setting for step (4) or
decrease the number of days between air draw cycles. There is no way to view the number of days
until the next air draw will take place.
5. System Capacity in Grains ( c ) – Meter (Demand) Only
- Press the Menu/Enter button. This display is used to set the system capacity in grains and is used in
conjunction with the hardness setting to calculate total gallons of treated water available between
regenerations. This option is identified by the letter “c” in the left digit. The maximum value for this item
is 399. Example: 32,000 grain capacity ( c 032 ).
6. To Exit the Master Programming Mode, press the Menu/Enter button until time of day returns.
Note: If no buttons are pressed for 60 seconds, the Master Programming Mode will be exited automatically.

Signature 2 Series
pg. 10
Utilizing Bluetooth Control
To take advantage of the Bluetooth interface this feature must be set up on a Bluetooth enabled device.
Note: At the time of this release Bluetooth control only works on Android devices with a compatible version
of Bluetooth.
1. Download the Legacy View app from the Google Play Store or www.ChandlerSystemsInc.com
2. Pair the smart phone or tablet to the control valve
- Open the settings menu on your smart phone or tablet and click on Bluetooth.
- Look for the softener or filter valve under the list of available Bluetooth devices.
- Select the device and pair (Default password is: 1234)
3. Once the devices are paired open the Legacy View app
- Click the Legacy View logo in the top left corner to refresh the list of connected paired control valves
and select which valve you would like to view.
This device complies with part 15 of the FCC Rules. Operation is subject to the following conditions: (1) this
device may not cause harmful interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation. Changes or modifications not expressly
approved by the party responsible for compliance could void the user’s authority to operate the equipment.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to radio or television reception,
which can be determined by turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.

Signature 2 Series
pg. 11
SET
CHANGE
MENU
ENTER
Master Programming Mode Flow Chart
- To enter Master Programming mode,
Press and hold both buttons for 5 seconds.
→
SET
CHANGE
To change value
REGEN
TYPE ↓
↓ →
MENU
ENTER To accept value
MENU
ENTER
↓ →
SET
CHANGE
To change value
DAY
OVERRIDE ↓
METER MODE ONLY
↓ → MENU
ENTER To accept value
MENU
ENTER
↓ →
SET
CHANGE To change value
UNIT
CAPACITY ↓
METER MODE ONLY
↓ → MENU
ENTER
To accept value
MENU
ENTER
↓ →
S
ET
CHANGE
To change value
REGEN
TIME ↓
↓ →
MENU
ENTER
To accept value
MENU
ENTER
↓ →
SET
CHANGE To change value
REGEN STEP
1,2,3 & 4 ↓
↓ →
MENU
ENTER
To accept value
MENU
ENTER
→
The Program Mode will be exited and
normal operation resumed.

Signature 2 Series
pg. 12
Control Valve Assembly (Nitro & Nitro Pro)

Signature 2 Series
pg. 13
NITRO & NITRO PRO BODY ASSEMBLY

Signature 2 Series
pg. 14
NITRO & NITRO PRO BODY ASSEMBLY
PART No.
DESCRIPTION
Qty.
1 20009X231 PISTON ASSEMBLY 1
2 20001X226 HEX SCREW 3
3 20001X232 SEAL & SPACER KIT 1
4 20251X100 DRAIN LINE FLOW CONTROL HOUSING 1
5 20561X225 BRINE VALVE 1
6 N/A END SPACER 1
7 20001X214 DRAIN RETAINER CLIP 1
8 20001X228 BRINE LINE FLOW CONTROL ASSY. 1
9 20251X305 BRINE LINE FERRULE 1
10 20251X304 BRINE LINE COMPRESSION NUT 1
11 20009X005 PLUG 1
12 20001X226 HEX SCREW 2
13 20009X001 INJECTOR COVER NITRO PRO 1
14 20001X224 INJECTOR SEAL 1
15 20001X219 INJECTOR ASSEMBLY WHITE (SPECIFY COLOR)
1
16 20001X222 INJECTOR SCREEN 1
17
20001X217
INJECTOR PLUG
1
18 20001X215 TANK O-RING 1
19 20561X204 DISTRIBUTOR PILOT O-RING 1
20
20251X272
DLFC 5.0 BUTTON (SPECIFY SIZE)
1
21 20561X216 ADAPTER O-RING 4
22 20561X201 CLIP 2
23
20561X217
HEX SCREW
2
24 20561X215 ADAPTER COUPLING 1
25 20111X011 ADAPTER COUPLING CHECKVALVE 1
26 N/A VALVE BODY 1
27 20009X010 INJECTOR CAP PLUG 1
28 GA-T0620666B 3/8" 90 ELBOW 3
29 57005X001 3/8" BLACK TUBING / FT. 0.2
30
GA
-
S0660416B
STEM ADAPTER
1
31 20009X007 INJECTION ASSEMBLY 1

Signature 2 Series
pg. 15
Control Valve Drive Assembly (Filter Version)

Signature 2 Series
pg. 16
Control Valve Drive Assy. (Filter Version)
Ref
# Description Part # Qty.
Ref
# Description Part # Qty.
0 Valve Body Complete 20001X200
1
15 O Ring 20561X204
1
1 Valve Body Only 20001X201
1
16 O Ring 2000X215
1
2 End Spacer N/S 1
17 O Ring N/S 1
3 Seal N/S 5
18 Injector N/S 1
4 Spacer N/S 4
19 O Ring N/S 2
4A
Seal & Spacer Kit
Incl. (1) #2, (5) #3, & (4) #4 20001X232
1
19A
Injector Plug & O Ring Assembly
Incl. (1) each #17 thru #19 20001X217
1
5 Down Flow Piston N/S 1
20 Injector Seal 20001X224
1
6 Piston End Rod Retainer N/S 1
21 Injector Cap 20001X223
1
7 End Plug Assembly N/S 1
22 10-24 X 1 Hex Washer HD Screw 20001X226
2
8 Piston Arm N/S 1
22A
Filter Conversion Kit
Incl. (1) each #19A, #24A, #26A,
#20, #21 & (2) #22
20001X221
1
8A
Piston Assembly
Incl. (1) each #5 thru #8 20001X231
1
9 Hex Washer HD 10-24 X 13/16” Screw
N/S 3
23 O Ring N/S 1
10 Drain Retainer 20001X214
1
24 Filter Plug N/S 1
11 O Ring 20251X254
1
24A
O Ring & Filter Plug Assembly
Incl. (1) each #23 thru #24 20001X229
1
12 Flow Control Button 1.5 GPM 20251X266
1
Flow Control Button 2.0 GPM 20251X267
1
25 O Ring N/S 1
Flow Control Button 2.4 GPM 20251X268
1
26 Brine Valve Cap N/S 1
Flow Control Button 3.0 GPM 20251X269
1
26A
O Ring & Brine Valve Cap Assembly
20001X230
1
Flow Control Button 3.5 GPM 20251X270
1
Flow Control Button 4.0 GPM 20251X271
1
Items #27 thru #30 used only with clock regeneration
Flow Control Button 5.0 GPM 20251X272
1
27 Adapter Coupling N/S 2
Flow Control Button 7.0 GPM 20251X274
1
28 O Ring 20561X216
4
13 Plastic Flow Control Housing N/S 1
28A
Adapter Coupling & O Ring
Assembly
Incl. (1) # 27 & (2) #28
20561X215
1
14 Drain Line Fitting 90º Elbow
1/2” NPT x 1/2” Tubing 20251X255
1
29 Mounting Clip 20561X201
2
14A
Flow Control Assembly-Specify GPM
Incl. (1) each #11 thru #14
30 8-18 X 5/8” Hex Washer HD Screw 20561X217
2
Flow Control Assy. 1.5 GPM-PVC 20251X256
1
Flow Control Assy. 2.0 GPM-PVC 20251X257
1
N/S indicates non-stocked item
Shaded Ref # indicates assembly or kit
Flow Control Assy. 2.4 GPM-PVC 20251X258
1
Flow Control Assy. 3.0 GPM-PVC 20251X259
1
Flow Control Assy. 3.5 GPM-PVC 20251X260
1
Flow Control Assy. 4.0 GPM-PVC 20251X261
1
Flow Control Assy. 5.0 GPM-PVC 20251X262
1
Flow Control Assy. 7.0 GPM-PVC 20251X264
1

Signature 2 Series
pg. 17
Control Valve Assembly (Softener Version)

Signature 2 Series
pg. 18
Control Valve Drive Assembly Parts List (Softener Version)
Ref
# Description Part # Qty.
Ref
# Description Part # Qty.
0
Valve Body Complete
20001X200
1
24
O Ring
20561X204
1
1
Valve Body Only
20001X201
1
25
O Ring
20001X215
1
2
End Spacer
N/S
1
26
O Ring
N/S
2
3
Seal
N/S
5
27
Injector Plug
N/S
1
4
Spacer
N/S
4
28
O Ring
N/S
1
4A
Seal & Spacer Kit
Incl. (1) #2, (5) #3 & (4) #4 20001X232
1
28A
Injector Plug & O Ring Assy.
Incl. (1) each #26 thru # 28 20001X217
1
5
Down Flow Piston
N/S
1
29
Injector Throat
N/S
1
6
Piston End Rod Retainer
N/S
1
30
Injec
tor Nozzle
N/S
1
7
End Plug Assembly
N/S
1
31
Vortex Generator
N/S
1
8
Piston Arm
N/S
1
31A
Injector Assy. Specify Size
Incl. (1) each #2 & #28 thru #31 20001X219
1
8A
Piston Assembly
Incl. (1) each #5, #6, #7 & #8 20001X231
1
32
Injector S
creen
20001X222
1
9
Hex Washer HD 10
-
24 X 13/16” Screw
N/S
3
33
Injector Seal
20001X224
1
10
Brine Valve Set
N/S
1
34
Injector Cap
20001X223
1
11
Brine Valve Stem
N/S
1
35
10
-
24 1 Hex Washer HD Screw
20001X226
2
12
Brine Valve Spacer
N/S
1
35A
Inje
ctor Kit
–
Specify Size
–
Incl. (1) ea #31A, #32, #33, #34 & (2) #35
20001X220
1
13
O Ring
N/S
1
14
Quad Ring
N/S
1
36
BLFC Button Retainer
20561X240
1
15
Brine Valve Cap
N/S
1
37
5 GPM BLFC Button
20251X318
1
16
Brine Valve Spring
N/S
1
38
O R
ing
20561X239
1
17
Plain Nylon Washer
N/S
1
39
BLFC Adapter
20561X241
1
18
Retaining Ring
N/S
1
39A
BLFC Assembly .5 GPM
-
Inc. (1) each #36 thru #39 20001X228
1
18A
Brine Assembly
Incl. (1) each #10 thru #18 20001X210
1
19
Drain Retai
ner
20001X214
1
20
O Ring
20251X254
21
Flow Control Button 1.5 GPM 20251X266
1
Items #40 thru #43 used ONLY with clock regeneration
Flow Control Button 2.0 GPM
20251X267
1
40
Adapter Coupling
N/S
2
Flow Control Button 2.4 GPM
20251X268
1
41
O Ring
20561X216
4
Flow Control Button 3.0 GPM
20251X269
1
41A
Adapter Coupling & O Ring Assy.
Incl. (1) #40 & (2) # 41 20561X215
1
Flow Control Button 3.5 GPM
20251X270
1
Flow Control Button 4.0 GPM
20251X271
1
42
Mounting Clip
20561X201
2
Flow Control Button 5.0 GPM
20251X272
1
43
8
-
18 X 5/8” Hex Washer HD Screw
20561X217
2
Flow Control Button 7.0 GPM
20251X274
1
22
Plastic Flow Control Housing
N/S
1
23 Drain Line Fitting 90º Elbow
1/2" NPT X 1/2" Tubing 20251X255
1
N/
S indicates non
-
stocked item
shaded Ref # indicates assembly
or kit
23A
Flow Control Housing
–
Specify GPM
Incl. (1) each #20 thru #23
Flow Control Assy. 1.5 GPM
-
PVC
20251X256
1
Flow Control Assy. 2.0 GPM
-
PVC
20251X25
7
1
Flow Control Assy. 2.4 GPM
-
PVC
20251X258
1
Flow Control Assy. 3.0 GPM
-
PVC
20251X259
1
Flow Control Assy. 3.5 GPM
-
PVC
20251X260
1
Flow Control Assy. 5.0 GPM
-
PVC
20251X262
1
Flow Control Assy. 7.0 GPM
-
PVC
20251X264
1

Signature 2 Series
pg. 19
Meter Assembly
Meter Assembly Parts List
Ref #
Description
Part #
Qty.
1A
Meter Assembly, Turbine Complete
20564X200
1

Signature 2 Series
pg. 20
Bypass Assembly (Plastic)
Ref #
Description
Part #
Qty.
1
Plastic Bypass Valve Assembly
20561X292
1
Table of contents
Other CSI Control Unit manuals
Popular Control Unit manuals by other brands

Siemens
Siemens SINUMERIK 802D sl instruction manual

OMC
OMC VD10 Series Installation, operation and maintenance manual

Datex-Ohmeda
Datex-Ohmeda M-NMT Technical Reference Manual Slot

Allen-Bradley
Allen-Bradley PowerMonitor 500 user manual

Inorea
Inorea PB6014 quick start guide

Samson
Samson 42-36 E Mounting and operating instructions