To restore to the factory default settings, start with the unit in the “RUN” mode. Press and hold the
“ENTER” button. The “RUN” LED indicator will begin to blink. After about 2.5 seconds all LED
indicators will flash indicating the factory settings have been restored. Range settings are not
affected by this operation.
To complete these steps, you must have set-up privileges.
CONFIGURING EDGE SOFTWARE FOR AIRSPEED SENSOR:
1. Select the Equipment Congifuration Icon.
2. Select the room to which the equipment will be added.
3. Scroll down and select Generic Input.
4. Select the Add or Copy equipment button.
5. Give the sensor a Name and then select the Signal Type, Units, and Precision as shown below.
“Min value” and “Max value” are determined by sensor setting. 1000 FPM is recommended. Set
“Min value” to “0” and “Max value” to “1000”.
The Expansion Box, Slot, and Input are site-specific and determined by where the sensor wiring is landed.
6. Select the Home Screen Icon.
7. Scroll to the room you added the equipment to and select the generic input tile.
8. Select the sensor and check the “Show on tile”. Up to 3 inputs can be shown on a tile per room.