Curtis 700 series User manual

Read Instructions Carefully!
5mm HOUR METERS & COUNTERS
700/732 SERIES
®
CURTIS INSTRUMENTS, INC.
200 Kisco Ave.
Mount Kisco, New York 10549
914-666-2971 Tel
914-666-2188 Fax
www.curtisinstruments.com
53004 Rev. G 9/14

TABLE OF CONTENTS
1. Model Encodement 2
2. Technical Specifications
2.1 Electrical 6
2.2 Mechanical 10
2.3 Environmental 12
3. Installation 13
4. Operation 14
5. Troubleshooting 18
6. Maintenance 18
7. Warranty 19
SAFETY INSTRUCTIONS
This instrument was manufactured and tested according to the
applicable technical standards. It complies with all the safety
regulations as shipped from the factory.
Installation and startup must be performed by skilled personnel.
Failure to install and operate the unit in accordance with these
instructions may result in damage or injury.
If safe operation of the instrument can no longer be ensured,
stop and secure it against accidental operation.
If instrument failure or malfunction may cause personal injury
or material damage, use additional safety measures such as
limit switches, guards, etc.
Read the Operating Instructions carefully before startup.
Note the safety instructions marked with this
warning symbol in this manual!

2 3
Example: 7 01 G R 001 0512D0612A N
Function
Case
Style
Reset
Sequential
Code
Nominal
Voltage
1 3 5
2 4 6
Logo
Function
1 2
1. MODEL ENCODEMENT
(All models except 732)
00 2 wire Hour Meter
01 3 wire Hour Meter
03 Pulse Counter
Reset
3
RElectrical Reset
NNo Reset
Case Style
See section 2.2 for
complete specifications.
4Sequential Code
Factory specified.
Nominal Voltage
5
0512D 5 to 12VDC
1248D 12 to 48VDC
48150D 48 to 150VDC
0512D0612A 5 to 12VDC, 6 to 12VAC
1248D2060A 12 to 48VDC, 20 to 60VAC
48150D100230A 48 to 150VDC,100 to 230VAC
(See Section 2.1 for absolute voltage)
O Curtis
N None
Logo
6

4 5
Example: 732 N 2 3 001 N
Function
Case
Style
LED
Voltage
Sequential
Code
1 3 5
2 4
Logo
Function
1
2
02-wire Hour Meter, no enable; LED gnd-enabled, no reset.
12-wire Hour Meter, no enable; LED pwr-enabled, no reset.
22-wire Hour Meter, no enable; LED gnd-enabled, w/reset.
32-wire Hour Meter, no enable; LED pwr-enabled, w/reset.
43-wire Hour Meter, w/enable; LED gnd-enabled, no reset.
53-wire Hour Meter, w/enable; LED pwr-enabled, no reset.
LED Voltage (VDC)
3
0 12
1 24
2 36
3 48
Case Style
See section 2.2 for complete specifications.
5
732 Model Encodement Only
Note: 732 has a built-in LED in its face
4Sequential Code
Factory specified.
O Curtis
N None
Logo

6 7
2. TECHNICAL SPECIFICATIONS
2.1 Electrical
Operating Voltage 700 Series
The operating voltage ranges specified apply to voltages
connected between terminal 1 and terminal 2 (700,
701, 703), terminal 3 and terminal 2 (701,703 only), and
terminal 4 and terminal 2 (Reset option).
DC only models
DC/AC models
Nominal (VDC) / Absolute (VDC) : Same as above
Nominal (VDC) Absolute (VDC)
5 to 12 4.75 to 15
12 to 48 9.0 to 60
48 to 150 36 to 185
Nominal (VAC) Absolute (VAC)
6 to 12 5.0 to 15
20 to 60 15 to 75
100 to 230 75 to 270
Operating Voltage 732 Only
Voltages connected between pins 1 and 2 and
between 4 and 2 (Enable option).
732 DC only, all voltage models
LED voltages betweeen pins 3 and 2.
Frequency (AC models)
The AC operating frequency range is 48 to 440 Hz.
Maximum AC-Reset Frequency is 150 Hz.
Accuracy
Model 700, 701, 732 = ±0.1%
Model 703 = ±1 count
Nominal (VDC) Absolute (VDC)
12 to 48 9.0 to 60
732 LED Voltage Absolute (VDC)
12 9 to 15
24 18 to 30
36 27 to 45
48 36 to 60

8 9
Operating Current
(All models except 732)
The maximum operating current at terminal 1
is tabulated below for each nominal operating
voltage limit.
DC Only Model
DC/AC Model
VDC: Same as above.
Operating Voltage
(VDC) V+ to V++
Maximum Current
@ V+
Maximum Current
@ V++
5 to 12 0.5 mA 10.0 mA
12 to 48 0.8 mA 5.0 mA
48 to 150 0.8 mA 2.5 mA
Operating Voltage
(VAC) V+ to V++
Maximum Current
@ V+
Maximum Current
@ V++
6 to 12 0.7 mA 6.0 mA
20 to 60 0.5 mA 2.5 mA
100 to 230 0.9 mA 2.0 mA
Operating Current continued
(732 Model only)
Single Voltage, DC only
Operating Voltage (VDC) Maximum Current w/LED (mA)
12 15.0
24 10.0
36 7.0
48 5.0
Voltage
Encodement
Impedance (Min)
Terminal 3
Impedance (Min)
Terminal 4
0512D 10 KΩ 25 KΩ
1248D 60 KΩ 70 KΩ
48150D 480 KΩ 480 KΩ
0512D 0612A 10 KΩ 25 KΩ
1248D 2060A 70 KΩ 70 KΩ
48150D 100230A 480 KΩ 480 KΩ
732 (all voltages) –70 KΩ
Impedance
The minimum impedance at terminal 3 and at terminal 4
are tabulated below for each model.

10 11
Case Bezel Shape Terminals Max Pins Mounting Lens Matrl. Case Matrl. Bezel Material Panel Cutout (mm) Panel Cutout (in.)
F Hexagonal 1/4” Faston 4 Flange Acrylic ABS (black) ABS (black) 36.8x24.1 1.45x0.95
G Hexagonal Packard 2 Flange Acrylic ABS (black) ABS (black) 36.8x24.1 1.45x0.95
J Hexagonal Packard 4 Flange Acrylic ABS (black) ABS (black) 36.8x24.1 1.45x0.95
K Hexagonal Packard 4 Flange Acrylic ABS (black) ABS (black) 36.8x24.1 1.45x0.95
N Hexagonal 1/4” Faston 4 Flange Acrylic ABS (black) ABS (black) 36.8x24.1 1.45x0.95
D Rect. - DIN 3/16” Faston 4 U-Bracket Acrylic ABS (black) ABS (black) 45x22.2 1.77x0.87
L Rectangular Molex-mini 4 Snap-In Plycarb. Polycarb. Polycarb. 36.8x24.1 1.45x0.95
H Rectangular Packard 2 Bracket (plast.) Acrylic ABS (black) Acrylic (clear) 36.8x24.1 1.45x0.95
Y Rectangular Packard 4 Bracket (plast.) Acrylic ABS (black) ABS (black) 36.8x24.1 1.45x0.95
Z Rectangular 1/4” Faston 4 Bracket (plast.) Acrylic ABS (black) ABS (black) 36.8x24.1 1.45x0.95
Q Round 1/4” Faston 4 U-bracket Glass Polycarb. Alum. Anodzd. (blk) Ø 52 Ø 2 1/16”
R (5mm) Round 3/16” Faston 4 U-bracket Glass Polycarb. Alum. Anodzd. (blk) Ø 52 Ø 2 1/16”
NOTE:
K & N – LED indicator molded in bezel face (available as 732 models only);
G & H – Require 2-pin Delphi- Packard mating connector P/N 12162000;
J, K & Y – Require 4-pin Delphi- Packard mating connector P/N 12162035;
L - Snap tabs built in(no mounting hardware required); case and bezel 1-piece clear
Hexagonal - Screw mount through flange (optionally mounted with plastic bracket,
available separately)
2.2 Mechanical
Display
6-digit LCD, 5 mm high
Range & Resolution
700, 701, 732 Hour Meters: 99,999.9 Hours
703 Counter: 999,999 Counts.
Case & Connector Specifications

12 13
3. INSTALLATION
V+: Operating voltage;
V–: Common (ground);
I: Enable (optional, use operating voltage to power this pin
to record elapsed time [701] or increment count [703]);
R: Reset (optional, supply with operating voltage when
unit is to be reset to 0);
LED: Externally driven by active high or low – factory
configured;
NC: No connection;
2.3 Environmental
Temperature
Operating: –40°C to +85°C
Storage: –50°C to +90°C
Humidity
95% RH (Non Condensing) at 38°C
Shock & Vibration
Meets SAE J 1378
Case - IP Ratings
Case Style D, Q, R F, Z, N G, J, Y, H, K L
Front 65 65 65 65
Rear 50 65 *65 40
* Rated with mating connector installed
Case Style Pin 1 Pin 2 Pin 3 Pin 4
D, F, Q, R, J, Y, Z V+ V– I R
G, H V+ V– NC NC
L V+ V– I NC
K, N V+ V– LED I

14 15
4. OPERATION
NOTE: All models display an 8 in all digits for
1 sec. at power-up.
700 Hour Meter (AC/DC)
To Display & Operate: Apply DC+ or AC hot to pin 1
and DC – or AC neutral to pin 2. The accumulation of
elapsed time is indicated by the flashing hourglass icon.
If power has been applied for 5 seconds minimum, the
accumulated time will be stored in non-volatile memory
when power is removed.
To Reset: (for Resettable Models) Apply DC+ or AC hot
to pin 4 for 1/2 second minimum while power (pins 1 &
2) is applied for 5 seconds minimum. The reset voltage
must be at the same level as the voltage used to power
the unit.
701 Hour Meter (AC/DC or DC Only)
To Display: Apply DC+ or AC hot to pin 1 and DC– or
AC neutral to pin 2. The display is activated at this point
but the elapsed time will not be accumulated until a
signal is applied to pin 3. Note, for proper operation:
Power must be applied to pins 1 & 2 before or coincident
with pin 3.
701 Hour Meter continued
To Operate: Apply DC+ or AC hot to pin 3 for 1/2
second minimum (AC/DC model) or DC+ for 1
millisecond mimimum (DC Only model). The accumulation
of elapsed time is indicated by the flashing hourglass
icon. If power (pins 1 & 2) has been applied for 5 seconds
minimum, the accumulated time will be stored in non-
volatile memory when power is removed.
To Reset: (for Resettable Models) Apply DC+ or AC hot to
pin 4 for 1/2 second minimum while power (pins 1 & 2) is
applied for 5 seconds minimum. The reset voltage must be
at the same level as the voltage used to power the unit.
703 Counter (AC/DC or DC Only)
To Display: Apply DC+ or AC hot to pin 1 and DC – or AC
neutral to pin 2. The display is activated at this point but
the count will not be started until a signal is applied to pin
3. Note, for proper operation: Power must be applied to
pins 1 & 2 before or coincident with pin 3.
To Operate: Apply DC+ or AC hot to pin 3. The count is
incremented when the input signal is removed from pin 3.

16 17
703 Counter continued
The input signal must be applied for 1/2 second
minimum (AC/DC model) or for 1 millisecond
mimimum (DC Only model). If power (pins 1 & 2) has
been applied for 5 seconds minimum, the incremented
count will be stored in non-volatile memory when power
is removed.
To Reset: (for Resettable Models) Apply DC+ or AC hot to
pin 4 for 1/2 second minimum while power (pins 1 & 2) is
applied for 5 seconds minimum. The reset voltage must
be at the same level as the voltage used to power the unit.
732 Hour Meter (DC Only)
To Activate Display: Apply DC+ to pin 1 and DC- to pin 2.
To Activate LED: Apply DC+ (for active-high models) or
DC- (for active-low models) to pin 3 during indicator-on
condition.
To Activate Elapsed Time: For models without separate
enable option - elapsed time is activated when power is
applied to pins 1 & 2. For models with enable option -
apply signal to pin 4. Note: Power (to pins 1 & 2) must be
applied before or at the same time as signal to pin 4.
732 Hour Meter continued
Operation: Apply DC+ to pin 4 for 1 millisecond
minimum. Activation (accumulation) of elapsed
time is indicated by the hourglass icon flashing. Time
accumulated will be stored into non-volatile memory when
power is removed, if power (to pins 1 & 2) has been applied
for the minimum of 5 seconds.
Reset: (for resettable models), Apply DC+ to pin 4 for 1/2
second minimum, while power to pins 1 & 2 has been
applied for 5 seconds minimum. Note: The reset voltage
must be at the same level as the voltage used to power
the unit.

18 19
5. TROUBLESHOOTING
To maximize the life of this meter, please read
all instructions carefully and review Safety
Precautions on inside front cover of this manual. Most
minor problems can be resolved by removing all power
for at least 10 seconds and then reconnecting.
Problem Possible Cause
No Display Power not connected or too low.
Display Present, but counter
does not activate.
Input (or enable) wire not connected. Start
Input not connected. Input voltage not reaching
specified minimum signal level.
LED not turning ON during
activation condition. Switch or switch-connection faulty.
6. MAINTENANCE
Curtis Model 700 & 732 Series hour meters are not
serviceable in the field. Units returned to the factory within
the warranty period (see inside backcover) will be replaced
without charge.
7. WARRANTY
Curtis Instruments’ products and/or components are
guaranteed against defects in workmanship and material
for a period of two years, or as defined in the individual
product literature, from date of shipment from our factory,
when applied in a proper application within specified ratings.
This guarantee is limited to repairor replacement F.O.B. our
factory. There is no further warranty or implied representation,
guarantee, promise or agreement as to any Curtis Instruments
product and/or component. Curtis Instruments, Inc., cannot
assume responsibility or accept invoices for unauthorized
repairs to its products and/or components,even though
defective. In no case will Curtis Instruments’ responsibility
extend to products, components or equipment not of its
manufacture. Under no circumstances shall Curtis Instruments,
Inc., be liable for any special or consequential damages or
loss of profits or other damages. Returned goods will not
be accepted unless identified by a Curtis Return Material
Authorization (RMA).
All specifications are subject to
change without notice.
Other manuals for 700 series
1
This manual suits for next models
1
Table of contents
Other Curtis Measuring Instrument manuals