Curtiss-Wright EXLAR Tritex II AC Manual

Curtiss-Wright | Tritex II AC 90, 115 Rev. XPN39892 7/12/22
1
Tritex II®AC Series Actuators
240V AC Linear and Rotary Actuator
90 mm and 115 mm Frame Sizes
Installation and Service Manual
Information furnished by Exlar Corporation is believed to be accurate and reliable.
However, no responsibility is assumed by Exlar Corporation for its use. Exlar reserves the
right to change the design and operation of the equipment described herein and any
associated motion products that may appear in this document. Information in this document
pertaining to equipment not furnished by Exlar should be confirmed by that equipment
manufacturer. Exlar assumes no responsibility for changes to information by other
manufacturers or errors in that information or the description of that information. Information
in this document is subject to change without notice.
This document does not contain any export controlled technical data.

Curtiss-Wright | Tritex II AC 90, 115 Rev. XPN39892 7/12/22
3
TABLE OF CONTENTS
SAFETY CONSIDERATIONS ........................................................................................... 5
Warnings and Cautions................................................................................................. 5
Underwriters Laboratories Listed.................................................................................. 8
UL Certificate of Compliance ...................................................................................... 11
CE Declaration of Conformity ..................................................................................... 12
UK Declaration of Conformity ..................................................................................... 12
EU Declaration of Conformity ..................................................................................... 12
CSA Certified Product................................................................................................. 17
GENERAL SPECIFICATIONS ........................................................................................ 21
Tritex II Overview........................................................................................................ 21
Drive Specification for all Tritex 240 Volt Models........................................................ 22
Specifications: Size 90 Linear Actuators..................................................................... 23
Specifications: Size 115 Linear Actuators................................................................... 24
Specifications: Size 90 Motors and Gearmotors......................................................... 25
Extended Temperature De-ratings.............................................................................. 27
Linear Actuator Ordering Guide.................................................................................. 28
MECHANICAL INSTALLATION ..................................................................................... 30
Mounting and Operating Considerations .................................................................... 30
Lubrication .................................................................................................................. 30
General Operation ...................................................................................................... 31
Mounting Configurations............................................................................................. 31
T2M Series Linear Actuator Anti-rotation Option ........................................................ 31
T2M/X090 Actuator Mounting Dimensions ................................................................. 32
T2M/X115 Actuator Dimensions ................................................................................. 33
R2M090 and R2G090 Motor/Gearmotor Dimensions................................................. 34
R2M115 and R2G115 Motor/Gearmotor Dimensions................................................. 35
Options and Rod End Attachment Dimensions........................................................... 36
Outdoor and Wash Down Installations........................................................................ 38
ELECTRICAL INSTALLATION....................................................................................... 41
Introduction ................................................................................................................. 41
Tritex Configurations................................................................................................... 42
Grounding ................................................................................................................... 43
Shielding ..................................................................................................................... 44
NPT Connections........................................................................................................ 44
AC Input Power........................................................................................................... 45
Input Power Ratings......................................................................................... 45
AC Supplies NOT Requiring Transformers...................................................... 45
AC Supplies Requiring Transformers .............................................................. 48
Wire Size, Branch Circuit Protection and Overcurrent Protection.................... 50
Power Terminal Wiring..................................................................................... 51
Power Terminal Connections........................................................................... 52
Power Connector Wiring.................................................................................. 53
Brake / Shunt Resistor Considerations....................................................................... 54
Control Logic Power Supply........................................................................................ 56

Curtiss-Wright | Tritex II AC 90, 115 Rev. XPN39892 7/12/22
4
Input / Output Connections .............................................................................. 56
Terminal Board Connections for Digital and Standard Analog I/O................... 56
Terminal Board Connections for IA4 Option (4-20 mA Isolated Analog I/O..... 57
I/O Wiring for “I” option (M16 I/O connector).................................................... 57
I/O Power Supply............................................................................................. 60
4-20 mA I/O - IA4 Option Board....................................................................... 67
Communications ......................................................................................................... 70
Standard Modbus RTU Communications ........................................................ 70
Important Considerations................................................................................. 72
PC Communications ........................................................................................ 73
CANopen ......................................................................................................... 74
Ethernet Options, EIP or TCP or ProfiNET...................................................... 75
AF Option - Absolute Feedback....................................................................... 76
MAINTENANCE PROCEDURES FOR RE-GREASING................................................. 78
Maintenance Procedure for Roller Screw Re-Greasing.............................................. 78
Disassembly..................................................................................................... 78
Lubrication Maintenance.................................................................................. 79
Grease Renewal .............................................................................................. 79
Reassembly ..................................................................................................... 80
Maintenance Procedures for Complete Re-Greasing................................................. 81
Disassembly..................................................................................................... 81
Lubrication Maintenance.................................................................................. 82
Grease Renewal .............................................................................................. 82
Reassembly ..................................................................................................... 83
ACCESSORIES............................................................................................................... 85
Cables......................................................................................................................... 85
RETURNING A PRODUCT FOR REPAIR...................................................................... 88

Curtiss-Wright | Tritex II AC 90, 115 Rev. XPN39892 7/12/22
5
SAFETY CONSIDERATIONS
Warnings and Cautions
As with any electro-mechanical device, safety must be considered
during the installation and operation of your Tritex II Series actuator.
Throughout this manual, you will see paragraphs marked with CAUTION
and WARNING signs as shown below:
“WARNING”indicates the information following is
essential to avoiding a safety hazard.
“CAUTION” indicates the information following is
necessary for avoiding a risk of damage to the product or
other equipment.
General
Failure to follow safe installation guidelines can cause
death or serious injury. The voltages used in the product
can cause severe electric shock and/or burns and could be lethal.
Extreme care is necessary at all times when working with or adjacent to
the product. The installation must comply with all relevant safety
legislation in the country of use. The forces created by actuator could be
lethal or cause severe injury if proper protection is not provided to keep
personnel away from moving components.
System Design and safety for personnel
The actuator is intended as a component for professional
incorporation into complete equipment or a system. If
installed incorrectly, the actuator may present a safety hazard. The
actuator uses high voltages and currents, carries a high level of stored
electrical energy, and is used to control equipment which can cause
injury. Close attention is required to the electrical installation and the
system design to avoid hazards either in normal operation or in the event
of equipment malfunction. System design, installation, commissioning
WARNING
CAUTION
WARNING
WARNING

Curtiss-Wright | Tritex II AC 90, 115 Rev. XPN39892 7/12/22
6
and maintenance must be carried out by personnel who have the
necessary training and experience. They must read this safety
information and this manual carefully.
None of the functions or features of the Tritex actuator may be
used to ensure safety of personnel, i.e. they must not be used for
safety-related functions.
For example the actuators enable / disable, brake, stop/start and
forward/reverse functions are not sufficient for use in safety-critical
applications without additional independent channels of protection.
Careful consideration must be given to the functions of the actuator
which might result in a hazard, either through their intended behavior or
through incorrect operation due to a fault. In any application where a
malfunction of the actuator or its control system could lead to or allow
damage, loss or injury, a risk analysis must be carried out, and where
necessary, further measures taken to reduce the risk.- for example a
failsafe brake in case of loss of actuator braking power.
Never attempt to connect or disconnect the actuator
with power applied.
Dangerous voltages are present. Damage to equipment
and injury to personnel can result. Refer to the following warnings on
supply isolation and stored energy discharge time for more information.
Supply isolation
The AC supply or high voltage DC supply must be
removed from the actuator using an approved isolation
device or disconnect before any maintenance is performed except
adjustments to the settings or parameters as specified in the manual.
Risk of Electric Shock.
Allow 3 minutes for Discharge Time.
The actuator contains capacitors that remain charged to a
potentially lethal voltage for up to 3 minutes after the
supply has been removed. Do not touch power wiring or terminals until
this discharge time has expired.
WARNING
WARNING
WARNING
3-Minutes

Curtiss-Wright | Tritex II AC 90, 115 Rev. XPN39892 7/12/22
7
If connected by plug and socket
A special hazard may exist where the actuator is
incorporated into a system connected to the AC supply by
a plug and socket. The pins of the plug are not generally isolated from
the charge stored in the bus capacitor, so must be considered electrically
“hot” until the discharge time has expired. It is the responsibility of the
user to avoid any possibility of electric shock from the pins when they are
accessible.
Grounding - High Leakage Current
The drive must be grounded by a conductor sufficient to
carry all possible fault current in the event of a fault. This
equipment has high earth leakage current. You must comply with local
safety regulations with respect to minimum size and special installation
requirements on the protective earth conductor for high leakage current
equipment. The instructions for ground connections shown in this manual
must be followed.
Compatibility with Residual Current-operated
Protection Device (RCD)
This product can cause a DC current in the protective
earthing conductor. Where a residual current –operated protective (RCD)
or monitoring (RCM) device is used for protection in case of direct or
indirect contact, only an RCD or RCM of Type B is allowed on the supply
side of this product.
Hot Surface – Risk of Burn.
Exposed surfaces of the actuator may exceed 70 degrees
C under normal operation and can take a long time to cool,
resulting in a risk of burns when touched.
WARNING
WARNING
CAUTION
WARNING

Curtiss-Wright | Tritex II AC 90, 115 Rev. XPN39892 7/12/22
8
Underwriters Laboratories Listed
Certain models of Tritex II Linear and Rotary Actuators are marked
“UL Listed” after passing a rigorous set of design and testing criteria
developed by Underwriters Laboratories (UL508C). This label indicates
that UL certifies this product to be safe when installed according to the
installation instructions and used in accordance with the product
specifications and the following conditions of acceptability:
The conditions of acceptability required by UL are:
•Drive input maximum continuous operating ratings:
Input Voltage (all models): 240 VAC, 1 Ф, 50/60 Hz
Drive Model
Drive Description
Input Continuous
Current (Arms)
R2M090- or R2G090-
90 mm rotary motor
6.3
R2M115- or R2G115-
115 mm rotary motor
8.3
T2M090- or T2X090-
90 mm linear
actuator
6.3
T2M115- or T2X115-
115 mm linear
actuator
8.3
•Above full load ratings are at a maximum surrounding air
temperature of 25°C.
•This product is “Suitable For Use On A Circuit Capable of
Delivering Not more Than 5,000 rms Symmetrical Amperes,
240 Volts maximum”, when protected by fuses or inverse-time
circuit breaker only, sized 250% FLA maximum.
•Drives shall be protected by Class CC or Class RK1 fuses or
drives shall be protected by non-semiconductor fuses or inverse-
time circuit breakers only, sized a maximum of 250% of the
drives FLA and 250 Volts maximum.
•“Integral solid state short circuit protection does not provide
branch circuit protection. Branch circuit protection must be
provided in accordance with the National Electrical Code and
any additional local codes”.
IND. CONT. EQ.
UL File E325731

Curtiss-Wright | Tritex II AC 90, 115 Rev. XPN39892 7/12/22
9
•If used, the +24 VDC Control Logic power supply and/or the I/O
power supply must be a recognized or listed Class 2 Power
Supply
•A secondary circuit intended to be supplied from a Class 2
transformer or power source in the field shall be marked “Class
2” next to the voltage rating of the device.
•If used, optional input control power shall be 24 VDC, Class 2
supply or 24 VDC provided with a 4A fuse.
•L1, L2, PE: For input terminals maximum 14 AWG wire shall be
used but not less than 125% of the maximum current for the
input.
•Wires ends are to be solid for input terminal connections. When
stranded wire is used tin the wires or a similar method should be
used to prevent stray strands of wire.
•Do not strip wires more than 0.25 inch (6.3 mm) for input
terminal leads.
•“Use copper conductors only”for all power wiring.
•Use UL approved copper only wires, 300 Vac minimum rating,
and 105º C minimum rating at input power and PE terminals.
•The Type 4 enclosure rating requires that the motor face plate is
attached to a similarly rated panel enclosure.
•A ½ inch NPT connection with conduit is required to maintain
Type 4 enclosure rating. Teflon tape or equivalent must be used
to seal the NPT conduit to the housing.
Additional Information Related to UL
Motor Over temperature Sensing is not provided by the Drive
Though Tritex II AC has a high temperature limit switch built into the
motor, its overall function has not been approved by UL for motor over
temperature protection and is therefore not used as the basis for motor
overload protection.
Electronic Overload Protection
Solid state overload protection is provided in each model at no more
than 110% of rated output torque / force. This overload protection is
based on maximum continuous current capacity. It will allow up to 200 %
of rated output to be delivered for the amount of time determined by the
following chart:

Curtiss-Wright | Tritex II AC 90, 115 Rev. XPN39892 7/12/22
10
0
10
20
30
40
50
60
100 125 150 175 200
Time (sec)
% Rated Output
Torque / Force Output vs. Time

Curtiss-Wright | Tritex II AC 90, 115 Rev. XPN39892 7/12/22
11
UL Certificate of Compliance

Curtiss-Wright | Tritex II AC 90, 115 Rev. XPN39892 7/12/22
12
CE Declaration of Conformity
The Tritex II Linear and Rotary Actuators are marked with the
“Conformité Européenne Mark” (CE Mark) after passing a rigorous set of
design and testing criteria. This label indicates the product meets
applicable electrical safety, and electromagnetic immunity and emissions
(EMC) standards when installed according to the installation instructions.
The conditions of acceptability required for CE are:
•Drive input maximum continuous operating ratings:
Input Voltage (all models): 240 VAC, 1 Ф, 50/60 Hz
Drive Model
Drive Description
Input Continuous
Current (Arms)
R2M090- or R2G090-
90mm rotary motor
6.3
R2M115- or R2G115-
115mm rotary motor
8.3
T2M090- or T2X090-
90mm linear
actuator
6.3
T2M115- or T2X115-
115mm linear
actuator
8.3
•L1, L2, PE: For input terminals maximum 14 AWG/ 2.5mm² wire
shall be used but not less than 125% of the maximum current for
the input.
•Wires ends are to be solid for input terminal connections. When
stranded wire is used tin the wires or a similar method should be
used to prevent stray strands of wire.
•Do not strip wires more than 0.25 inch (6.3 mm) for input
terminal leads.
•Use 300VAC minimum rating, and 105º C minimum rating
copper wires
•An externally connected ground wire must be used. Single rear
screw connection, screw. Must be earthed (grounded) for safety,
minimum wire size 2.5mm². Adequate strain relief and
mechanical protection must be provided for this wire. Note, this
does not replace and is used in addition to the 2.5mm² grounding
conductor that is connected to the input power terminals.
•If used, the +24 VDC Control Logic power supply and/or the I/O
power supply must be a CE marked 24V supply and negative
side must be connected to PE.
•This product is suitable for use on a circuit capable of delivering
5,000 rms symmetrical amperes, 240 volts maximum, when
protected with by a Class RK1 or Class CC fuse or Inverse Time
Circuit Breaker, rated at 15 A rms.

Curtiss-Wright | Tritex II AC 90, 115 Rev. XPN39892 7/12/22
13
•The full load ratings are at a maximum surrounding air
temperature of 25°C, see de-rating chart below for higher
ambient temperatures.
•All cables must be shielded, with the outer shield bonded to
the case.
•When using cable glands use glands that connect the braided
shield of the cable directly to enclosure.
•When using connectors ensure that the outer shield of the cable
is in full contact with the connector housing. Connector housings
must conductive.
•Make ground connections as short as possible for low
impedance.
•Keep cable runs as short as possible. Power and signal cables
must be separated and far as possible and only crossing them at
right angles as described in the Cable routing section of this
manual.
•IP rating: Model T2M actuators are IP 54 rated unless they
include the IP65 option, Models T2X, R2M, and R2G are IP65
rated.
•To maintain IP rating the RS485 cable or cap must be installed.
All other cable connections must be connected or sealed.

Curtiss-Wright | Tritex II AC 90, 115 Rev. XPN39892 7/12/22
14

Curtiss-Wright | Tritex II AC 90, 115 Rev. XPN39892 7/12/22
15

Curtiss-Wright | Tritex II AC 90, 115 Rev. XPN39892 7/12/22
16
Per EU directives implemented on April 20th, 2016 the following requirement for
requirement must be followed by Importers and Distributors.
The requirements for importers include:
Importers shall indicate their name, registered trade name or registered trade mark and the
postal address at which they can be contacted on the apparatus (unless that is not
possible, in which case it should be included on the packaging or in an accompanying
document).
Importers shall ensure that the product is accompanied by instructions and safety
information in a language which can be easily understood by end-users, as determined by
the Member State concerned.
Importer is to translate the EU declaration of conformity into the languages required by the
member state(s), where the product is sold.” Importers shall keep a copy of the EU
declaration of conformity (for 10 years).
Importers shall provide a reasoned request from a competent national authority and provide
it with all the information and documentation in paper or electronic form necessary to
demonstrate the conformity of a product in a language which can be easily understood by
that authority.
Importers shall ensure that, while apparatus is under their responsibility, its storage or
transport conditions do not jeopardize its compliance with the safety objectives.
Importer shall corrective action necessary when they consider or have reason to believe
that the product is not in conformity with its directive(s).
The requirements for distributor include:
Distributors shall indicate their name, registered trade name or registered trade mark and
the postal address at which they can be contacted on the apparatus (unless that is not
possible, in which case it should be included on the packaging or in an accompanying
document).
Distributor shall ensure that apparatus is accompanied by instructions and safety
information in an appropriate language. Distributor shall translate the EU declaration of
conformity into the languages required by the member state(s), where the product is sold.”
Distributors shall keep a copy of the EU declaration of conformity (for 10 years).
Distributor shall ensure that, while apparatus is under their responsibility, its storage or
transport conditions do not jeopardize its compliance with the safety objectives.
Distributor shall corrective action necessary when they consider or have reason to believe
that the product is not in conformity with its directive(s).

Curtiss-Wright | Tritex II AC 90, 115 Rev. XPN39892 7/12/22
17
CSA Certified Product
The Tritex II Linear and Rotary Actuators are marked as
shown after passing a rigorous set of design and testing
criteria developed by CSA International (C22.2 No. 139).
This label indicates that CSA certifies this product to be
safe when installed according to the installation guidelines and used with
the scope of the product specifications.
The conditions of acceptability required by CSA are:
•Drive input maximum continuous operating ratings:
Input Voltage (all models): 240 VAC, 1 Ф, 50/60 Hz
Drive Model
Drive Description
Input
Continuous
Current (Arms)
R2M090- or R2G090-
90 mm rotary motor
6.3
R2M115- or R2G115-
115 mm rotary motor
8.3
T2M090- or T2X090-
90 mm linear actuator
6.3
T2M115- or T2X115-
115 mm linear actuator
8.3
•Maximum Rated Force: Up to 3325 lbf (14kN)
•Installation Requirements
- Hazardous Location (Class I Division 2 Group A, B, C, D)
installations – ½” rigid conduit with NPT connections and use
UL approved copper only wires, 14 AWG, 300 Vac minimum
rating, and 105º C minimum rating shall be used.
- For other non-hazardous locations:
• Use the above connection method, or
• Cable with connector assemblies, or
• Cables with cable glands are permitted.
For additional information on cable installations or part numbers
contact Exlar Corporation.
•If a customer requires an additional +24 VDC power supply to
provide power then it must be a recognized or listed Class 2
Power Supply.
•Branch circuit protection must be provided. Reference the
manual’s electrical installation section for fuse and circuit breaker
options. Note: branch circuit protection must be located outside
of the hazardous location environment.

Curtiss-Wright | Tritex II AC 90, 115 Rev. XPN39892 7/12/22
18
•The full load ratings are at 25°C ambient temperature. See de-
rating chart on page 13 for higher ambient temperatures.
•These conditions of acceptability only apply to units with a CSA
mark on the product label.

Curtiss-Wright | Tritex II AC 90, 115 Rev. XPN39892 7/12/22
19
This manual suits for next models
3
Table of contents
Other Curtiss-Wright Controllers manuals

Curtiss-Wright
Curtiss-Wright EXLAR GTX Series Installation and maintenance instructions

Curtiss-Wright
Curtiss-Wright Compact CHAMP-AV IV User manual

Curtiss-Wright
Curtiss-Wright Tritex EVA080 Installation and maintenance instructions

Curtiss-Wright
Curtiss-Wright EL30 Manual

Curtiss-Wright
Curtiss-Wright EXLAR GTX Series Installation and maintenance instructions