Cutler-Hammer S801N User manual

Pub 49004
Revision F
Cutler-Hammer Intelligent Technology (IT) S801N and
S801R Soft Starter Models Quick Setup Guide
Effective 9/00
Unpacking
Remove all packing material from the unit. Be sure to
remove all packing material from lug locations. Also, make
sure no packing material blocks the air flow near the fans.
Check the unit for an signs of shipping damage. If further
damage to the product is found after unpacking, report it
to the freight compan . Retain the packing materials for
carrier to review.
Verif that the units catalog number and options match
those stated on the order/purchase form.
Storage
It is recommended that the unit be stored in its original
shipping box/crate until it is to be installed.
The unit should be stored in a location where:
- The ambient temperature is between -50oC and 70oC
(-58oF and 158oF).
- The relative humidit is between 0% and 95%, non-
condensing
- The environment is dr , clean, and non-corrosive
- The unit will not be subjected to high shock or vibration
conditions
Introduction
The Intelligent Technolog (IT) Soft Starter is an electronic,
self-contained, panel or enclosure mounted motor soft-
starting device. It is intended to provide 3-phase induction
motors with a smooth start, both mechanicall and elec-
tricall . The IT line of soft starters utilizes six th ristors
connected in a full wave power bridge. The voltage and
current applied to the motor is controlled b var ing the
th ristor conduction period. This, in turn, controls the
torque supplied b the motor. After the motor reaches
speed, single phase b pass contactors are energized to
b pass the th ristors.
The Intelligent Technolog (IT) Soft Starter is designed
to fulfill the industrial service requirements for applications
such as chiller starters, pump panels, and machine tools.
The Intelligent Technolog (IT) Soft Starter meets all
relevant specifications set forth b ICS-1, ICS-2, ICS-5,
UL508, IEC 60947-4-2, CE, and CSA.
This leaflet is intended to cover basic installation and
setup for Models S801N and S801R Soft Starters. For a
cop of the S801 Soft Start User Manual (publication
49003), contact Cutler-Hammer.
No publication can take into account ever possible situ-
ation. If ou require further assistance with an aspect of
this product or a particular application, feel free to contact
us. You will find our address, phone number, and other
contact information on the back cover of this instruction
leaflet.
Inspection
General
Upon receipt of the unit, verif that the catalog number
and unit options stated on the shipping container match
those stated on the order/purchase form.
Inspect the equipment upon deliver . Report an carton
damage to the carrier prior to accepting the deliver . Have
this information noted on the freight bill. Cutler-Hammer
is not responsible for damage incurred in shipping.

Pub 49004
Fig. 1 Model S801N (65mm)
Effective 9/00
Page 2
Mounting Dimensions
Fig. 2 Model S801R (110mm)
Frame Screw Washer Quantity Torque
Size Size Size Required Required
S801N #10 - 32 x 0.5 Standard #10 41.7 N-m
65mm Lockwasher and (15 in-lb)
(2.55 in) Flat Washer
S801R 1/4 - 20 x 0.625 Standard 1/4 42.8 N-m
110mm Lockwasher and (25 in-lb)
(4.33 in) Flatwasher
Required Mounting Hardware
Frame Size Weight of Unit
65mm 2.6 Kg (5.8 pounds)
110mm 4.8 Kg (10.5 pounds)
Weight Support Requirements
Mm
[Inches]
Mm
[Inches]
Table 1
Table 2

Pub 49004
Effective 9/00
Page 3
Operating Temperature Range -40oC to 50oC (-40oF to 122oF)
Storage Temperature Range -50oC to 70oC (-58oF to 158oF)
Elevation Above 2000 Meters (6600 feet) consult factor
Humidity Functional to 95% non-condensing
Operating Orientation An
Pollution Degree IEC 947-1 3
Shock Resistance 15g in an direction
Vibration Resistance 3g in an direction
Environmental Requirements
Mounting Instructions for Models S801N and S801R
The IT Soft Starter is eas to mount. It does not require
an special tools.
To aid ou with panel la out, refer to the dimension
drawings on page 2 of this leaflet. Drill and tap holes per
mounting hole location as shown.
To mount the unit, use all the hardware specified in Table
1 on page 2 of this leaflet. Tighten to the torque specified.
TO AVOID SHOCK HAZ-
ARD, DISCONNECT ALL
POWER BEFORE ANY
FUNCTIONS ARE PER-
FORMED ON THIS
EQUIPMENT.
POUR EVITER TOUT
CHOC ELECTRIQUE,
COUPLER L’ALIMENTA-
TION DE CET EQUIPE-
MENT AVANT D’Y EF-
FECTUER DES
TRAVAUX.
AVERTISSEMENT
WARNING
Hazard of Burn or
Electrical Shock
Risque de Brulure ou de
Choc Electrique
Wiring Diagrams
Each diagram illustrates a t pical wiring scheme for the
options described. The soft starter is represented b the
terminal board. The additional items shown on the dia-
grams are not included, but the ma be purchased from
Cutler-Hammer.
Fig. 3 Elementary Diagram for Soft Starter with
START/STOP/RESET/JOG with 120VAC
Alarm and Run Indication
261348
Table 3

Pub 49004
Effective 9/00
Page 4
Fig. 5 Terminal Board
APPLY ONLY 24VDC TO CONTROL TERMINAL
BOARD UNLESS SPECIFIED OTHERWISE IN THIS
MANUAL. ALL CONTROL WIRING IS 22 - 12 AWG.
FAILURE TO FOLLOW THIS CAUTION COULD RE-
SULT IN SEVERE DAMAGE TO THE CONTROLLER.
Power Wiring
Control Wiring Inputs
The controller on the IT Soft Starter has the inputs shown
in Table 4 on Page 5 of this leaflet.
Fig. 4 Elementary Diagram for Soft Starter with
HAND/OFF/AUTO/RESET with PLC Shown
with 120VAC Alarm and Run Indication
261349
CAUTION
APPLIQUER UNE TENSION DE 24V C.C. AUX BORNES
SAUF AVIS CONTRAIRE DANS CE MANUEL. TOUTE
LA FILERIE DE COMMANDE EST DE CALIBRE 22 A
12 AWG. L’INOBSERVATION DE CETTE MESURE
POURRAIT CAUSER DES DOMMAGES IMPORTANTS
AU CONTROLEUR.
ATTENTION
THERE CAN BE LINE VOLTAGE POTENTIAL AT THE
MOTOR LOAD TERMINALS EVEN WITH THE START-
ER IN THE OFF STATE. THIS IS DUE TO THE POSSI-
BLE LEAKAGE ACROSS SCRS. ALWAYS DISCON-
NECT INPUT POWER BEFORE SERVICING STARTER
MOTOR.
CAUTION
IL PEUT EXISTER UNE TENSION DE LIGNE AUX
BORNES DU COTE CHARGE DU MOTEUR BIEN QUE
LE MOTEUR SOIT ARRETE. CELAS’EXPLIQUE DU
FAIT DE FUITES POSSIBLES A TRAVERS LES RE-
DRESSEURS AU SILICIUM. TOUJOURS DEBRANCH-
ER L’ALIMENTATION AVANT D’EFFECTUER DES
TRAVAUX SUR LE DEMARREUR.
ATTENTION

Pub 49004
Effective 9/00
Page 5
Providing Control Power
Name Terminal Board Default Input
Designation
Common - - Negative
Power + - 24VDC nominal
Permissive P (24VDC onl ) Hardwired Stop 24 VDC onl
Input 1 1 (24VDC onl ) Start 24VDC onl
Input 2 2 (24VDC onl ) Jog Forward 24VDC onl
Input 3 3 (24VDC onl ) Overload Disable 24VDC onl
Input 4 4 (24VDC onl ) Fault Reset 24VDC onl
Common 13 - Rela close connects to 14
NO Contact 14 - 3 Amps @ 120VAC/24VDC
in B pass 10 Amps, Max (Resistive) Switching
Common 95 - NC Connects to 96. Rela closure connects to 98.
Read 96 - 3 Amps @ 120VAC/24VDC
10 Amps, Max (Resistive) Switching
Fault 98 - 3 Amps @ 120VAC/24VDC
10 Amps, Max (Resistive) Switching
Control Wiring Inputs
13 and 14 - Closes when in b pass. Contact is normall open.
95 and 96 Close - S stem OK, Open Fault. Pins 95, 96, and
98 are Form C contact. 95 acts as the common, 96 is a normall
closed contact, and 98 is a normall open contact. On an
fault that trips the unit or causes it not to start, 96 opens and
98 closes.
95 and 98 Open - S stem OK, Close - Fault
95 and 96 Open - Fault
The control wiring is connected to the soft starter b a
12-pin terminal strip connector located on the front of the
unit. Each connection is capable of holding one or two
#22 - #16 AWG wires, or one #14 or #12 AWG wire.
Each terminal should be tightened to 3.5 in-lb.
APPLY ONLY 24VDC TO CONTROL TERMINAL
BOARD UNLESS SPECIFIED OTHERWISE IN THIS
MANUAL. ALL CONTROL WIRING IS 22 - 12 AWG.
FAILURE TO FOLLOW THIS CAUTION COULD RE-
SULT IN SEVERE DAMAGE TO THE CONTROLLER.
CAUTION
APPLIQUER UNE TENSION DE 24V C.C. AUX BORNES
SAUF AVIS CONTRAIRE DANS CE MANUEL. TOUTE
LA FILERIE DE COMMANDE EST DE CALIBRE 22 A
12 AWG. L’INOBSERVATION DE CETTE MESURE
POURRAIT CAUSER DES DOMMAGES IMPORTANTS
AU CONTROLEUR.
ATTENTION
1. Connect DC common (negative) to pin -.
2. Connect +24VDC positive to pin +.
3. Pin P, permissive circuit, must be energized (+24VDC)
to allow operation of unit. If power is removed from
permissive circuit at an time, unit will initiate a stop.
4. If 24VDC power is toggled to Input 1 while P is at 24V,
device will initiate a start.
5. Input 2 is Forward Jog. If 24VDC power is applied to
Input 2 while P is at 24V, the soft starter will initiate
motor jog.
6. Input 3 is Overload Disable. When Input 3 is toggled,
the overload will be disabled for the next start.
7. If +24VDC input power is applied to Input 4, the soft
starter is reset. Faults are cleared onl if fault has
been corrected.
8. Pins 13 and 14 - 120VAC or 24VDC provide for the
integral b pass contact. The integral b pass contact
will close upon b pass and will remain closed until
stop is initiated. Motor ma continue to run even after
stop is initiated during soft stop until programmed
ramp has been completed.
9. Pins 95, 96, and 98 provide alarm circuit NO-NC
change state on an fault. Form C Max. 24VDC,
120VAC, 3 amps.
NOTE - When control power (+24VDC) is first applied,
all the LEDs on the CIM will illuminate briefl . This is a
normal startup test that verifies communication to the
CIM. Pressing Fault Reset also momentaril lights all
the LEDs. This verifies the CIM board is functional, and
tests all LEDs for functionalit .
Table 4

Pub 49004
Effective 9/00
Page 6
Catalog Steady State Inrush Input
Number Wattage Wattage Voltage
PSS55A 55W 250W 115VAC
PSS55B 55W 250W 230VAC
PSS55C 55W 250W 360 - 480VAC
Protective Features, Cont’d
timer. If 24VDC power is removed, the soft starter remem-
bers the remaining cool-down time and will not reset until
the total cool-down time has elapsed.
The unit monitors these conditions for overload:
Thermal (current) Overload - monitors RMS, with a
5, 10, 20, or 30-second dela time based on Trip
Class setting.
Protective Setting Factory
Feature Default
Overload 32% - 100% of rated current 32%
(FLA Dial Range)
Trip Class 5, 10, 20, 30 5
Fault Reset Auto, Manual Manual
Jam On, Disable On
Stall On, Disable On
Phase Loss On, Disable On
Phase Reversal On, Disable On
Overload On, Disable On
Programming Settings
General
To program and operate the IT Soft Starter, a Control
Interface Module (CIM) is required (see Fig. 6). The CIM
(Catalog No. EMA71) is for use with all models: S801N,
S801R, S801T, and S801V. The CIM (Catalog No. EMA72)
is used with all model S801N, S801R, S801T and S801V
with the pump control option (see Fig. 7). The CIM serves
as the interface between the operator and the Soft Starter
control circuitr to program the Soft Starter. The CIM dip
switches and rotar controls are used to select the Soft
Starter settings. When making adjustment to the CIM
under normal operation, the LEDs will function as follows:
A change to an dip switch will cause all LEDs to flash
momentaril .
An adjustment to an POT will cause all LEDs to light
and sta lit until adjustment of POT has been completed.
While selecting these parameters, 24VDC power ma be
applied to the Soft Starter, but it is not required.
NOTE: The IT Soft Starter does not have to be powered
to make adjustment to the control interface module. Once
the unit is energized, it will communicate with the CIM
and load the program into the Soft Starter. Allow the unit
2 seconds to ensure communication checks complete
and values are set. To verif CIM is operational, press
Fault Reset. If the CIM is powered and communicating,
all LEDs will momentaril flash.
See the user manual for additional detail on the standard
and pump control option.
Procedure for Starting
Application Note - Permissive (P)
(P) must be held high (24VDC) in order to START the
Soft Starter.
Remove 24VDC from terminal P to initiate a stop.
Run inputs (terminals 1 through 4) are a momentar
high (24VDC).
If the inputs (Input 1, 2, 3, 4) are high when the Per-
missive opens, the Soft Starter will STOP.
The Soft Starter will not start when 24VDC is applied
to the Permissive (P) until Input 1 changes from 0 volts
(open) to a high (+24V) condition. (Once P is at 24
volts, Input 1 must c cle from 0 volts to 24 volts to
start.)
On the larger soft starters when the b pass contactors
close, a sound similar to contactor chattering can be
heard. This sound is caused b more than one contactor
closing in a staggered manner over a ver short period
of time. This is part of normal operation and should not
be misinterpreted as a dirt pickup.
For two-wire control, jumper permissive (P) and Input
1, together.
24VDC Power Requirements
When sizing a 24VDC power suppl for our IT soft starter,
it must meet the following stead state and inrush charac-
teristics.
Stead State Minimum = 25 watts
Inrush Minimum = 240 watts for 150 msecs
Voltage on the unit cannot exceed 30VDC. The soft starter
will turn off at approximatel 20.9VDC.
It is recommended that power supplies from Cutler-Hammer
be used.
The following C-H power supplies are available:
Table 5
Table 6
NOTE: A minimum of #14 AWG should be used between
the power suppl and the 24V (+) and (-) terminals of the
soft starter.
Protective Features
The soft starter cannot be restarted until the calculated
cool-down time has passed. C cling power does not reset

Pub 49004
Page 7
Soft Starter Flash Codes Sent to CIM
To obtain flash codes from the CIM, hold the RESET
button down and count the number of times all the LEDs
on the CIM flash.
For example, if ou see three flashes, and then two more
flashes after a short pause, the flash code is 32.
The CIM can provide multiple flash codes, if more than
one error condition caused a stop. Once ou see the
same flash code repeated, ou have seen all the flash
codes for the error conditions that caused the stop.
For example, if ou see three flashes, a pause, then two
flashes, a pause, then four flashes, a pause, then one
flash, the flash codes are 32 and 41. If ou then see three
flashes, a pause, then two flashes, ou are seeing the
first code again. This means ou have seen all the flash
codes for this stop. You ma now release the RESET
button.
A list of flash codes and the faults the represent is shown
below.
Code Fault
11 Thermal overload trip
12 Motor stall
13 Motor jam
14 Phase sequence ACB
15 Pole over-temperature
16 SCR failed to fire
21 15V Power suppl low
22 Phase loss
23 B pass dropout
24 SCR/Contactor overcurrent
25 Phase imbalance
26 Non-volatile memor error
31 Zero voltage cross failure
32 Short SCR, phase loss, load disconnect
33 Serial communication lost
34 SCR instantaneous overcurrent
41 24V power suppl low
42 Timer s stem fault
43 Watchdog reset occurred
44 PLL (DSP)
45 Illegal address (DSP)
Effective 9/00
Table 7
Fig. 6 Soft Start Control Interface Module (CIM)
TORQUE (%)
T2T1
TORQUE
(
T
2
)
T1
T1TORQUE(T2)
45
5 85
65
25
45
5 85
65
25
30
0 60
B C
A D
FLA
CLASS
TRIP
TIME (Sec.)
tk
0 2
OVLD
RAMP START
MANUAL RESET
JAM
STALL
PH. REV.
PH. LOSS ON
ON
ON
ON DISABLE
DISABLE
DISABLE
AUTO RESET
CURRENT LIMIT
DISABLE
START
Made in U.S.A.
ON DISABLE
OVERLOAD -
20
0.5
EMA71
S.S. TRIP
60 15 45
5 10 20 30
BYPASS
BYPASS
trts
tktrts
tktrts
TRIP
10
1
1.5
0.5
180
40
15
120
5
Auto Reset
Select auto or manual reset on the Control Interface
Module.
When a fault is present, the auto-reset will attempt to
reset the fault ever 2.5 seconds. If the fault is clear, the
s stem resets the fault(s). The soft starter is read for
use, and ma be restarted b selecting Run 1 (assuming
power is present.)
The motor does NOT automaticall restart after a fault is
reset.
Fig. 7 Soft Starter Pump Control Interface Module (CIM)
TORQUE (%)
T2T1
TORQUE
(
T
2
)
T1
T1TORQUE(T2)
45
5 85
65
25
45
5 85
65
25
30
0 60
B C
A D
FLA
CLASS
TRIP
TIME (Sec.)
tk
0 2
OVLD
RAMP START
MANUAL RESET
JAM
STALL
PH. REV.
PH. LOSS ON
ON
ON
ON DISABLE
DISABLE
DISABLE
AUTO RESET
CURRENT LIMIT
DISABLE
START
Made in U.S.A.
ON DISABLE
OVERLOAD -
20
0.5
EMA72
S.S. TRIP
60 15 45
5 10 20 30
BYPASS
BYPASS
trts
tktrts
tktrts
S.F. - ENABLE DISABLE
TRIP
10
1
1.5
0.5
180
40
15
120
5
Stop Ramp ts = dial setting x 2

Pub 49004
Page 8
Ratings
HP and KW Ratings
Standard Dut Ratings
25-Second Ramp, 4 Starts per Hour, 300% Current Limit @ 40oC
15-Second Ramp, 4 Starts per Hour, 300% Current Limit @ 50oC
50-Second Ramp, 2 Starts per Hour, 300% Current Limit @ 50oC
Effective 9/00
Frame Max Catalog
Width Current Number
230 380-400 440
Volt Volt Volt 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
65mm 34 9 15 18.5 10 7.5 10 10 25 20 30 25 S801N3 N3S
63 15 30 33 20 15 20 20 40 40 60 50 N66N3S
110 mm 96 25 45 55 30 25 30 30 75 60 75 75 S801R10N3S
120 33 63 63 40 30 40 40 75 75 100 100 R13N3S
Three-Phase Motor
kW Rating (50 Hertz) hp Rating (60 Hertz)
200V 230V 460V 5 5V
Frame Max Catalog
Width Current Number
230 380-400 440
Volt Volt Volt 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
65mm 34 9 15 18.5 10 7.5 10 10 25 20 30 25 S801N3 N3S
63 15 30 33 20 15 20 20 40 40 60 50 N66N3S
110 mm 96 25 45 55 30 25 30 30 75 60 75 75 S801R10N3S
120 33 63 63 40 30 40 40 75 75 100 100 R13N3S
Three-Phase Motor
kW Rating (50 Hertz) hp Rating (60 Hertz)
200V 230V 460V 5 5V
Frame Max Catalog
Width Current Number
230 380-400 440
Volt Volt Volt 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
65mm215.51011555515101515S801N3 N3S
421118.5221010151030254030 N66N3S
110 mm 60 15 30 33 15 15 20 15 40 40 50 50 S801R10N3S
80 22 40 45 25 20 30 25 60 50 75 60 R13N3S
Three-Phase Motor
kW Rating (50 Hertz) hp Rating (60 Hertz)
200V 230V 460V 5 5V
15-Second Ramp, 4 Starts per Hour, 450% Current Limit @ 40oC
Frame Max Catalog
Width Current Number
230 380-400 440
Volt Volt Volt 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
65mm 29 7.5 12.5 15 7.5 7.5 10 7.5 20 15 25 20 S801N3N3S
49 12.5 22 25 15 10 15 15 30 30 40 40 N66N3S
110 mm 73 18.5 37 40 20 20 25 20 50 40 60 60 S801R10N3S
94 25 45 55 30 25 30 30 60 60 75 75 R13N3S
Three-Phase Motor
kW Rating (50 Hertz) hp Rating (60 Hertz)
200V 230V 460V 55V
Frame Max Catalog
Width Current Number
230 380-400 440
Volt Volt Volt 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
65mm 29 7.5 12.5 15 7.5 7.5 10 7.5 20 15 25 20 S801N3 N3S
49 12.5 22 25 15 10 15 15 30 30 40 40 N66N3S
110 mm 73 18.5 37 40 20 20 25 20 50 40 60 60 S801R10N3S
94 25 45 55 30 25 30 30 60 60 75 75 R13N3S
Three-Phase Motor
kW Rating (50 Hertz) hp Rating (60 Hertz)
200V 230V 460V 5 5V
30-Second Ramp, 4 Starts per Hour, 450% Current Limit @ 40oC
Frame Max Catalog
Width Current Number
230 380-400 440
Volt Volt Volt 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
65mm 21 5.5 10 12.5 5 5 5 5 15 10 15 15 S801N3 N3S
40 11 18.5 22 10 10 10 10 30 25 30 30 N66N3S
110 mm 55 15 25 30 15 15 20 15 40 30 50 40 S801R10N3S
75 22 37 45 20 20 25 20 50 50 60 60 R13N3S
Three-Phase Motor
kW Rating (50 Hertz) hp Rating (60 Hertz)
200V 230V 460V 5 5V

Pub 49004
Page 9
Effective 9/00
Short Circuit Ratings
Soft Starter Three Phase Short Circuit Rating
Frame Size 240V 480V 600V
S801N 65mm 10KA 10KA 10KA
S801R 110mm 10KA 10KA 10KA
15-Second Ramp, 4 Starts per Hour, 300% Current Limit @ 40oC
Severe Dut Ratings
Severe Dut Ratings are defined as an combination of parameters that exceed the Standard Dut Ratings.
Example; 35-Second Ramp, 5 Starts per Hour, 350% Current Limit @ 40 Deg C Ambient.
Frame Max Catalog
Width Current Number
230 380-400 440
Volt Volt Volt 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
65mm 37 10 18.5 18.5 10 10 10 10 25 20 30 30 S801N3 N3S
66 18.5 30 37 20 15 20 20 50 40 60 50 N66N3S
110 mm 105 30 55 59 30 25 40 30 75 60 100 75 S801R10N3S
135 40 63 80 40 30 50 40 100 75 125 100 R13N3S
Three-Phase Motor
hp Rating (60 Hertz)kW Rating (50 Hertz)
200V 230V 460V 5 5V
Frame Max Catalog
Width Current Number
230 380-400 440
Volt Volt Volt 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
65mm 22 5.5 10 11 5 5 7.5 5 15 10 20 15 S801N3 N3S
42 11 18.5 22 10 10 15 10 30 25 40 30 N66N3S
110 mm 65 15 30 33 15 15 20 15 50 40 50 50 S801R10N3S
80 22 40 45 25 20 30 25 60 50 75 60 R13N3S
Three-Phase Motor
hp Rating (60 Hertz)kW Rating (50 Hertz)
200V 230V 460V 5 5V
Cooling
Fans are used to cool the IT Soft Starter. The fans are
turned on when the temperature of an of the thermal
sensors exceeds a preset value. If the temperature is
below this value, the fans will be off.
The fans will also be turned on whenever the IT is started,
stopped, or jogged. The fans will remain on for 15 minutes
to assure the SCRs are adequatel cooled prior to the
next start or jog.
If a temperature is sensed above a second preset level,
a Pole Over-Temperature Fault will occur. This fault cannot
be reset until the temperature returns to a safe level.
Note that the fans will onl operate if 24 VDC is applied
to the + and terminals.
CE Conformity
S801N will meet IEC 60947-4-2 and EN60947-4-2
Radiated Immunit Test requirements, except for the
following frequenc bands:
80 to 89.2 MHz @ 9 V/m
90.1 to 92 MHz @ 6 V/m
S801R will meet IEC 60947-4-2 and EN60947-4-2
Radiated Immunit Test requirements, except for the
following frequenc bands:
90.04 to 92.87 MHz @ 6 V/m
91.9 to 92.8 MHz @ 9 V/m

Pub 49004
Page 10
CUTLER-HAMMER
Milwaukee, WI U.S.A.
Effective 9/00
Printed in U.S.A.
For additional information on this product,
please call our Customer-Support
Center at: 1-800-356-1243
For service or start-up assistance,
24 hours/day, 7 days/week
please call:
1-800-498-2678
Cutler-Hammer Solid State Reduced Voltage Motor Starter
Aftermarket Services
Technical/telephone support.
Resident service engineers in major trading centers.
Factory repair services.
Warranty administration.
Equipment Modification and upgrading services
Training seminars.
This manual suits for next models
8
Table of contents
Other Cutler-Hammer Controllers manuals
Popular Controllers manuals by other brands

Hardy Process Solutions
Hardy Process Solutions HI 4060 Quick installation guide

Emerson
Emerson Bettis M3 operating instructions

Tecnoplastic
Tecnoplastic SPIDER instructions

Samson
Samson TROVIS 3730-1 installation instructions

Paia
Paia 8700 Assembly and using manual

Heidolph
Heidolph Hei-VAC Control Instructions for use