• Outdoor Units • R410A • MXS-FV1B_F2V1B
1
2
• Split Sky Air • Outdoor Units
7
2 Specifications
Piping
connections Liquid(OD) Quantity 2 4 2
Diameter
(OD) mm 6.35 6.35 6.35
Gas Quantity 2 2 1
Diameter
(OD) mm 9.5 9.5 9.5
Quantity 2 1
Diameter
(OD) mm 12.7 12.7
Drain Quantity 1 1
Diameter
(OD) mm 18 18 18
Piping Length Minimum m 3 3 (for one room)
Maximum m 30(fortotalof each room)20 (forone
room) 60(fortotalofeachroom)/25(forone
room) 30(fortotal of each room)20(forone
room)
Chargele
ss m20
Additional Refrigerant
Charge kg/m 0.02/>20 0.02/>30m 0.02/>20m
Installation
height
difference
Maximum m 15 15.0 (between indoor unit and
outdoor unit) 15 (between indoor andoutdoor)7.5
(between indoors)
Max. internunit level
difference m 7.5 7.5 (between indoor units)
Heat Insulation Both liquid and gas pipes
Standard
Accessories Item Installation manual
Quantity 111
Item Screw bag Drain plug Screw bag
Quantity 111
Item Drain plug Reducer assembly Reducer assembly
Quantity 111
Notes Nominalcoolingcapacitiesarebased
on : indoor temperature : 270CDB,
190CWB, outdoor temperature :
350CDB, equivalent refrigerant
piping : 5m, level difference : 0m.
Nominalcoolingcapacitiesarebased
on : indoor temperature : 270CDB,
190CWB, outdoor temperature :
350CDB, equivalent refrigerant
piping : 7.5m, level difference : 0m.
Nominalcoolingcapacitiesarebased
on : indoor temperature : 270CDB,
190CWB, outdoor temperature :
350CDB, equivalent refrigerant
piping : 5m, level difference : 0m.
Nominalheatingcapacitiesarebased
on : indoor temperature : 200CDB,
outdoor temperature : 70CDB,
60CWB, equivalentrefrigerantpiping
: 5m, level difference : 0m
Nominalheatingcapacitiesarebased
on : indoor temperature : 200CDB,
outdoor temperature : 70CDB,
60CWB, equivalentrefrigerantpiping
: 7.5m, level difference : 0m
Nominalheatingcapacitiesarebased
on : indoor temperature : 200CDB,
outdoor temperature : 70CDB,
60CWB, equivalentrefrigerantpiping
: 5m, level difference : 0m
2-2 ELECTRICAL SPECIFICATIONS 2MXS40FV1B 4MXS68F2V1B 2MXS50FV1B
Power Supply Name V1
Phase 111
Frequency Hz 50 50
Voltage V 220-240 230
Current Starting current
(cooling/heating) A5.9 6.2 9.8
Recomended fuses A 16
Wiring
connections For Power
Supply Quantity 3 3 3
For connection
with indoor Quantity 4 4 4
Power Supply Intake Outdoor unit only
Notes RLA is based on following conditions: indoor temperature: 27°CDB/19°CWB, outdoor temperature: 35°CDB
Voltagerange:units are suitable for use on electrical systems where voltagesuppliedto unit terminal is not below or
above listed range limits
Maximum allowable voltage range variation between phases is 2%.
Select wire size based on the value of MCA or TOCA
MFA is used to select the circuit breaker and the ground fault circuit interrupter
2-1 TECHNICAL SPECIFICATIONS 2MXS40FV1B 4MXS68F2V1B 2MXS50FV1B