dalap CECYL User manual

Dalap CECYL

Please read the instructions carefully. Pay particular attention to the operating
requirements.
Axial-flow duct electric fans of the combined type
Purpose
CECYL axial-flow duct electric fans are intended for use in ventilation systems of industrial, public, and
residential buildings. The duct funs are connected to round ducts.
Electric fans are designed to remove air and other non-explosive gas-air mixtures that do not contain
sticky substances and fibrous materials, with a dust and other solid impurities content of no more than
10mg/m³, at a temperature of transported air not lower than -20 °C and not above +40 °C.
Safety requirements
The fans are designed to be connected to an alternating current with a voltage of 220-240V and a
frequency of 50Hz. According to the shock-hazard protection type, the fans refer to Class II devices (for
models 100-200), Class I (for models 250-315), in accordance with GOST 12.2.007.0-75. The climate
category «moderately cold» Type «4» (УХЛ4) GOST 15150-69.The degree of
the fan protection against access to hazardous parts and water ingress is IP44 and the degree of the
motor protection is Ip44.
ATTENTION!
The fan should not be operated outside the specified temperature range (from +1 °C to +40 °C).
It is forbidden to install the fan in the same ventilation line with the smoke injector pipe from
devices with fuel burners.
ATTENTION!
• All work on installation and connection of fans should be carried out only with the mains voltage
removed.
• The fans shall be connected by electricians who have a special permit for the work performed.
Means for disconnecting from the mains supply should be built into the fixed wiring, in
accordance with the installation regulations. The disconnecting device should
disconnect all poles. The grounding conductor should not break.
• The device is not intended for use by persons (including children) with reduced physical,
mental capacity, or mental abilities or lack of experience or knowledge, unless they are
supervised or instructed to use the device by a person responsible for their safety. Children
should be supervised to ensure that they do not play with the device.
2

C
D
B
A
Figure 1
Table 1.
Type
Dimensions, m Weight, kg,
no more
A B C D
CECYL 100
371 173 216 99 2,3
CECYL 125
291 173 216 124 2,3
CECYL 150 323 190 238 149 3,3
CECYL 160 340 190 238 159 3,3
CECYL 200 376 250 266 198,5 4,0
CECYL 250 450 290 323 250 7,5
CECYL 315 446 324 420 312 11,5
3
Installation example
CECYL main dimensional characteristics
The fans are manufactured by Dalap company, in accordance with TU 28.25.20-008-96059883-2020,
current norms and standards. The fans are designed to be connected to an alternating current with a
voltage of 220-240V and a frequency of 50Hz. They have a motor on ball bearings (rolling bearings).
Dalap CECYL fan is available in seven standard sizes, depending on the installation diameter of the
casing. Fan designation, their appearance, overall and mounting dimensions are shown in Figure 1 and
Table 1.

Model Speed
CECYL 100 L2
L1 220~240V/50Hz 25
23
2500
1850
250
180
190
110
40
31
CECYL 125 L2
L1 220~240V/50Hz 29
25
2450
1800
355
240
190
110
39
30
CECYL 150 L2
L1 220~240V/50Hz 50
42
2600
2000
570
415
305
225
49
40
CECYL 160 L2
L1 220~240V/50Hz 50
42
2600
2000
570
415
305
225
49
40
CECYL 200 L2
L1 220~240V/50Hz 105
75
2600
2250
1100
850
350
300
58
50
CECYL 250 L2
L1 220~240V/50Hz 180
134
2550
1985
1560
1150
510
370
60
52
CECYL 315 L2
L1 220~240V/50Hz 285
215
2350
1900
2060
1650
715
480
69
61
Type of current – alternating, single-phase. Table 2.
4
CECYL main specification
Voltage /
Frequency
Power
(W)
Speed
(RPM)
Performance
(m3/h)
Air
pressure
(Pa)
Noise
level
(dBА)
CECYL fan installation
Installation
CECYL fan is suitable for the following types of installation:
- on a wall, a ceiling, or a floor;
- for self-assembly or as a part of air ducts;
- for horizontal and vertical installation.
For horizontal installation, the length of the air duct should be at
least 0.5m; for vertical installation, a ventilation hood should be
installed to prevent moisture from entering the device.
In case of non-compliance with
these requirements, the IP44
degree will not be provided.
It is prohibited to install and to use CECYL fan with
the terminal box facing down.
The level of inclination of the CECYL fan terminal box
should not be lower than the central axis.

1
45
N
(Neutral)
Figure 2a
Figure 3a
Figure 2b
N
(Neutral)
5
CECYL fan installation instructions:
1. Disconnect power supply.
2. Open the clamp by pulling the tab upwards.
3. Remove the fan casing from the base.
4. Attach the base to the mounting surface and mark the screw hole.
5. Drill holes; fix the fan base to the mounting surface with screws.
6. Install the body by tightly connecting the clamp
Installation instructions for the speed switch button:
1. Remove the cover with a wide flat screwdriver. To do this, insert a screwdriver into the groove of the plug on the
terminal box casing and knock out the plug with a sharp blow.
2. Install the button in the drilled hole.
3. Connect, according to the diagram using RPI-M(n) 1.5-6.3 connectors (3 pcs., not included). To connect, it is
necessary to bring the wires into flat connectors and clamp them with a crimping tool. You can also connect the
contacts in other safe ways: by twisting, soldering, and welding.
ATTENTION! By installing the speed switch button, the protection level is reduced to Ip42.
Wiring connection diagram for models with flange
diameter 100-200 (for fans without speed switch
button)
Wiring connection diagram for models with flange
diameter 100-200 (for fans with speed switch button)
CECYL wiring connection diagram
blue
black
white
(High speed)
(Low speed)
blue
black
white

N
(Neutral)
Figure 3a
Figure 3b
N
(Neutral)
6
Wiring connection diagram for models with flange
diameter 250, 315 (for fans without speed switch
button)
Wiring connection diagram for models with flange
diameter 250, 315 (for fans with speed switch
button)
blue
black
white
(High speed)
(Low speed)
yellow
blue
black
white
yellow
Connecting the fan to the mains
The fan has two speeds. Depending on the required fan performance, the phase of the power supply is switched
between the terminals:
For models with flange diameter from 100mm to 315mm
• L1 Low Speed
• L2 High Speed
When setting a high fan speed, depending on the model, it is necessary to connect the fan as follows: L2 (phase of the
supply network), N (neutral of the supply network), protective earth (for models 250, 315).
When setting a low fan speed, it is necessary to switch the phase of the supply network from terminal blocks L2 (phase)
to terminal blocks L1 (phase), connection N (neutral of the supply network), the protective ground remains unchanged
(for models 250, 315).
ATTENTION! In order to avoid damage to the fan, do not simultaneously connect a phase of the supply mains to
terminals L1 and L2.
ATTENTION! All work on installation and connection of fans should be carried out only with the mains voltage
removed.
The fans shall be connected by electricians who have a special permit for the work performed.
Means for disconnecting from the mains supply should be built into the fixed wiring, in accordance with the installation
regulations. The disconnecting device should disconnect all poles. The grounding conductor should not break.
The fan and auxiliary control equipment should be isolated from the power supply during installation and/or
maintenance.
The equipment should be grounded (for 250, 315 models).
Please remove the cover from the terminal box, study the wiring diagram (Fig. 2 or Fig. 3), and make the necessary
connections. Check whether a ground connection exists (for 250, 315 models).
After finishing the connection work and checking the connections to the terminal box, move the cover and make sure it
is fixed.
Installation: The length of the well-established pipeline from the fan should be at least 1000 mm. A shorter pipeline
should be equipped with a rigid lid/grid that complies with EN ISO 13857.
When connecting CECYL fan with IP44, it is required to pass a network cable with a diameter of at least 4 mm through a
cable gland.
The cable gland is designed for sealed input-output of cables from wires in switchboard enclosures.
The compression nut design has special locking notches to prevent self-loosening. A protective diaphragm prevents
dust from entering the enclosure and achieves a degree of protection IP44 and above.

Malfunction Probable cause Troubleshooting method
7
When connected to the mains, the
fan does not rotate, it does not
respond to controls.
Low air consumption.
Increased noise or vibration.
Burning odor.
Power supply is not connected.
Malfunction in the internal connection
Clogged ventilation system.
Impeller is clogged.
Fan is not secured or it is incorrectly
mounted.
Clogged ventilation system.
The mains wire is connected to L1 and L2.
It was necessary to address a specialist.
Clean the ventilation system.
Clean the impeller.
Eliminate the installation error.
Clean the ventilation system.
Connect the wires correctly
ATTENTION! The fan and auxiliary control equipment should be isolated from the power supply during
installation and/or maintenance. The equipment should be grounded (for 250, 315 models).
Storage and transportation rules
It is necessary to store the fan only in the manufacturer’s packaging in a ventilated room at a
temperature from +5°C to +40°C and a relative humidity of no more than 70% (at T = 25°C). Shelf life is 2
years from the date of manufacture. Products shall be transported by any type of transport, provided
that consumer or shipping containers are protected from the direct impact of atmospheric precipitation,
from the absence of displacement of transport places during transportation, from the absence of mutual
shocks during transportation and while ensuring the safety of the fans. Transportation shall be carried
out, in accordance with the rules in force for this mode of transport.
Disposal
This appliance is marked, in accordance with European Directive 2012/19/EU on the disposal of
old electrical and electronic equipment (waste electrical and electronic equipment – WEEE). This
Directive defines the EU-wide rules for the collection and disposal of old appliances.
At the end of their service life or failure of the fan or its components, they should be disposed of.
Disposal shall be carried out separately, according to material groups: plastic elements, metal
fasteners.
ATTENTION!
Dismantling and disassembly of the fan should be carried out by qualified specialists with a
complete disconnection from the power supply
Maintenance
• Disconnect the fan from the mains;
• Dismantle the fan by disconnecting the middle unit and removing it from the installation site;
• Remove dust from impeller blades using a soft dry brush or cloth;
• Clean the fan impeller blades using a detergent solution;
• Wipe all plastic parts with a soft cloth dampened with soapy water;
• Wipe all surfaces dry;
• Assemble the fan and reinstall;
• Cleaning is recommended every 6 months.
ATTENTION!
Do not get the cleaning solution on the electric motor!
Water entering the fan is not allowed!

GUARANTEE
DALAP assures the efficient operation of the device in accordance with tha technical-exploitation conditions attached
hereto. The guarantee covers constructional and material defects of devices. The following guarantee is valid at the
territory of the European Union.
The guarantee covers free reparation within 24 months from the date of a purchase.
The following guarantee does not exclude, limit, nor suspend the powers of a buyer.
Exclusions:
The guarantee does not cover defects arising as a result of:
źmechanical forces,dirt,
źtransformations,
źconstructional changes,
źactivities connected with conservation and cleaning of the devices,
źaccidents,
źnatural disasters, chemical and atmospherical factors,
źimproper storing,
źunauthorized reparation,
źimproper installation of the device.
Guarantee claims shall be refused thereat.
The realization of a client´s rights shall happen by the reparation or free replacement of the defective device, removal
of other defects of the device, the term „reparation” does not cover the activities provided in the manual (conservation,
cleaning), that the user is bound to on his own.
The complaint shall be considered within 30 days from the day the product is delivered to the producer or the seller.
Decisions made by DALAP GmbH connected with the guarantee claims are considered final.
CAUTION!
Connecting with the electric network should be carried out by professional electrician with SEP qualifications! Before
the conservation, a fan should be disconnected from the electric network! The electrical installation should have a
switch with the distance between contacts of all the poles less then 3 mm. The complete grounding system of a fan is
required. The inverse flow of gases to the room from open chimney hole or other devices with an open fire have to be
avoided, fans should not be used in rooms having increased humidity and as anti-explosion fans. The producer
reserves the right to introduce constructional changes, arising of the technical progress.
8
This manual suits for next models
7
Table of contents
Other dalap Fan manuals