manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Danfoss
  6. •
  7. Air Compressor
  8. •
  9. Danfoss DSF485A4ABA User manual

Danfoss DSF485A4ABA User manual

Danfoss scroll compressors
DSF
Instructions
2 | AN309640488445en-000201 - 8510290P02B © Danfoss | DCS (CC) | 2020.10
The compressor must only be used for its
designed purpose(s) and within its scope of
application (refer to «operating limits»).
Consult Application guidelines and datasheet
available from cc.danfoss.com
Under all circumstances,
the EN378 (or other
applicable local safety
regulation) requirements
must be fulfilled.
The compressor is delivered under
nitrogen gas pressure (between 0.3 and
0.7 bar) and hence cannot be connected
as is; refer to the «assembly» section for
further details.
The compressor must be
handled with caution in the
vertical position (maximum
offset from the vertical : 15°)
Installation and servicing of the compressor by
qualified personnel only. Follow these instructions and
sound refrigeration engineering practice relating to
installation, commissioning, maintenance and service.
A: Model number
B: Serial number
C: Refrigerant
D: Supply voltage, Starting current & Maximum operating current
E: Housing service pressure
F: Factory charged lubricant
1 – Introduction
These instructions pertain to the Danfoss scroll compressors DSF scroll com-
pressors used for air-conditioning systems. They provide necessary informa-
tion regarding safety and proper usage of this product.
DSF Large Operating map
3 - Operating map
2- Nameplate
Model no: DSF485A4ABA
Serial no: ZQ1109974321
MADE IN FRANCE
M400V 3~50Hz
LR 343 A MAX OPER.92 A
Thermally protected system
P.E.D.
Marking
PS
TS MAX
TS MIN
Volume
Lubricant: 185 SL
Refrigerant: R32
PROTECTED BY DOMESTIC AND FOREIGN PATENTS
2019
LP Side
31,2 bar
51,0 °C
-35,0 °C
27,5 L
48,7 bar
150,0 °C
-35,0 °C
3,9 L
HP Side
0038
1234799011
A
D
E
F
B
C
Condensing temperature (°C)
Evaporating temperature (°C)
5
10
15
20
25
30
35
40
45
50
55
60
65
70
-35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30
SH: 10 K
SH: 5 K
Instructions
8510290P02B - AN309640488445en-000201 | 3
© Danfoss | DCS (CC) | 2020.10
These Danfoss scroll compressor motors are protected by an external
module protecting against phase loss/reversal, overheating and high
current draw.
DSF270, DSF325
MPM
S
SSH
CCSS
LPS
UNIT
CONTROLLER
KM
DGT
CB
4 - Electrical connections details
DSF485, DSF530
Legend:
Fuses .........................................................................................F1
Compressor contactor........................................................ KM
High pressure safety switch................................................ HP
Discharge gas thermistor
(embedded in compressors)............................................ DGT
Surface Sump Heater......................................................... SSH
Compressor motor .................................................................M
Motor Protection Module ...............................................MPM
Thermistor chain...................................................................... S
Safety pressure switch........................................................LPS
Thermal magnetic motor circuit breaker ....................... CB
SSH
CONTROL
CIRCUIT
LPS
UNIT
CONTROLLER
SEPARATE
SUPPLY
KM
DGT
MPM
S
CB
These Danfoss scroll compressor motors are protected by an external
module protecting against phase loss/reversal, overheating and high
current draw.
Instructions
4 | AN309640488445en-000201 - 8510290P02B © Danfoss | DCS (CC) | 2020.10
5 – Handling and storage
• Handle the compressor with care. Use the
dedicated handles in the packaging. Use the
compressor lifting lug and use appropriate and
safe lifting equipment.
• Store and transport the compressor in an
upright position.
• Store the compressor between Ts min and Ts
max values for LP side indicated on compressor
nameplate.
• Don’t expose the compressor and the
packaging to rain or corrosive atmosphere.
6 – Safety measures before assembly
Never use the compressor in a flammable
atmosphere.
• Check before assembly that the compressor
does not show any obvious signs of
deterioration that could have occurred during
inappropriate transportation, handling or
storage.
• The compressor ambient temperature may not
exceed Ts max value for LP side indicated on
compressor nameplate during off-cycle.
• Mount the compressor on a horizontal flat
surface with less than 3° slope.
• Verify that the power supply corresponds to
the compressor motor characteristics (see
nameplate).
• Use clean and dehydrated refrigeration-grade
copper tubes and silver alloy brazing material.
• Use clean and dehydrated system components.
• The piping connected to the compressor must be
flexible in 3 dimensions to dampen vibrations.
7 – Assembly
• The compressor must be mounted on rails or
chassisaccordingto Danfoss recommendations
described in related product guidelines (type
of spacer, tightening torques).
• Slowly release the nitrogen holding charge
through the schrader port.
• Remove the gaskets when brazing rotolock
connectors.
• Always use new gaskets for assembly.
• Connect the compressor to the system as soon
as possible to avoid oil contamination from
ambient moisture.
• Avoid material entering into the system while
cutting tubes. Never drill holes where burrs
cannot be removed.
• Braze with great care using state-of-the-art
technique and vent piping with nitrogen gas
flow.
• Connect the required safety and control
devices. When the schrader port is used for
this, remove the internal valve.
• Do not exceed the maximum tightening
torque for rotolock connections:145 Nm.
8 – Leak detection
Never pressurize the circuit with oxygen or dry
air. This could cause fire or explosion.
• Pressurize the system on HP side first and then
on LP side. Never let the pressure on LP side
exceed the pressure on HP side with more than
5 bar. Such pressure difference could cause
internal compressor damage.
• Do not use dye for leak detection.
• Perform a leak detection test on the complete
system.
• The test pressure must not exceed 1.1 x PS
value for LP side and HP side indicated on
compressor nameplate.
• When a leak is discovered, repair the leak and
repeat the leak detection.
9 – Vacuum dehydration
• Never use the compressor to evacuate the
system.
• Connect a vacuum pump to both the LP & HP
sides.
• Pull down the system under a vacuum of 500
µm Hg (0.67 mbar) absolute.
• Do not use a megohmmeter nor apply power
to the compressor while it is under vacuum as
this may cause internal damage.
10 – Electrical connections
• Switch off and isolate the main power supply.
See overleaf for wiring details.
• All electrical components must be selected
as per local standards and compressor
requirements.
• Refer to section 4 for electrical connections
details.
• The Danfoss scroll compressors only works
correctly in one rotation direction. Line phases
L1, L2, L3 must absolutely be connected
to compressor terminals T1, T2, T3 to avoid
reverse rotation.
• Electrical power is connected to the
compressor terminals by M5 studs and nuts
. Use appropriate ring terminals, fasten with
3Nm torque.
• The compressor must be connected to earth
with the 5 mm earth terminal screw. The
maximum torque is 4Nm.
11 – Filling the system
• Keep the compressor switched off.
• Fill the refrigerant in liquid phase into the
condenser or liquid receiver. The charge must
be as close as possible to the nominal system
charge to avoid low pressure operation and
excessive superheat. Never let the pressure
on LP side exceed the pressure on HP side
with more than 5 bar. Such pressure difference
could cause internal compressor damage.
• Keep the refrigerant charge below the
indicated charge limits if possible. Above this
limit; protect the compressor against liquid
flood-back with a pump-down cycle or suction
line accumulator.
• Never leave the filling cylinder connected to
the circuit.
Compressor models Refrigerant charge
limit (kg)
DSF270, DSF325 15
DSF485, DSF530 17
12 – Verification before commissioning
Use safety devices such as safety pressure
switch and mechanical relief valve in compliance
with both generally and locally applicable
regulations and safety standards. Ensure that
they are operational and properly set.
Check that the settings of high-pressure
switches and relief valves don’t exceed the
maximum service pressure of any system
component.
• A low-pressure switch is recommended to
avoid vacuum operation. Minimum setting for
1.7 bar g.
• Verify that all electrical connections are
properly fastened and in compliance with local
regulations.
• When a crankcase heater is required, it must be
energized at least 12 hours before initial start-
up and start-up after prolonged shutdown for
belt type crankcase heaters (6 hours for surface
sump heaters).
13 – Start-up
Never operate the compressor without the
electrical box cover fitted.
• Never start the compressor when no refrigerant
is charged.
• All service valves must be in the open position.
• Balance the HP/LP pressure.
• Energize the compressor.It muststartpromptly.
If the compressor does not start, check wiring
conformity and voltage on terminals.
• Eventual reverse rotation can be detected by
following phenomena; the compressor doesn’t
build up pressure, it has abnormally high sound
level and abnormally low power consumption.
In such case, shut down the compressor
immediately and connect the phases to
their proper terminals. DSF compressors are
protected against reverse rotation by the
external electronic protection module. They
will shut off automatically.
• If the internal pressure relief valve is opened
the compressor sump will be warm and
the compressor will trip out on the motor
protector.
14 – Check with running compressor
• Check current draw and voltage.
• Check suction superheat to reduce risk of
slugging.
• Observe the oil level in the sight glass for about
60 minutes to ensure proper oil return to the
compressor.
• Respect the operating limits.
• Check all tubes for abnormal vibration.
Movements in excess of 1.5 mm require
corrective measures such as tube brackets.
• When needed, additional refrigerant in liquid
phase may be added in the low-pressure side
as far as possible from the compressor. The
compressor must be operating during this
process.
• Do not overcharge the system.
• Never release refrigerant to atmosphere.
• For reversible systems, ensure that the 4-way
valve does not reverse when the compressor
is stopped due to heating or cooling demand
(stop on thermostat)
• Before leaving the installation site, carry out
a general installation inspection regarding
cleanliness, noise and leak detection.
• Record type and amount of refrigerant charge
as well as operating conditions as a reference
for future inspections.
15 – Maintenance
Internal pressure and surface temperature
are dangerous and may cause permanent injury.
Maintenance operators and installers require
appropriate skills and tools. Tubing temperature
may exceed 100°C and can cause severe burns.
Instructions
8510290P02B - AN309640488445en-000201 | 5
© Danfoss | DCS (CC) | 2020.10
Ensure that periodic service inspections to
ensure system reliability and as required by local
regulations are performed.
To prevent system related compressor problems,
following periodic maintenance is recommended:
• Verify that safety devices are operational and
properly set.
• Ensure that the system is leak tight.
• Check the compressor current draw.
• Confirm that the system is operating in a way
consistent with previous maintenance records
and ambient conditions.
• Check that all electrical connections are still
adequately fastened.
• Keep the compressor clean and verify
the absence of rust and oxidation on the
compressor shell, tubes and electrical
connections.
16 - Warranty
Always transmit the model number and serial
number with any claim filed regarding this
product.
The product warranty may be void in following
cases:
• Absence of nameplate.
• External modifications; in particular, drilling,
welding, broken feet and shock marks.
• Compressor opened or returned unsealed.
• Rust, water or leak detection dye inside the
compressor.
• Use of a refrigerant or lubricant not approved
by Danfoss.
• Any deviation from recommended instructions
pertaining to installation, application or
maintenance.
• Use in mobile applications.
• Use in explosive atmospheric environment.
• No model number or serial number transmitted
with the warranty claim.
The compressor is not designed to withstand
natural disasters such as earthquakes, cyclones,
floods…. or extreme events such as fires, terrorist
attacks, military bombardments, or explosions of
any kind.
Danfoss Commercial Compressor is not liable
for any malfunction of its product resulting from
such events
17 – Disposal
Danfoss recommends that compressors
and compressor oil should be recycled
by a suitable company at its site.
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This
also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trade-
marks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

This manual suits for next models

1

Other Danfoss Air Compressor manuals

Danfoss AKC 25H1 User manual

Danfoss

Danfoss AKC 25H1 User manual

Danfoss VZH028 Instruction Manual

Danfoss

Danfoss VZH028 Instruction Manual

Danfoss VZH028 User manual

Danfoss

Danfoss VZH028 User manual

Danfoss VLZ065 User manual

Danfoss

Danfoss VLZ065 User manual

Danfoss BOCK UL-HGX24e CO2 LT User manual

Danfoss

Danfoss BOCK UL-HGX24e CO2 LT User manual

Danfoss DSH Series Instruction Manual

Danfoss

Danfoss DSH Series Instruction Manual

Danfoss Turbocor TTS Series User guide

Danfoss

Danfoss Turbocor TTS Series User guide

Danfoss Maneurop VTZ Series User manual

Danfoss

Danfoss Maneurop VTZ Series User manual

Danfoss DSH Series User manual

Danfoss

Danfoss DSH Series User manual

Danfoss MLZ Instruction Manual

Danfoss

Danfoss MLZ Instruction Manual

Danfoss BOCK UL-HGX12 CO2 T User manual

Danfoss

Danfoss BOCK UL-HGX12 CO2 T User manual

Danfoss MT User manual

Danfoss

Danfoss MT User manual

Danfoss Optyma OP-MCGC003TLA00G User manual

Danfoss

Danfoss Optyma OP-MCGC003TLA00G User manual

Danfoss GLT80TDC Instruction Manual

Danfoss

Danfoss GLT80TDC Instruction Manual

Danfoss Performer S Series User manual

Danfoss

Danfoss Performer S Series User manual

Danfoss Performer SZ R407C User manual

Danfoss

Danfoss Performer SZ R407C User manual

Danfoss GD30FDC User manual

Danfoss

Danfoss GD30FDC User manual

Danfoss H Series User manual

Danfoss

Danfoss H Series User manual

Danfoss DCJ Series User manual

Danfoss

Danfoss DCJ Series User manual

Danfoss VCH115 User guide

Danfoss

Danfoss VCH115 User guide

Danfoss DSF User manual

Danfoss

Danfoss DSF User manual

Danfoss Turbocor TT-300 User manual

Danfoss

Danfoss Turbocor TT-300 User manual

Danfoss DSG Series User manual

Danfoss

Danfoss DSG Series User manual

Danfoss VZH052 Series User manual

Danfoss

Danfoss VZH052 Series User manual

Popular Air Compressor manuals by other brands

Scheppach HC25Si Translation of original instruction manual

Scheppach

Scheppach HC25Si Translation of original instruction manual

Clarke SHHH 2 Operating & maintenance instructions

Clarke

Clarke SHHH 2 Operating & maintenance instructions

Daikin DWSC 050 Installation, operation and maintenance manual

Daikin

Daikin DWSC 050 Installation, operation and maintenance manual

Scheppach HC06 Translation of original instruction manual

Scheppach

Scheppach HC06 Translation of original instruction manual

F.F. Group AC-B 90/4MC PRO Original instructions

F.F. Group

F.F. Group AC-B 90/4MC PRO Original instructions

California Air Tools 20020 owner's manual

California Air Tools

California Air Tools 20020 owner's manual

Jefferson JEFC100V10B Series user manual

Jefferson

Jefferson JEFC100V10B Series user manual

Ryobi RC-1506N Owner's operating manual

Ryobi

Ryobi RC-1506N Owner's operating manual

Husky H150PL Operator's manual

Husky

Husky H150PL Operator's manual

Compact TRANS-TECH Operation manual

Compact

Compact TRANS-TECH Operation manual

Grizzly H3272 instruction manual

Grizzly

Grizzly H3272 instruction manual

American Eagle V230 STANDARD OPERATION & PARTS MANUAL

American Eagle

American Eagle V230 STANDARD OPERATION & PARTS MANUAL

MasterCraft 58-7922-8 instruction manual

MasterCraft

MasterCraft 58-7922-8 instruction manual

Chicago Pneumatic QRS 20 instruction manual

Chicago Pneumatic

Chicago Pneumatic QRS 20 instruction manual

Clarke PP10ND operating & maintenance manual

Clarke

Clarke PP10ND operating & maintenance manual

Champion A Series Operating and service manual

Champion

Champion A Series Operating and service manual

Maximum 058-1980-4 instruction manual

Maximum

Maximum 058-1980-4 instruction manual

Emerson Copeland YA K1 Series manual

Emerson

Emerson Copeland YA K1 Series manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.