manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Danfoss
  6. •
  7. Compressor
  8. •
  9. Danfoss MLZ Series User manual

Danfoss MLZ Series User manual

© Copyright Danfoss | Commercial Compressors | 2014.12FRCC.PI.014.A4.02 - December 2014
MLZ/MLM compressors
Instructions
A
B
C
D
E
F
G
H
I
J
Group 2
Quick connect spade terminals
P terminal box type
push
push
push
10
5
15
20
25
30
35
40
45
50
55
60
65
-35 -30 -25 -20 -15 -10 -5 0 5 10 15
Evap. Temp. (°C)
Cond. Temp. (°C)
RGT: 20°C
SH 10K
Cond. temp. (°C)
Evap. temp. (°C)
65
60
55
50
45
40
35
30
25
20
15
10
-30 -25 -20 -15 -10 -5 0 5 10 15
SH 10K
RGT 20°C
MLZ076
Cond. temp. (°C)
Evap. temp. (°C)
65
60
55
50
45
40
35
30
25
20
15
10
-30 -25 -20 -15 -10 -5 0 5 10 15
SH 10K
RGT 20°C
MLZ076
RGT: 25°C
10
15
20
25
30
35
40
45
50
55
60
65
70
-35 -30 -25 -20 -15 -10 -5 0 5 10 15
Evap. Temp. (°C)
Cond. Temp. (°C)
SH: 11K
15
20
25
30
35
40
45
50
55
60
65
70
75
-20 -15 -10 -5 0 5 10 15 20
Evap. Temp. (°C)
Cond. Temp. (°C)
SH: 11K
MLZ - R404A / R507
MLZ - R407A
MLZ - R407F
MLZ / MLM - R22 / R417A
MLZ - R134a
Operating limits
Electrical connections
NL₁
Run capacitor
Thermostat
C
SR
IOL
N L₁
Thermostat
Start capacitor
Start Relay
5
2
1
15 kΩ -1 w
C
SR
Run capacitor
PSC wiring
CSR wiring
Single phase
C
T₁
Ring connect screw terminals
C terminal box type
S
T₂
R
T₃
Quick connect spade terminals
T and P terminal box type
Ring connect screw terminals
Q and C terminal box type
When MLM compressors are used with R417A,
the factory charged oil must be replaced by PVE
oil 320HV (120Z5034).
Models Brazed
connection size Rotolock
connection size
MLZ/MLM
015-026 Suction 3/4"
Discharge 1/2" Suction 1"1/4
Discharge 1"
MLZ/MLM
030-045 Suction 7/8"
Discharge 1/2" Suct. 1"1/4
Discharge 1"
MLZ/MLM
048 Suction 7/8"
Discharge 3/4" Suction 1"1/4
Discharge 1" 1/4
MLZ/MLM
058-076 Suction 1"1/8
Discharge 7/8" Suction 1"3/4
Discharge 1"1/4
Installation and servicing of the compressor by qualied personnel only.
Follow these instructions and sound refrigeration engineering practice
relating to installation, commissioning, maintenance and service.
The compressor must only be
used for its designed purpose(s)
and within its scope of applica-
tion (refer to «operating limits»).
Consult Application guidelines
and datasheet available from
cc.danfoss.com
Never operate
compressor wit-
hout terminal box
cover in place and
secured.
Under all circumstances, the EN378
(or other applicable local safety regu-
lation) requirements must be fullled.
Wear protective goggles and work
gloves.
The compressor is delivered under nitrogen gas pres-
sure (between 0.3 and 0.4 bar / 4 and 6 psi). Do not di-
sassemble bolts, plugs, ttings, etc... unless all pressure
has been relieved from the compressor.
The compressor must be handled with
caution in the vertical position (maxi-
mum oset from the vertical : 15°).
A: Model number
B: Technical number
C: Serial Number
D: Internal protection
E: Supply voltage range
F: Run capacitor
G: Locked rotor current
Maximum operating current
H: Lubricant type and nominal charge
I: Approved Refrigerant
J: Manufacturing year
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alterations can be made without subsequential changes being necessary in specications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
© Copyright Danfoss | Commercial Compressors | 2014.12FRCC.PI.014.A4.02 - December 2014
1 – Introduction
These instructions pertain to the MLZ / MLM scroll
compressorsusedforrefrigerationsystems.Theyprovide
necessary information regarding safety and proper
usage of this product.
2 – Handling and storage
• Handle the compressor with care. Use the dedicated
handles in the packaging. Use the compressor lifting
lug and use appropriate and safe lifting equipment.
•
Store and transport the compressor in an upright position.
• Store the compressor between -35°C and 70°C /
-31°F and 158°F.
• Don’t expose the compressor and the packaging
to rain or corrosive atmosphere.
3 – Safety measures before assembly
Never use the compressor in a flammable atmosphere.
• Mount the compressor on a horizontal at surface
with less than 7° slope.
• Verify that the power supply corresponds to the
compressor motor characteristics (see nameplate).
•
When installing a compressor for R404A,
R507 R407A, R407F or R134a, use equipment
specically reserved for HFC refrigerants which
was never used for CFC or HCFC refrigerants.
• Use clean and dehydrated refrigeration-grade
copper tubes and silver alloy brazing material.
• Use clean and dehydrated system components.
• The piping connected to the compressor must be
exible in 3 dimensions to dampen vibrations.
• The compressor must always be mounted with the
rubber grommets supplied with the compressor.
4 – Assembly
• Slowly release the nitrogen holding charge
through discharge and suction ports.
•
Connect the compressor to the system as soon as possible
to avoid oil contamination from ambient moisture.
• Avoid material entering into the system while
cutting tubes. Never drill holes where burrs
cannot be removed.
• Braze with great care using state-of-the-art
technique and vent piping with nitrogen gas ow.
• Connect the required safety and control devices.
When the schrader port, if any, is used for this,
remove the internal valve.
• For parallel assemblies of the compressors in
version C8, contact Danfoss.
5 – Leak detection
Never pressurize the circuit with oxygen or dry
air. This could cause re or explosion.
• Do not use leak detection dye.
• Perform a leak detection test on the complete system.
• The low side test pressure must not exceed 31 bar
/450 psi.
• When a leak is discovered, repair the leak and
repeat the leak detection.
6 – Vacuum dehydration
• Never use the compressor to evacuate the system.
• Connect a vacuum pump to both the LP & HP sides.
• Pull down the system under a vacuum of
500 µm Hg (0.67 mbar) / 0.02 inch Hg absolute.
• Do not use a megohmmeter nor apply power to
the compressor while it is under vacuum as this
may cause internal damage.
7 – Electrical connections
• Switch o and isolate the main power supply.
• All electrical components must be selected as per
local standards and compressor requirements.
•
Refer to electrical connections details. For three
phase applications, the terminals are labeled T1, T2,
and T3. For single-phase applications the terminals
are labeled C (common), S (start), and R (run).
• Danfoss scroll compressors will only compress gas
while rotating counter-clockwise (when viewed
from the compressor top). Since single-phase
motors will start and run in only one direction,
reverse rotation is not a major consideration.
Three-phase motors, however, will start and
run in either direction, depending on the phase
angles of the supplied power. Care must be taken
during installation to ensure that the compressor
operates in the correct direction.
• Use ø 4.8 mm / #10 - 32 screws and ¼” ring terminals
for the power connection with ring connect screw
terminal (C type). Fasten with 3 Nm torque.
• Use ø 6.3 mm tabs for quick connect spade
terminals (P type).
• Use a self tapping screw to connect the
compressor to earth.
8 – Filling the system
• Keep the compressor switched o.
• Keep the refrigerant charge below the indicated
charge limits if possible. Above this limit; protect the
compressor against liquid ood-back with a pump-
down cycle or suction line accumulator.
•
Never leave the lling cylinder connected to the circuit.
Compressor models
Refrigerant charge limit
MLZ / MLM015-019-021-026 3.6 kg / 8 lb
MLZ / MLM030-038-045-048 5.4 kg / 12 lb
MLZ / MLM058-066-076 7.2 kg / 16 lb
9 – Verification before commissioning
Use safety devices such as safety pressure switch
and mechanical relief valve in compliance with both
generally and locally applicable regulations and
safety standards. Ensure that they are operational
and properly set.
Check that the settings of high-pressure
switches don’t exceed the maximum service
pressure of any system component.
• A low-pressure switch is recommended to avoid
low pressure operation.
Minimum setting for R22 1.5 bar (absolute) / 22 psia
Minimum setting for R404A
2.8 bar (absolute) / 41 psia
Minimum setting for R407A
1.7 bar (absolute) / 25 psia
Minimum setting for R407F
1.9 bar (absolute) / 28 psia
Minimum setting for R134a
1.45 bar (absolute) / 21 psia
•
Verify that all electrical connections are properly
fastened and in compliance with local regulations.
• When a crankcase heater is required, it must be
energized at least 24 hours before initial start-up
and start-up after prolonged shutdown.
• Please respect a 90 Nm ± 20 Nm for tightening
torque of all rotolock nut.
10 – Start-up
•
Never start the compressor when no refrigerant is charged.
• Do not provide any power to the compresor
unless suction and discharge service valves are
open, if installed.
• Energize the compressor. It must start promptly.
If the compressor does not start, check wiring
conformity and voltage on terminals.
• Eventual reverse rotation can be detected by
following phenomena; the excessive noise, no
pressure dierential between suction and discharge,
and line warming rather than immediate cooling.
A service technician should be present at initial
start-up to verify that supply power is properly
phased and that the compressor is rotating in the
correct direction. MLZ / MLM Scroll compressors are
designed to operate for a maximum of 150 hours
in reverse, but as a reverse rotation situation can
go unnoticed for longer periods, phase monitors
are recommended. For compressors MLZ / MLM
048 and larger, phase monitors are required for
all applications. Danfoss recommends phase
protection for residential compressors.
•
If the internal overload protector trips out, it must cool
down to 60°C / 140°F to reset. Depending on ambient
temperature, this may take up to several hours.
11 – Check with running compressor
Check current draw and voltage. Measurement of
amps and volts during running conditions must be
taken at other points in the power supply, not in the
compressor electrical box.
• Check suction superheat to reduce risk of slugging.
• Observe the oil level in the sight glass (if provided)
for about 60 minutes to ensure proper oil return to
the compressor.
• Respect the operating limits.
• Check all tubes for abnormal vibration.
Movements in excess of 1.5 mm / 0.06 in require
corrective measures such as tube brackets.
• When needed, additional refrigerant in liquid phase
may be added in the low-pressure side as far as
possible from the compressor. The compressor must
be operating during this process.
• Do not overcharge the system.
• Never release refrigerant to atmosphere.
• Before leaving the installation site, carry out
a general installation inspection regarding
cleanliness, noise and leak detection.
• Record type and amount of refrigerant charge
as well as operating conditions as a reference for
future inspections.
12 – Maintenance
Internal pressure and surface temperature
are dangerous and may cause permanent injury.
Maintenance operators and installers require
appropriate skills and tools.Tubing temperature may
exceed 100°C / 212°F and can cause severe burns.
Ensure that periodic service inspections to
ensure system reliability and as required by local
regulations are performed.
To prevent system related compressor problems,
following periodic maintenance is recommended:
• Verify that safety devices are operational and
properly set.
• Ensure that the system is leak tight.
• Check the compressor current draw.
• Conrm that the system is operating in a way
consistent with previous maintenance records
and ambient conditions.
• Check that all electrical connections are still
adequately fastened.
• Keep the compressor clean and verify the absence
of rust and oxidation on the compressor shell,
tubes and electrical connections.
• Acid / moisture content in system and oil should
be checked regularly.
13 - Warranty
Always transmit the model number and serial
number with any claim led regarding this product.
The product warranty may be void in following
cases:
• Absence of nameplate.
• External modications; in particular, drilling,
welding, broken feet and shock marks.
• Compressor opened or returned unsealed.
•
Rust, water or leak detection dye inside the compressor.
•
Use of a refrigerant or lubricant not approved by Danfoss.
•
Any deviation from recommended instructions
pertaining to installation, application or maintenance.
• Use in mobile applications.
• Use in explosive atmospheric environment.
• No model number or serial number transmitted
with the warranty claim.
14 – Disposal
Danfoss recommends that compressors
and compressor oil should be recycled by
a suitable company at its site.

Other manuals for MLZ Series

3

This manual suits for next models

15

Other Danfoss Compressor manuals

Danfoss Turbocor User manual

Danfoss

Danfoss Turbocor User manual

Danfoss Turbocor TT Series User manual

Danfoss

Danfoss Turbocor TT Series User manual

Danfoss Maneurop NTZ048 Instruction Manual

Danfoss

Danfoss Maneurop NTZ048 Instruction Manual

Danfoss 101N0800 User manual

Danfoss

Danfoss 101N0800 User manual

Danfoss Turbocor TTS Series User manual

Danfoss

Danfoss Turbocor TTS Series User manual

Danfoss WSH 090 Instruction Manual

Danfoss

Danfoss WSH 090 Instruction Manual

Danfoss MPZ Series User manual

Danfoss

Danfoss MPZ Series User manual

Danfoss Performer HHP015T4LP6 User manual

Danfoss

Danfoss Performer HHP015T4LP6 User manual

Danfoss MLM116 Instruction Manual

Danfoss

Danfoss MLM116 Instruction Manual

Popular Compressor manuals by other brands

American Eagle SRS-65 owner's manual

American Eagle

American Eagle SRS-65 owner's manual

Aphex 240 instruction manual

Aphex

Aphex 240 instruction manual

Scheppach GK250o Original instruction manual

Scheppach

Scheppach GK250o Original instruction manual

Hanbell RC2-AV Series manual

Hanbell

Hanbell RC2-AV Series manual

Schulz MSI 5,2 ML quick start guide

Schulz

Schulz MSI 5,2 ML quick start guide

Luna ACD1.5-24OL manual

Luna

Luna ACD1.5-24OL manual

Scheppach HC24V Translation from the original instruction manual

Scheppach

Scheppach HC24V Translation from the original instruction manual

Coltri Compressors ERGO MCH-16/EM Use and maintenance manual

Coltri Compressors

Coltri Compressors ERGO MCH-16/EM Use and maintenance manual

Bitzer 2HL-1.2Y operating instructions

Bitzer

Bitzer 2HL-1.2Y operating instructions

COLTRI MCH-5-10-14 EVO CNG Maintenance manual

COLTRI

COLTRI MCH-5-10-14 EVO CNG Maintenance manual

Roller Multi-Control SL instruction manual

Roller

Roller Multi-Control SL instruction manual

American Eagle SHD-60 owner's manual

American Eagle

American Eagle SHD-60 owner's manual

Beta 1555B instructions

Beta

Beta 1555B instructions

MGF SIL-EOL Series Operating & maintenance instruction manual

MGF

MGF SIL-EOL Series Operating & maintenance instruction manual

KAESER SK Series operating manual

KAESER

KAESER SK Series operating manual

Ingersoll-Rand P-130 SD Operating & Maintenance Manual with Spare Parts List

Ingersoll-Rand

Ingersoll-Rand P-130 SD Operating & Maintenance Manual with Spare Parts List

Drawmer SL22 manual

Drawmer

Drawmer SL22 manual

VITO PRO-POWER instruction manual

VITO

VITO PRO-POWER instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.