Installation Guide
Pressure Control, types KP 1, KP 1W, KP 1A, KP 2, KP 5, KP 5A,
KP6W, KP 6B, KP 6S, KP 6AW, KP 6AB, KP 6AS, KP 7W, KP 7B, KP 7S
Refrigerants
Ambient temperatures / Mounting requirements
KP 1, KP 2,
KP 5, KP 6, KP 7
KP 1, KP 2,
KP 5, KP 6, KP 7 KP 1A, KP 5A
KP 1, KP 1W, KP 2, KP 5, KP 6W, KP 6B,
KP 6S, KP 7W, KP 7B, KP 7S:
HCFC and non-ammable HFC
KP 1A, KP 5A, KP 6AW, KP 6AB, KP 6AS:
R717, HCFC and non-ammable HFC
Connections
Connections
for KP 1A, KP 5A, KP 6AS
Mounting
-40 – 65 °C
-25 – 65 °C (PED approved units)
Relative humidity RH: 30 – 98%
Vibrations resistance: 4 g (10 – 1000 Hz)
PS/MWP
(Maximum Working Pressure)
Type Regulation range PS/MWP
KP 1
KP 1, reset
KP 1 W
KP 2
KP 2
-0.2 – 7.5 bar
-0.9 – 7.0 bar
0.5 – 3.0 bar
-0.2 – 5.0 bar
-0.2 – 3.5 bar
245 psig / 17 bar
245 psig / 17 bar
245 psig / 17 bar
245 psig / 17 bar
145 psig / 10 bar
KP 5
KP 6
KP 7
8 – 32 bar
8 – 42 bar
8 – 32 bar
510 psig / 35 bar
675 psig / 46,5 bar
510 psig / 35 bar
Ptestmax.:
KP 1, KP 2: 20 bar pe(285 psig)
KP 2: 12 bar pe(174 psig)
KP 5, KP 7: 35 bar pe(510 psig)
KP 6: 46,5 bar pe(675 psig)
Test pressure (Ptest)
PS/MWP
Enclosure
B: Enclosure IP30
(EN 60529)
C: Enclosure IP44
(EN 60529)
A: 8 – 32 UNC (M4)