
INSTALLATION MANUAL H5001 HYBRID INVERTER
REV.4 ©2022 DARFON ELECTRONICS CORP. 15 | PAGE
Error and Warning Definition
On the Power Flows Page, the icon will flash when there is an error. Below are the error codes and their solutions.
DC bus voltage exceeds the upper
threshold
1. Turn off the inverter.
2. Make sure the PV terminal are not used, and DC Disconnect is off.
3. If Grid is absent, disconnect any grid-tied inverter from to the load terminal.
4. Turn on the inverter. If the error remains, contact your installer.
Reboot the inverter. If the error remains, contact your installer.
DC bus voltage falls below the lower
threshold
1. Turn off the inverter.
2. Measure the voltage at the battery and at the cabling above and below the
battery disconnect to make sure voltage is within 44 to 58Vdc.
3. If the voltages are in range, check if the battery went into protection mode.
4. Turn on the inverter. If the error remains, contact your installer.
Parallel setting is not correct
1. Check the parallel setting and mode setting.
2. Check the communication cable between stacking system.
3.
Reboot the inverter. If the error remains, contact your installer.
Battery discharging current exceeds
the upper threshold
1. Turn off the inverter.
2. Make sure the Grid, Load and Battery terminals are wired properly.
3. Turn on the inverter. If the error remains, contact your installer.
Battery charging current exceeds the
upper threshold
Short circuit on PV1 input
Reboot the inverter. If the error remains, have your installer check the PV array for
short circuits.
Short circuit on PV2 input
Short circuit on AC output
1. Turn off the inverter.
2. Turn off the load breaker.
3. Make sure L1, L2 and N on the load circuit are not shorted.
4. Turn on the inverter. If the error remains, contact your installer.
10 Leakage current CT fault None 1.
Turn off the inverter.
2. If DC Disconnect is on, turn it off. Then turn on the inverter. If the error remains,
turn off the inverter again.
3. Turn off the battery breaker. Check the battery and the battery cablers for leaking
current. If found, contact your installer.
4. Turn off the load breaker. Check all appliances on the essential load for leaking
current. If found, unplug the appliance safely. Then turn on the inverter.
5. If the error remains, turn off the Utility and the inverter’s Grid breaker. Then
measure the Grid and make sure the impedance of L1, L2 and N relative to
ground and to each other should be an open circuit.
6. Reboot the inverter. If the error remains, contact your installer.
DC/DC Current Sensor fault
Reboot the inverter. If the error remains, contact your installer.
Communication with main & secondary
controllers are interrupted
[The internal temperature is too high]
Off: 1s
1. Make sure the inverter is properly ventilated by removing any obstruction around
the vents.
2. Make sure the fans are working.
3. Turn off the inverter, let it cool down for 10 minutes, then turn it back on.
4.
If the error remains, contact your installer.
PV input voltage exceeds the upper
threshold
OC
is higher than 500VDC, contact your installer.
2. If the PV VOC is less than 500VDC, turn off the inverter and restart it after 5
seconds. If the error remains, contact your installer.
[The Grid/ Load power has been over
Off: 0.75s
1. Turn off the inverter.
2. Make sure the load is lower than 5kW
3. Turn on the inverter. If the error remains, contact your installer.
PV insulation resistance is too low
1. Turn off the DC Disconnect.
2. Check if the impedance between positive and negative poles to the ground is
greater than 1MΩ.
3. If the impedance is lower than 1MΩ, contact your installer.
Battery charging voltage is too high
1. Turn off the inverter.
2. Make sure the connection between battery and inverter has firm and solid
contact.
3. Make sure the battery voltage is within manufacturer’s specifications.
4.
Turn on the inverter. If the error remains, contact your installer.
1. Reboot the inverter.
2. Make sure the fans are working. If the error remains, contact your installer.
[The load exceeds available output
power. This error will disappear once
load is in an acceptable range.]
Off: 0.75s
1. If an overload occurs for more than 40 seconds, the inverter will turn off the load
output for 30 seconds. If the inverter turns off the load output 3 times within a 5-
minute interval, the load output will be turned off indefinitely.
2. To turn the load output back on, reboot the inverter.
3. If overload error appears constantly, decrease the load.
1. Make sure your total PV does not exceed 6.5kW, and each string does not
exceed 3.25kW.
2. Reboot the inverter. If the error remains, contact your installer.