About Panel
About JRS1Dsp Series Thermal Overload Relay
Trip level Trip current
Aux. contact
Legends:
1.Power end 2.Current regulation 3.Test button
4.Aux. contact 5.Load end 6.Stop button
7.Manual reset key, manual and auto regulating key 8.Model
9.Rated insulation voltage of main circuit 10.Certificaiton mark
11. Rated insulation voltage of auxiliary circuit 12.Resistive current of aux. circuit
13. Trip level: Level 10A for JRS1Dsp-25 and JRS1Dsp-38, and Level 10 for JRS1Dsp-93.
14.Trip current: 125% setting current
Normal Operation, Installation and Transport Conditions
●Normal operation and installation conditions
(1) The ambient air temperature is not higher than +40℃, and is not below -5℃; the average value within 24
hours does not exceed +35℃;
(2) The altitude of the installation site does not exceed 2000m;
(3) The relative humidity of the atmosphere does not exceed 50% at the maximum ambient temperature of +40℃,
and a higher relative humidity is allowed at lower temperatures, such as 90% at 20℃. Special measures shall be
taken for condensation occasionally generated due to temperature changes.
(4) The product shall be installed vertically and the inclination angle in each direction shall not exceed 5°;
(5) Installed in places where there is no impact vibration or rain and snow erosion;
(6) Pollution level: Level 3;