Please read this instruction carefully before use.
Switch off the power before wiring.
DVP04DA-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust,
humidity,electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the
device (e.g. key or specific tools arerequired to open the enclosure) in case danger and damage on the device may
occur.
DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check
all the wiring again before switching on the power.
DO NOT touch any terminal when the power is switched on. DO NOT touch any internal circuit in 1 minute after
the power is switched off.
Make sure the groud terminal is correctly grounded in order to prevent electromagnetic interference.
Introduction
Model Explanation & Peripherals
Thank you for choosing Delta DVP series PLC. The data in DVP04DA-H2 can be read or written
FROM/TO instructions given by the program of DVP-EH2 series MPU. The analog signal output module
receives 4 groups of 12-bit digital data from PLC MPU and converts the data into 4 points of analog
signals for output in either voltage or current.
You can select voltage or current output by wiring. Range of voltage output: 0V ~ +10V DC (resolution:
2.5mV). Range of current output: 0mA ~ 20mA (resolution: 5µA).
Product Profile (Indicators, Terminal Block, I/O Terminals)
Unit: mm
D - V + I +
CO M
24V 0V
V + I + V+ I +
C O M
D + CO M
8
C H 1 C H 3 CH 4RS -4 8 5
F G
V +
F G C O M F G
I +
CH2
○
1
DIN rail (35mm)
○
6
Terminals
○
2
Connection port for extension modules
○
7
Mounting hole
○
3
Model name
○
8
I/O terminals
○
4
POWER, ERROR, D/A indicator
○
9
Mounting port for extension modules
○
5
DIN rail clip
ENGLISH
External Wiring
V+
I+
CH1
0V~+1 0V
*2
*3
0mA~2 0mA
DC24V
CH4 CH4
AC drive,recorder,
scale valve...
AC drive, recorder,
scale valve...
shieldingcable *1
shieldingcable *1
currentoutput
converter
terminal of
powermodule
systemgrounding
class 3 grounding
(100
Note:
1. When performing analog output, please isolate other power wirings.
2. If the ripples at the loaded input terminal are too significant that causes noise interference on the wiring, connect the
wiring to 0.1 ~ 0.47µF 25V capacitor.
3. Please connect the terminal on both the power modules and DVP04DA-H2 to the system earth point and ground the
system contact or connect it to the cover o f power distribu tion cabinet.
4. DO NOT wire empty terminals
.
Specifications
Digital/Analog (4D/A)
module Voltage output Current output
Power supply voltage 24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)
Analog output channel 4 channels/module
Range of analo g output 0 ~ 10V 0 ~ 20mA
Range of digital data 0 ~ 4,000 0 ~ 4,000
Resolution 12 bits (1
LSB
= 2.5mV) 12 bits (1
LSB
= 5µA)
Output impedance 0.5Ωor lower
Overall accurac y
±0.5% when in full scale (25°C, 77°F)
±1% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F
Responding time 3ms × the number of channels
Max. output current 10mA (1KΩ~ 2MΩ) -
Tolerable load impedance
- 0 ~ 500Ω
Digital data format 11 significant bits out of 16 bits are available; in 2’s complement.
Isolation Internal circuit and analog output term inals are isolated by optical coupler.
No isolation among analog channels.
Protection Voltage output is protected by short circuit. Short circuit lasting for too long may cause
damage on internal circuits. Current output can be open circuit.
Communication mode ASCII/RTU mode.
(RS-485) Communication speed: 4,800/9,600/19,200/38,400/57,600/115,200 bps.
ASCII data format: 7-bit, even bit, 1 stop bit (7, E, 1).
RTU data format: 8-bit, even bit, 1 stop bit (8, E, 1).
RS-485 cannot be used when connected to PLC M PU.
When connected to
DVP-PLC MPU in series
The modules are numbered from 0 to 7 automatically by their distance from MPU. No.0 is
the closest to MPU and No.7 is the furthest. Maximum 8 modules are allowed to connect to
MPU and will not occupy any digital I/O points.
Other Specifications
Power supply
Max. rated po wer
consumption 24V DC (20.4V DC ~ 28.8V DC) (-15 % ~ +20%), 4.5W, supplied by external power.
Environment
Operation/storage Operation: 0°C ~ 55°C (temperature); 50 ~ 95% (humidity); pollution degree 2
Storage: -25°C ~ 70°C (temperature); 5 ~ 95% (humidity)
Vibration/shock
immunity
International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27
(TEST Ea)
Control Registers
CR
#
RS-485
Model name
Set up by the s ystem. DVP04DA-H2 model code = H’6401.
The user can read the model name from the program and see
if the extension module exists.
Reserved CH4 CH 3 CH2 CH1
#1 H’4033
○
Output mode setting
Output mode: Default = H’0000
Mode 0: Voltage output (0V ~ 10V)
Mode 1: Voltage output (2V ~ 10V)
Mode 2: C urrent output (4mA ~ 20mA)
Mode 3: C urrent output (0mA ~ 20mA)
CR#1: The working mode of the four channels in the analog input module. There are 4 modes for each channel which c
be set up separately. For example, if the user needs to set up CH1: mode 0 (b2 ~ b0 = 000); CH2: mode 1 (b5 ~ b3 = 001),
CH3: mode 2 (b8 ~ b6 = 010) and CH4: mode 3 (b11 ~ b9 = 011), CR#1 has to be set as H’
000A and the higher bits (b12 ~
b15) have to be reserved. Default value = H’0000.
#6
CH4 output value
Range of output value at CH1 ~ CH4: K0 ~ K4,000
Default = K0 (unit: LSB)
#18
Adjusted OFFSET value of CH1
Adjusted OFFSET value of CH 2
Adjusted OFFSET value of CH 3
Adjusted OFFSET value of CH 4
Range of OFFSET at CH1 ~ CH4: K-2,000 ~ K2,000
Default = K0 (unit: LSB)
#24
Adjusted GAIN value of CH1
#25
Adjusted GAIN value of CH2
#26
Adjusted GAIN value of CH3
Range of GAIN at CH1 ~ C H4: K0 ~ K4,000
Default = K2,000 (unit: LSB)
CR
#
Adjusted GAIN value of CH4
CR#18 ~ CR#27: Please note that: GAIN value - OFFSET value = +400
LSB
~ +6,000
LSB
(voltage or current). When GAIN -
OFFSET is small (steep oblique), the resolution of output signal will be finer and variation on the digital value will be
greater. When GAIN - OFFSET is big (gradual oblique), the resolution of output signal will be rougher and variation on the
digital value will be smaller.
#30
R Error status Register for storing all error status.
See the table of error status for more information.
CR#30: Error status value (See the table below)
Error status Content b15 ~ b8 b7 b6 b5 b4 b3 b2 b1 b0
Abnormal power supply K1 (H’1) 0 0 0 0 0 0 0 1
Incorrect analog input valu e K2 (H’2) 0 0 0 0 0 0 1 0
Incorrect mode settin g K4 (H’4) 0 0 0 0 0 1 0 0
OFFSET/GAIN error K8 (H’8) 0 0 0 0 1 0 0 0
Hardware malfunction K16 (H’10) 0 0 0 1 0 0 0 0
Abnormal digital range K32 (H’20) 0 0 1 0 0 0 0 0
Incorrect average times setting K64 (H’40) 0 1 0 0 0 0 0 0
Instruction error K128 (H’80)
Reserved
1 0 0 0 0 0 0 0
Note: Each error status is determined by the corresponding bit (b0 ~ b7) and there may be more than 2 errors occurring at the
same time. 0 = normal; 1 = error.
Example: Iif the digital input exceeds 4,000, error (K2) will occur. If the analog output exceeds 10V, both analog input value
error K2 and K32 will occur.
#31
Communication address setting
For setting up RS-485 comm unication address.
Range: 01 ~ 254. Default = K1
#32
Communication speed (baud
rate) setting
Default = H’0002. For settin g up communication speed: 4,800
/9,600/19,200/38,400/57,600/115,200 bps.
ASCII data format: 7-bit, even bit, 1 stop bit (7, E, 1).
RTU data format: 8-bit, even bit, 1 stop bit (8, E, 1).
b0: 4,800 bps. b1: 9,600 bps (Default).
b2: 19,200 bps. b3: 38,400 bps.
b4: 57,600 bps. b5: 115,200 bps.
b6 ~ b13: R eserved.
b14: High/low bit exchange of CRC checksum (only valid in
RTU mode).
b15: Switch between ASCII/RTU mode. 0 = ASCII mod e
(Default).
Reserved CH4 CH3 CH2 CH1
#33
Return to default setting;
OFFSET/GAIN tuning
authorization
Default = H’0000. Take the setting of CH1 for example:
1. When b0 = 0, the user is allowed to tune CR#18
(OFFSET) and CR#24 (GAIN) of CH1. W hen b0 = 1, the
user is not allo wed to tune CR#18 (OFFSET) and CR#24
(GAIN) of CH1.
2. b1 represents whether the OFFSET/GAIN tuning registers
are latched. b1 = 0 (default, latched); b1 = 1 (non-latched).
3. When b2 = 1, all se ttings will return to default values.
(except CR#31, CR#32)
CR#33: For authorizations on some internal functions, e.g. OFFSET/GAIN tuning. The latched function will store the
output setting in the internal memory before the power is cut off.
#34
Firmware version Displaying the current firm ware version In hex; e.g. version
1.0A is indicated as H’010A.
#35 ~ #48 For system use.
Symbols:
○
:Latched (when written in through RS-485 communication);
╳
: Non-latched;
R: Able to read data by FROM instruction or RS-485 communication;
W: Able to write data by TO instruction or RS-485 communication.
LSB (Least Significant Bit):
For voltage output: 1
LSB
= 10V/4,000 = 2.5mV. For current output: 1
LSB
= 20mA/4,000 = 5µA.
CR#0 ~ CR#34: The corresponding parameter addresses H’4032 ~ H’4054 are for users to read/write data by
RS-485 communication. When using RS-485, the user has to separate the module with MPU first.
a. Communication baud rate: 4,800/9,600/19,200/38,400/57,600/115,200 bps.
b. Modbus ASCII/RTU communication protocols: ASCII data format (7-bit, even bit, 1 stop bit (7, E, 1));
RTU data format (8-bit, even bit, 1 stop bit (8, E, 1)).
c. Function: H’03 (read register data); H’06 (write 1 word datum to register); H’10 (write many word data to
register).
d. Latched CR should be written by RS-485 communication to stay latched. CR will not be latched if written
by MPU through TO/DTO instruction.
Adjusting D/A Conversion Curve
Voltage output mode
CR#1 mode 0 GAIN = 5V (2,000
LSB
). OFFSET = 0V (0
LSB
).
CR#1 mode 1 GAIN = 6V (2,400
LSB
). OFFSET = 2V (800
LSB
).
GAIN The voltage output value when the digital input value = K2,000.
Range: 0
LSB
~ +4,000
LSB
.
OFFSET The voltage output value when the digital input value = K0.
Range: -2,0 00
LSB
~ +2,000
LSB
.
+2,0 00
Digi tal input
Mode 1
Mode 0
Range: +400
LSB
~ +6,000
LSB
.
Current output mode
CR#1 mode 2 GAIN = 12mA (2,400
LSB
). OFFSET = 4mA (800
LSB
).
CR#1 mode 3 GAIN = 10mA (2,000
LSB
). OFFSET = 0m A (0
LSB
).
GAIN The current outp ut value when the digital input value = K2,000.
Range: 0
LSB
~ +4,000
LSB
.
OFFSET The current output value when the digital input value = K0.
Range: -2,0 00
LSB
~ +2,000
LSB
.
0+2,000
20mA
OFFSET
GAIN
12mA
10mA
4mA
Range: +400
LSB
~ +6,000
LSB
.
注意事項
請在使用之前,詳細閱讀本使用說明書。
實施配線,務必關閉電源。
本機為開放型
(OPEN TYPE)
機 ,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊
/
衝擊
意外之外 配線箱內。另必須具備保護措施(如:特殊之工具或鑰匙才可打開)防止非維護人員操作或意外
衝擊本體,造成危險及損壞。
輸入電源不可連接於輸入
/
出信號端,否則可能造成嚴重的損壞,因此請在上電之前再次確認電源配線。
請勿在上電時觸摸任何端子。輸入電源切斷後,一分鐘之內,請勿觸摸內部電路。
本體上之接地端子 務必正確的接地,可提高產品抗雜訊能力。
產品簡介
說明及週邊裝置
感謝您採用台達
DVP
系列產品。
DVP04DA-H2
類比信號輸出模組可透過
DVP-EH2
系列主機程式以指令
FROM/TO
來 寫
DVP04DA-H2
類比信號輸出模組之資料。而類比信號輸出模組接受來自
PLC
主機的
4
組
12
位元數位資料,再將數位資料轉換為
4
點類比信號輸出(電壓或電流皆可)。
使用者可經由配線選擇電壓輸出或電流輸出。電壓輸出範圍
0V ~ +10V DC
(解析度為
2.5mV
)。電流輸出
範圍
0mA ~ 20mA
(解析度為
5µA
)。
產品外觀及各部介紹
尺寸單位:
mm
D - V + I +
C OM
24V 0 V
V + I + V + I +
C OM
D + CO M
8
C H1 CH 3 C H 4R S-4 85
FG
V +
FG CO M F G
I +
C H2
1
DIN
軌糟
(35mm)
6
端子
2
擴充機
/
擴充模組連接口
7
固定孔
3
機種名稱
8
端子配置
4
電源、錯誤及轉換指示燈
9
擴充機
/
擴充模組連接座
5
DIN
軌固定扣
繁體中文
外部配線
V+
I+
COM
V+
I+
COM
24+
24-
DC/DC
轉換器
+15V
隔離線
*1
電壓輸出
0V~+10 V
*2
變頻器、 記錄器
比例閥...
*3
隔離線
*1
電流輸出
0mA~20mA
變頻器、 記錄器
比例閥...
接至電源模
組之 端
接地
(接地 阻 以下
CH4
註
1
:類比輸出請與其他電源線隔離。
註
2
:如果負載之輸入端漣波太大造成配線受 訊干擾時,請連接
0.1 ~ 0.47µF 25V
之電容。
註
3
:請將電源模組之 端及
DVP04DA-H2
類比信號輸出模組之 端連接到系統接地點,再將系統接點作接地或接到
配電箱之機殼上。
注意:空端子
請勿配線
。
規格
數位
/
類比
(4D/A)
模組
電壓輸出
電流輸出
電源電壓
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)
類比訊號輸出通道
4
通道
/
台
類比輸出範圍
0 ~ 10V 0 ~ 20mA
數位資料範圍
0 ~ 4,000 0 ~ 4,000
析度
12 bits (1
LSB
= 2.5mV) 12 bits (1
LSB
= 5µA)
輸出阻抗
0.5Ω
或更低
總和精密度
±0.5%
在(
25°C, 77°F
)範圍內滿刻度時。
±1%
在(
0 ~ 55°C, 32 ~ 131°F
)範圍內滿刻度時。
響應時間
3ms ×
通道數
最大輸出電流
10mA (1KΩ~ 2MΩ)
-
容許負載阻抗
-
0 ~ 500Ω
數位資料格式
16
位元二補數,有效位
11 bits
隔離方式
內部電路與類比輸出端以光耦合器隔離,類比通道間未隔離。
保護
電壓輸出有短路保護但須注意長時間短路仍有可能造成內部線路損壞,電流輸出可開路。
通訊模式
(RS-485)
包含
ASCII/RTU
模式,通訊速率可選(
4,800/9,600/19,200/38,400/57,600/115,200 bps
),
ASCII
模
式資料格式固定為
7 bits
、偶位元、
1 stop bit (7, E, 1)
,
RTU
模式資料格式固定為
8 bits
、偶位元、
1 stop bit (8, E, 1)
。當與
PLC
主機串接時,
RS-485
通訊無法使用。