1-3
1Important Safety Instructions
WARNING!
yFollow the IEC 60364-4-42 standard to install the UPS.
yConnect the UPS’s output to either critical loads or rack-mount PDCs (optional). Please
only choose one application. You can install at maximum two rack-mount PDCs in one
UPS.
yIf the UPS’s output connects to the rack-mount PDC (optional; at maximum two), please
refer to the rack-mount PDC’s user manual for relevant information about the rack-
mount PDC’s installation, wiring and operation.
yLeave adequate space around all sides of the UPS for proper ventilation and mainte-
nance. Please refer to 5.2 Installation Environment.
yThe installation of protective devices is highly recommended when the UPS is connect-
ed to power sources and critical loads.
yThe protective devices connecting to the UPS must be installed near the UPS and must
be easily accessible for operation.
yThe external slits and openings in the UPS are provided for ventilation. To ensure reli-
able operation of the UPS and to protect the UPS from overheating, these slits and
openings must not be blocked or covered. Do not insert any object into the slits and
openings that may hinder ventilation.
yTo protect the UPS from overheating, wiring must not block or cover any fans of the
Power Module (optional; at maximum six) and the rack-mount PDC (optional; at maxi-
mum two).
yIf the UPS is supplied by a source whose neutral is grounded, the protective device
installed as UPS input protection must be a 3-pole type. If the UPS is supplied by a
source whose neutral is not grounded, the protective device installed as UPS input pro-
tection must be a 4-pole type.
yDo not put beverages on the UPS, external battery cabinet or any other accessory as-
sociated with the UPS.
yBefore applying power to the UPS, you must allow it to adjust to room temperature (20°C
~ 25°C) for at least one hour to avoid moisture condensing inside the UPS.
yThe UPS is electrical equipment that runs 24 hours continuously. To ensure its normal
lifetime, regular maintenance of the UPS and batteries is of vital importance and neces-
sary.
ySome components like batteries, power capacitors, and fans will become worn-out due
to long-term usage, and this will increase the risk of UPS failure. To replace and main-
tain the components, please contact Delta customer service department.