manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Fike
  6. •
  7. Security Sensor
  8. •
  9. Fike FIK-W-PHOTO User manual

Fike FIK-W-PHOTO User manual

This sensor must be installed in compliance with the control panel system
installation manual and the SWIFT Wireless Manual. The installation must
meet the requirements of the Authority Having Jurisdiction (AHJ). Sensors
offer maximum performance when installed in compliance with the National
Fire Protection Association (NFPA); see NFPA 72.
GENERAL DESCRIPTION
Models FIK-W-PHOTO and FIK-W-ACCLIMATE are plug-in type smoke sensors
that combine a photoelectronic sensing chamber with wireless communica-
tion. The sensors transmit a digital representation of smoke density through
a wireless mesh to a gateway. The gateway will send the information to the
panel when requested. Rotary dial switches are provided for setting the sen-
sor’s address. (See Figure 1.)
Two LEDs on the sensor are controlled by the panel to indicate sensor status.
Model FIK-W-ACCLIMATE combines a photoelectronic sensing chamber and
135°F (57.2°C) fixed temperature heat detector. The FIK-W-ACCLIMATE also
transmits an alarm signal due to heat (135°F fixed) per UL 521.
Fike panels offer different features sets across different models. As a result,
certain features of the FIK-W-PHOTO and FIK-W-ACCLIMATE may be avail-
able on some control panels, but not on others. The possible features avail-
able in the FIK-W-PHOTO and FIK-W-ACCLIMATE, if supported by the control
panel are:
• The panel controls the LED operation on the sensor. Operational modes
include red, green and amber colors in various solid or blink patterns.
Please refer to the operation manual for the UL listed control panel for specific
operation of the FIK-W-PHOTO and FIK-W-ACCLIMATE.
The FIK-W-PHOTO and FIK-W-ACCLIMATE require compatible addressable
communications to function properly. Connect these sensors to listed-compat-
ible control panels only.
SPACING
Fike recommends spacing sensors in compliance with NFPA 72. In low air
flow applications with smooth ceilings, space sensors 30 feet apart. When
using the FIK-W-ACCLIMATE as a heat detector in FM3210 compliant applica-
tions, space sensors 20 feet apart. For specific information regarding sensor
spacing, placement, and special applications, refer to NFPA 72 or the System
Smoke Detector Application Guide, available from System Sensor.
Wireless technologies can exhibit communication disruption if devices are
spaced too close together. To avoid this form of disruption, SWIFT devices
should not be placed closer than 2 feet (60 cm) apart without an intervening
structure.
NOTE: Do not attach the base and detectors to temporary structures such as
removable ceiling tiles such that the placement could be altered. To prevent
I56-6960-000
INSTALLATION AND MAINTENANCE INSTRUCTIONS
changes in device placement, permanently secure the structure or mount the
detector across the ceiling panel support as shown in Figure 2.
BATTERY REPLACEMENT
Low battery levels on the wireless devices are displayed as a trouble on the
FACP. Therefore when the message “TROUBLE BATTERY LOW” is displayed,
replace the battery in the device. This message is an indication that approxi-
mately one week of battery life remains.
To replace the batteries in a wireless device use the following steps:
1. Have 4 CR123A (or DL123A) batteries available
2. Remove the detector from the base.
3. Open the battery compartment refer to Figure 3. Note: The battery com-
partment cover may be left attached at the hinges during battery replace-
ment.
4. Remove the used batteries and replace with new batteries. The battery
compartment is designed such that the batteries can only align in the ap-
propriate direction. Do not force the batteries into the openings.
5. Replace the battery compartment cover.
6. Return the device to its original location.
CAUTION
Dust covers provide limited protection against airborne dust particles during
shipping. Dust covers must be removed before the sensors can sense smoke.
Remove sensors prior to heavy remodeling or construction.
FIGURE 1. ROTARY ADDRESS SWITCHES
TENS ONES
9
10
11
12
13
14
15
8
7
6
5
4
3
210
9
8
7
6
5
4
3
210
C0162-00
SPECIFICATIONS
Operating Voltage Range: 3.3 VDC
Standby Current: 210µA @ 3.3 VDC (one communication every
23.8 seconds with LED blink enabled)
Maximum Alarm Current (LED on): 5 mA @ 3.3 VDC LED on
Maximum Transmit RF Power: 17dBm
Radio Frequency Range: 902-928 MHz
Operating Humidity Range: 10% to 93% Relative Humidity, Non-condensing
Operating Temperature Range: 32°F to 120°F (0°C to 49°C), FIK-W-PHOTO;
32°F to 100°F (0°C to 38°C), FIK-W-ACCLIMATE
Air Velocity: 0 to 4000 ft/min
Battery Type: 4 Panasonic CR123A or 4 Duracell DL123A
Battery Life: 2 year minimum
Battery Replacement: Upon TROUBLE BATTERY LOW display and/or during annual maintenance
Height: 2.4˝ (61 mm) installed in B210W Base
Diameter: 6.0˝ (152 mm) installed in B210W Base
Weight: 9.2 oz. (261 g) installed in B210W base with 4 batteries
R
704 SW 10th Street
Blue Springs, MO 64015
Phone: 816.229.3405; Fax: 816.228.9277
www.fike.com
FIK-W-PHOTO and FIK-W-ACCLIMATE
Wireless Intelligent
Photoelectric Smoke Sensors
http://www.fike.com/06-912
Fo
r system/product documentation including
installation, operation, and maintenance,
scan QR code or enter URL provided.
1 I56-6960-000
1/15/2021
MANUFACTURER MODEL
Home Safeguard Industries 25S and 30S
SDi CHEK02 and CHEK06
SDi SOLO A10
SDi SMOKESABRE-01
When used properly, the canned smoke agent will cause the smoke detector
to go into alarm. Refer to the manufacturer’s published instructions for proper
use of the canned smoke agent.
CAUTION
Canned aerosol simulated smoke (canned smoke agent) formulas will vary by
manufacturer. Misuse or overuse of these products may have long term ad-
verse effects on the smoke detector. Consult the canned smoke agent manufac-
turer’s published instructions for any further warnings or caution statements.
For FIK-W-ACCLIMATE, smoke entry testing should be performed imme-
diately following the magnet test. Magnet test initiates an approximately
5 minute period when the detector’s signal processing software routines
are not active. Failure to first perform the magnet test will introduce a
time delay before the detector alarms.
C. Direct Heat Method (Hair dryer of 1000-1500 watts).
FIK-W-ACCLIMATE only.
A hair dryer of 1000-1500 watts should be used to test the thermistors. Di-
rect the heat toward either of the two thermistors, holding the heat source
approximately 12 inches from the detector in order to avoid damaging
the plastic housing. The detector will reset only after it has had sufficient
time to cool. Make sure both thermistors are tested individually.
A sensor that fails any of these tests should be cleaned as described under
CLEANING, and retested. If the sensor fails after cleaning, it must be replaced
and returned for repair.
When testing is complete, restore the system to normal operation and notify
the proper authorities that the system is back in operation.
CLEANING
Before removing the detector, notify the proper authorities that the smoke de-
tector system is undergoing maintenance and will be temporarily out of service.
Disable the zone or system undergoing maintenance to prevent unwanted alarms.
1. Remove the sensor to be cleaned from the system.
2. Remove the sensor cover by pressing firmly on each of the four removal
tabs that hold the cover in place. (See Figure 5.)
3. Vacuum the screen carefully without removing it. If further cleaning is
required continue with Step 4, otherwise skip to Step 7.
4. Remove the chamber cover/screen assembly by pulling it straight out.
5. Use a vacuum cleaner or compressed air to remove dust and debris from
the sensing chamber.
6. Reinstall the chamber cover/screen assembly by sliding the edge over the
sensing chamber. Turn until it is firmly in place.
7. Replace the cover using the LEDs to align the cover and then gently
pushing it until it locks into place. Make sure that the thermistors do not
become bent under the cover on the FIK-W-ACCLIMATE model.
8. Reinstall the detector.
9. Test the detector as described in TESTING.
10. Reconnect disabled circuits.
11. Notify the proper authorities that the system is back on line.
SPECIAL NOTE REGARDING SMOKE DETECTOR GUARDS
Smoke detectors are not to be used with detector guards unless the combina-
tion has been evaluated and found suitable for that purpose.
BATTERY
COMPARTMENT
COVER
FIGURE 2. CEILING PANEL SUPPORT
FIGURE 3. BATTERY COMPARTMENT
TAMPER RESISTANCE
Models FIK-W-PHOTO and FIK-W-ACCLIMATE include a tamper-resistant ca-
pability that prevents their removal from the base without the use of a tool.
Refer to the base manual for details on making use of this capability. The base
also includes a magnet for tamper resistance. The magnet activates a supervi-
sory tamper fault at the panel if the detector is removed from the base.
TESTING
Before testing, notify the proper authorities that the system is undergoing
maintenance, and will temporarily be out of service. Disable the system to
prevent unwanted alarms.
All sensors must be tested after installation and periodically thereafter. Testing
methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors offer max-
imum performance when tested and maintained in compliance with NFPA 72.
The sensor can be tested in the following ways:
A. Functional: Magnet Test (P/N M02-04-01 or M02-09-00)
This sensor can be functionally tested with a test magnet. The test mag-
net electronically simulates smoke in the sensing chamber, as well as
tests the sensor electronics and connections to the control panel.
1. Hold the test magnet in the magnet test area as shown in Figure 4.
2. The sensor should alarm the panel.
Two LEDs on the sensor are controlled by the panel to indicate sensor
status. Coded signals, transmitted from the panel, can cause the LEDs
to blink, latch on, or latch off. Refer to the control panel technical docu-
mentation for sensor LED status operation and expected delay to alarm.
B. Smoke Entry
The GEMINI model 501 aerosol generator can be used for smoke entry
testing. Set the generator to represent 4%/ft to 5%/ft obscuration as de-
scribed in the GEMINI 501 manual. Using the bowl shaped applicator,
apply aerosol until the panel alarms.
Additionally, canned aerosol simulated smoke (canned smoke agent)
may be used for smoke entry testing of the smoke detector. Tested and
approved aerosol smoke products are:
C1091-00
C1092-00
2 I56-6960-000
1/15/2021
C2011-04
COVER
REMOVAL
TABS
SENSOR
COVER
FIK-W-PHOTO FIK-W-ACCLIMATE
SENSING CHAMBER
COVER AND SCREEN
SENSING
CHAMBER
COVER
REMOVAL
TABS
FIGURE 5. DETECTOR COMPONENTS
FIGURE 4. MAGNET TEST MARKERS
C0145-02
LED
TEST MAGNET
POSITION
MAGNET TEST
MARKER
LED
3 I56-6960-000
1/15/2021
Fike®is a registered trademark of Fike Corporation. SWIFT® and System Sensor® are registered trademarks of Honeywell International, Inc.
FCC STATEMENT
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interference will not occur in
a particular installation. If this equipment does cause harmful interference to radio or television recep-
tion, which can be determined by turning the equipment off and on, the user is encouraged to try to
correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is con-
nected.
– Consult the dealer or an experienced radio/TV technician for help.
LICENSING STATEMENT
Use of these products in combination with
non-Honeywell products in a wireless
mesh network, or to access, monitor or
control devices in a wireless mesh nework
via the internet or another external wide
area network, may require a separate
license from Sipco, LLC. For more infor-
mation, contact Sipco, LLC or Ipco, LLC at
8215 Roswell Rd., Building 900, Suite 950,
Atlanta, GA 303350, or at www.sipocollc.
com or www.intusiq.com.
SUPPLEMENTAL INFORMATION
For Limitations of Fire Alarm Systems,
please go to:
http://www.systemsensor.com/
en-us/Documents/I56-1558.pdf
Limitations of
Fire Alarm Systems
4 I56-6960-000
©2021. 1/15/2021

This manual suits for next models

1

Other Fike Security Sensor manuals

Fike Twinflex Multipoint 202-0003 User manual

Fike

Fike Twinflex Multipoint 202-0003 User manual

Fike FIK-RA100 Technical manual

Fike

Fike FIK-RA100 Technical manual

Fike CIE-A-200 User manual

Fike

Fike CIE-A-200 User manual

Fike 203-0003 User manual

Fike

Fike 203-0003 User manual

Fike 204-0003 Twinflex Multipoint ASD User manual

Fike

Fike 204-0003 Twinflex Multipoint ASD User manual

Fike FIK-W-PULL-DA User manual

Fike

Fike FIK-W-PULL-DA User manual

Fike FIK-IR3-HD User manual

Fike

Fike FIK-IR3-HD User manual

Fike RDU-A-200 User manual

Fike

Fike RDU-A-200 User manual

Fike 60-1039 User manual

Fike

Fike 60-1039 User manual

Fike FIK-IR3-H2 User manual

Fike

Fike FIK-IR3-H2 User manual

Fike FIK-IR3-AS25 User manual

Fike

Fike FIK-IR3-AS25 User manual

Fike OCELUS Series User manual

Fike

Fike OCELUS Series User manual

Fike 323-0001 User manual

Fike

Fike 323-0001 User manual

Fike FIK-FC351 User manual

Fike

Fike FIK-FC351 User manual

Fike Sita User manual

Fike

Fike Sita User manual

Fike VESDA LaserCOMPACT VLC-500 User manual

Fike

Fike VESDA LaserCOMPACT VLC-500 User manual

Fike FIK-IR3 User manual

Fike

Fike FIK-IR3 User manual

Fike FIK-UV-IR-HD Series User manual

Fike

Fike FIK-UV-IR-HD Series User manual

Fike FIK-2351 User manual

Fike

Fike FIK-2351 User manual

Fike FIK-IR3-H2-HD User manual

Fike

Fike FIK-IR3-H2-HD User manual

Fike CEREX User manual

Fike

Fike CEREX User manual

Fike FIK-RA1000R Technical manual

Fike

Fike FIK-RA1000R Technical manual

Popular Security Sensor manuals by other brands

teko Astra-3731 user guide

teko

teko Astra-3731 user guide

Visonic NEXT K9-85 PG2 installation instructions

Visonic

Visonic NEXT K9-85 PG2 installation instructions

PCB Piezotronics IMI SENSORS EX640B71 Installation and operating manual

PCB Piezotronics

PCB Piezotronics IMI SENSORS EX640B71 Installation and operating manual

Optex sensor manual

Optex

Optex sensor manual

klemko IB-06L Installation and operating instructions

klemko

klemko IB-06L Installation and operating instructions

CMR Electrical WLW manual

CMR Electrical

CMR Electrical WLW manual

Pfeiffer Vacuum ASM 340 operating instructions

Pfeiffer Vacuum

Pfeiffer Vacuum ASM 340 operating instructions

BASETech BT-300 WT operating instructions

BASETech

BASETech BT-300 WT operating instructions

Micromed MM-5kV Quick operation guide

Micromed

Micromed MM-5kV Quick operation guide

Milwaukee LLD50 Original instructions

Milwaukee

Milwaukee LLD50 Original instructions

ERNITEC Eagle PIR-045 manual

ERNITEC

ERNITEC Eagle PIR-045 manual

Dectris PILATUS 1M Operating procedures

Dectris

Dectris PILATUS 1M Operating procedures

TOOLCRAFT 1712611 operating instructions

TOOLCRAFT

TOOLCRAFT 1712611 operating instructions

schmersal SLC440 operating instructions

schmersal

schmersal SLC440 operating instructions

MDT Technologies SCN-P360D3.02 Technical manual

MDT Technologies

MDT Technologies SCN-P360D3.02 Technical manual

Interlogix RF-EV1012PI-K4 installation manual

Interlogix

Interlogix RF-EV1012PI-K4 installation manual

Orbis DICROMAT instructions

Orbis

Orbis DICROMAT instructions

Texecom Prestige Orbit QD installation manual

Texecom

Texecom Prestige Orbit QD installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.