Detection Systems DS7400Xi User manual

Reference Guide
for the DS7400Xi (Version 3+)
Control/Communicator
Turning On (arming) your System using the DS7445/DS7445i
or DS7447/DS7447E Keypad
Normal Arming [PIN] + [On]
Perimeter Arming, no entry delay [PIN] + [No Entry] [Perimeter
Only]
Perimeter Arming, with entry delay [PIN] + [Perimeter Only]
Maximum Security Arming [PIN] + [No Entry] + [On]
Custom Arming [PIN] + [#] [4]
Set Delayed Arming [PIN] + [#] [9] [9] and enter
number of hours from current
timetothedesiredarmingtime.
Extend Automatic Arming [PIN] + [OFF]
during pre-arm time
Force Arming Enter an arming command
followed by [Bypass]
Zone Bypass [PIN] + [Bypass] followed by
the Zone number.
[PIN] +[Bypass] [*] to clear ALL
Bypasses.
Turning Off (disarming) your System
Enter your [PIN] followed by [Off]
Commands for other System Features
Chime Mode [PIN] + [#] [7]
System Walk Test [PIN] + [#] [8] [1]
Event History Readback [PIN] + [#] [8] [9]
Battery Test [PIN] + [System Reset]
Communicator Test [PIN] + [#] [8] [2]
Fire Reset [PIN] + [System Reset]
Remote Program Dial-out [PIN] + [#] [8] [3]
Remote Program Answer [PIN] + [#] [8] [6]
Battery/Sounder Test [PIN] + [#] [8] [5]
Error Display [PIN] + [#] [8] [7]
Clear Error Display [PIN] + [System Reset]
Fire Walk Test [PIN] + [#] [9] [1]
To Silence a Fire Trouble/Alarm [PIN] + [Off]
To Clear a Fire Trouble Display [PIN] + [System Reset]
Access Control
Enter your [Access Control PIN] followed by [Off]
Keypad Quick Reference Guide
Armed
Status
Power
Fire
1 2 3
456
789
0
*#
No
Entry
System
Reset
Bypass
Only
Perimeter
Off
Ready To Arm
On

DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 2
Table of Contents
Keypad Quick Reference Guide ........................................ 1
1.0 Specifications .......................................................... 4
1.1 Enclosure Housing .............................................. 4
1.2 Temperature ........................................................ 4
1.3 Power .................................................................. 4
1.4 Outputs ............................................................... 4
1.5 Zones .................................................................. 4
1.6 Keypads .............................................................. 4
1.7 Communicator ..................................................... 4
1.8 Partitions............................................................. 4
1.9 Users .................................................................. 4
1.10 LightningProtection ............................................ 4
1.11 Burglar/FireZone Inputs...................................... 4
1.12 Fire Signal Initiating Circuit (2-wire mode) ........... 4
1.13 MultiplexBus Wiring Requirements..................... 4
1.13.1 Multiplex Zone Loop Wiring ........................ 4
1.14 OptionBus WiringRequirements ........................ 4
1.15 Max.Load Currents ............................................. 5
1.16 Backup Battery Calculation................................. 5
1.17 StandbyCurrent Load ......................................... 5
1.18 Options ............................................................... 6
2.0 Enclosure Installation ............................................. 8
2.1 Install the Enclosure ........................................... 8
2.2 Install theControl/Communicator ........................ 8
3.0 Control Terminal Wiring .......................................... 9
4.0 Hardware Layout Example .................................... 10
5.0 SystemWorksheet ................................................. 11
6.0 Glossary ................................................................. 15
6.1 GeneralControl Programming ........................... 15
6.2 Zone FunctionProgramming ............................. 15
6.3 ZoneProgramming............................................ 16
6.4 OutputProgramming ......................................... 17
6.5 Partition ControlProgramming .......................... 17
6.6 KeypadAssignment Programming .................... 18
6.7 EmergencyKeyProgramming........................... 18
6.8 Custom ArmingProgramming ........................... 18
6.9 Force Arming .................................................... 18
6.10 GroundFault DetectProgramming .................... 18
6.11 CommercialFire ModeProgramming ................ 18
6.12 Open/CloseReport Control Programming ........ 19
6.13 ReportProgramming ......................................... 19
6.14 PhoneNumber GeneralControlProgramming... 20
6.15 PhoneAnswering Programming ........................ 20
6.16 FCC Compliance Notice.................................... 20
6.17 FCCPhone ConnectionNoticeToUsers........... 20
6.18 CanadianDept. ofCommunications .................. 21
6.19 For Installations in New Zealand ....................... 21
7.0 Operating Guide .................................................... 22
7.1 PersonalIdentificationNumbers........................ 22
7.1.1 General Information ................................... 22
7.1.2 Removing a PIN......................................... 22
7.1.3 Authority Levels ......................................... 22
7.2 Arming/DisarmingCommands........................... 23
7.3 ChangingtheDate............................................. 23
7.4 Changing theTemporaryPINExpirationDate ... 23
7.5 ChangingtheTime ............................................ 24
7.6 DelayedArming................................................. 24
7.7 Automatic Arming ............................................. 25
7.8 Turning OFF the System under Duress ............. 26
7.9 Automatic Disarming......................................... 26
7.10 EmergencyProcedures..................................... 26
7.10.1 Identifying Alarm Sounds .......................... 26
7.10.2 Silencing Alarms........................................ 26
7.10.3 A Cautionary Note ..................................... 26
7.10.4 Use Common Sense ................................. 26
7.10.5 Caution When Entering A Building ........... 26
7.10.6 Fire Alarms ................................................. 26
7.11 FireReset/FireTrouble ...................................... 27
7.11.1 Fire Reset ................................................... 27
7.11.2 Fire Trouble ................................................ 27
7.12 Emergency KeypadAlarms............................... 27
7.13 Fire Safety ........................................................ 27
7.13.1 If Installed in Family Residences............... 27
7.11.3 Dirty Smoke ................................................ 27
7.14 Testing............................................................... 28
7.14.1 System Walk Test ....................................... 28
7.13.2 Having and Practicing an Escape Plan .... 28
7.13.3 Installation Considerations........................ 28
7.14.2 Fire Walk Test ............................................. 29
7.14.3 Battery/Sounder Test.................................. 29
7.14.4 Communicator Test .................................... 30
7.14.5 Event History Readback ............................ 30
7.14.6 Remote Program Dial-out and Answer..... 30
7.14.7 Error Displays/Warnings............................ 31
8.0 Keypads .................................................................. 32
8.1 TheMasterKeypad ........................................... 32
8.2 Master Keypad Displays ................................... 32
8.3 Arming from the Master Keypad........................ 32
8.4 Disarming from the Master Keypad ................... 33
8.5 Single Partition Mode ........................................ 33
8.6 Volume and Backlight Controls ......................... 33
9.0 How to Program the Control Panel ...................... 34
9.1 EnteringtheProgrammer’sMode ...................... 34
9.2 Reading back a Program Address..................... 34
9.3 Entering a value in a Program Address............. 34
9.4 HEX values ....................................................... 34
9.5 Defaults............................................................. 34
9.6 Setting the Control to the Factory Default ......... 34
9.7 ExitingtheProgrammer’sMode ........................ 35
10.0 Understanding the Programming Charts............. 35
11.0 Programming ......................................................... 36
11.1 GeneralControl Programming:Program Address
(0000) ................................................................ 36
11.2 ZoneFunction Programming:Program Addresses
(0001-0015) ....................................................... 37
11.3 ZoneProgramming: ProgramAddresses (0018-
0145) ................................................................. 38
11.4 Zone PartitionAssignment: ProgramAddresses
(1248-1311) ....................................................... 39
11.5 ZoneBypass Programming:ProgramAddresses
(0016-0017) ....................................................... 40
11.6 OutputProgramming: ProgramAddresses (0146-
0148) ................................................................. 41

DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 3
11.7 Output Partition Assignment: ProgramAddresses
(0149-0150) ....................................................... 42
11.8 PartitionControl Programming:ProgramAddress
(0165) ................................................................ 42
11.9 QuickArm ControlProgramming:Program
Address(0169).................................................. 43
11.10 KeypadAssignmentProgramming:Program
Addresses(0173-0180) ..................................... 44
11.11 Keypad PartitionAssignment: ProgramAddresses
(0208-0215) ....................................................... 44
11.12 EmergencyKey Programming:ProgramAd-
dresses(0181-0182).......................................... 45
11.13 CustomArming Programming:Program Ad-
dresses(0183-0184).......................................... 45
11.14 ForceArming and GroundFault DetectProgram-
ming:Program Address(0185).......................... 46
11.15 CommercialFire ModeProgramming: Program
Address(0186).................................................. 47
11.16 Open/CloseReport ControlProgramming: Pro-
gramAddress (0187)......................................... 48
11.17 Open/Close& ZoneReport ControlProgramming:
ProgramAddress (0189) ................................... 48
11.18 ReportControl Programming:ProgramAddress
(0190) ................................................................ 48
11.19 TimerProgramming: ProgramAddresses (0191-
0193,0195-0196) .............................................. 49
11.20 AC FailReportDelayProgramming:Program
Address(0197).................................................. 49
11.21 GeneralCode “ArmOnly”Programming:Program
Address(0198-0201) ......................................... 50
11.22 ArmingWarningProgramming: ProgramAd-
dresses(0202-0205).......................................... 50
11.23 DS7412RS232 InterfaceControl Programming:
ProgramAddress (0206) ................................... 51
11.24 DS7412RS232 InterfaceConfiguration Program-
ming:Program Address(0207) .......................... 51
11.25 ReportProgramming: ProgramAddresses(0256-
0304and0320-0340) ......................................... 52
11.26 Phone/ARDISRouting Control:Program Ad-
dresses(0494-0495).......................................... 54
11.27 AccountCode Programming:ProgramAddresses
(0496-0526) ....................................................... 55
11.28 PhoneNumberGeneralControlProgramming:
ProgramAddress (0528) ................................... 56
11.29 PhoneNumber FormatProgramming:Program
Addresses(0529-0530) ..................................... 56
11.29.1 Compatible Receivers ............................... 57
11.30 PhoneAnswering Programming:Program Address
(0531) ................................................................ 57
11.31 Programmer’sandMasterCodeProgramming:
ProgrammingAddresses (0532-0534) ............... 58
11.32 OctalRelayModule OutputProgramming: Pro-
gramAddresses (1456-1471) ............................ 58
11.32.1 Octal Relay Module Output Partition Assign-
ment: Program Addresses (3725-3732) ... 59
11.33 OutputFunction Programming:Program Ad-
dresses(1472-1516).......................................... 60
11.33.1 Output Function Partition Assignment:
Program Addresses (3733-3740) ............. 61
11.34 Dual Phone Line/Bell Supervision Module Output
Programming:Program Address(1520) ............ 61
11.35 Call-OutTimerProgramming:ProgramAddresses
(1521-1524) ....................................................... 62
11.36 Test ReportandRemote ProgrammerCall-Out
Programming:Program Address(1525) ............ 62
11.37 AlphaDescription Programming:Program Ad-
dresses(1526-3701).......................................... 63
11.38 PhoneNumber Programming:Program Addresses
(4028,4038, 4048) ............................................ 68
11.39 PagerDelayTime: ProgramAddress (3914)...... 68
12.0 Installation Guide for U.L. Listed Systems .......... 69
12.1 DS7400Xi U. L. Listings: .................................. 69
12.1.1 U.L System Configurations........................ 69
12.2 InstallationConsiderations ................................ 69
12.3 Programming theDS7400Xi .............................. 70
12.3.1 Household Fire Alarm using Digital Alarm
Communicator Transmitter with local bell . 70
12.3.2 Grade A Household Burglary Alarm using
Digital Alarm Communicator Transmitter with
local bell ..................................................... 70
12.4 GeneralSystem Requirements ......................... 70
12.4.1 Local Burglary Alarm ................................. 71
12.4.2 Police Station Connection ......................... 71
12.4.3 Central Station Burglary Alarm and Propri-
etary............................................................ 71
12.5 CommercialFireAlarm ..................................... 71
12.6 WiringandProgramming Informationfor Installa-
tions Using the Ademco AB-12 Bell/Housing .... 72
13.0 Report Programming............................................. 73
13.1 4/2 Format......................................................... 73
13.2 BFSK Format .................................................... 74
13.3 PersonalDialing andPager Format ................... 75
13.4 PagerFormat .................................................... 75
14.0 Report Programming - Values Sent...................... 77
14.1 SIA Formats...................................................... 77
14.2 CIDFormats...................................................... 79
15.0 Multiplex Zone Addressing Guide........................ 80
16.0 Troubleshooting Guide ......................................... 81
16.1 KeypadProblems .............................................. 81
16.2 ReportingProblems .......................................... 82
16.3 ZoneProblems.................................................. 82
16.4 General System Problems ................................ 83
17.0 ProgramAddresses............................................... 87
Index ................................................................................. 90

DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 4
1.0 Specifications
1.1 Enclosure Housing
The standard enclosure is manufactured from 20 Ga., cold-rolled
steel, and measures 12.5" Wide, by 14.5" High, by 3" Deep (31.8
cm x 36.8 cm x 7.6 cm). A keyed lock is included, and this enclo-
sure has provision for an optional tamper switch (required for com-
mercial burglary applications) for monitoring the door.
1.2 Temperature
• Storage and Operating Temperature: +32° to +120°F
(0° to +49°C)
1.3 Power
The total current output capacity for all auxiliary devices,
including keypads and smoke detectors = 1.5 A standby,
2.5 A alarm. The following ratings are maximum values.
The total combined output cannot exceed the max. load
current.
• Input power: 18 VAC, 50 VA, 50 Hz./60 Hz.
• Auxiliary regulated power: 12 VDC, 1.0 A max.
• U. L. Listed Auxiliary power: 12 VDC, 1.0 A max.
• U. L. Listed Alarm Power Output: 12 VDC, 1.75 A max.
• Auxiliary power voltage range: 12 V special application
• Optional Standby battery (P334): 12 V, 7.0 AH - 35 AH max.
• Control panel current draw: 175 mA, Standby
250 mA, Alarm
1.4 Outputs
• Alarm Output: 12 VDC, 1.75 A output. Can be
programmed for steady or pulsed
output.
• Programmable Output 1* Solid state current sink (1.0 A max.).
ShortstoAux. negative when activated.
Connect device toAux. power positive.
Can be used for alarm, arming state,
or access control.** This output is
generally programmable.
• Programmable Output 2* Solid state voltage source (500 mA
max.). Can be used for alarm, arming
state, or access control.**This output
is generally programmable. For use
with such compatible devices as the
Listed DS250 with a 4-wire base.
* = Current draw should be subtracted from either maximum
auxiliary or maximum alarm current draw.
** = Not investigated to the requirements of UL294.
1.5 Zones
• 8 on-board zones. Up to 128 total zones with expansion modules.
• Zone Response Time: 300 ms.
1.6 Keypads
• Maximum # of keypads: 15 Keypads
• Maximum wire length each: 1000 feet (305 m)
• Maximum wire length total: 6000 feet (1830 m)
in system
• Wire type: 4 conductor, unshielded, #22
AWG (0.8 mm) “Telephone
quad” or #18 AWG (1.0 mm)
quad wiring can be home-run
or daisy- chained.
No more than 2 keypads (#22 AWG) or 3 keypads (#18
AWG) are recommended on any 1000 foot (305 m) run.
Shared cable is not recommended for keypad, multiplex,
options bus, telephone, or siren wiring.
1.7 Communicator
Will report to two phone numbers with full single, double and back-
up reporting. Communicates in SIA (110 or 300 baud), 3/1, 3/1 Ext.,
3/1 with Parity, 3/1 Ext. with Parity, 4/1, 4/2, BFSK, Contact ID, Per-
sonal Dialing and Pager formats.
FCC Registration Number is ESVUSA-75333-AL-E
The ringer equivalence is 0.1B
Commercial Fire CSFM Listing Number is 7165-1062:111
Residential Fire CSFM Listing Number is 7167-1062:111
1.8 Partitions
The system has the capacity for 8 independent partitions. One par-
tition may be a common area.
1.9 Users
The DS7400Xi system allows up to 90 individual users. Each user
will have his own PIN number (the 4 digit code entered at the key-
pads) and his own authority level (to determine which functions he
may perform).
1.10 Lightning Protection
MOVs and spark gaps provide protection from lightning surges and
static discharges.
1.11 Burglar/Fire Zone Inputs
• Number of circuits: 8 Circuits on-board
• End-of-line resistor: 2.2 K Ω(P/N 25944, provided)
• Loop resistance tolerance: 60 ohms
1.12 Fire Signal Initiating Circuit (2-wire mode)
Fire circuit will work with 2- or 4-wire detectors and has optional
alarm verification.
• Number of circuits: 8 Circuits on-board
• Type of circuit: Class B, latching
• End-of-line resistor: 2.2 K Ω(P/N 25944, provided)
• Supervisory current: 5.5 mA
• Maximum short circuit current: 22 mA
• Maximum line resistance: 60 ohms
• Circuit voltage range: 8.5 to 14.1 VDC
• Total detector standby current: 2.5 mA
1.13 Multiplex Bus Wiring Requirements
• #22 AWG (0.8 mm). Up to 2000 feet (610 m) per system.
• #18 AWG (1.0 mm). Up to 5000 feet (1525 m) per system.
1.13.1 Multiplex Zone Loop Wiring
• Maximum wire length not to exceed 500 feet (150m) regardless
of the wire gauge.
1.14 Option Bus Wiring Requirements
• Maximum wire length 1000 feet (305 m) per home-run.
Do not use twisted pair or sheilded cable for
multiplex bus wiring.
IMPORTANT

DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 5
1.15 Max. Load Currents
Max. Current By Output: Not to exceed the max. load
currents listed above per column.
Option Power
Standby Alarm
U. L. Installations
Non-U. L. Applications
Aux. Power & Keypad (Combined)
Bell Output
Programmable Output 2
Loop Power +
1.5 A
2.0 A
1.0 A
1.0 A
X
500 mA
500 mA
2.5 A
2.5 A
1.0 A
1.0 A
1.75 A
500 mA
500 mA
Max. Load Currents
1.16 Backup Battery Calculation
• The following table is used to calculate the standby battery capacity required by NFPA when using the DS7400Xi:
1.17 Standby Current Load
• Battery AH - (20% Storage + 0.375 AH’s Alarm)
• The following table is the derated battery divided by hours minus the control standby (175 mA):
15 AH
7 AH
8 AH
14 AH
17.2 AH
21 AH
28 AH
30 AH
35 AH
Rechargeable
Battery Size Max. Standby
for 8 hours Max. Standby
for 24 hours Max. Standby
for 48 hours Max. Standby
for 60 hours Max. Standby
for 72 hours Max. Standby
for 80 hours
Max. Standby
for 4 hours
1.0 A
1.2 A
1.5 A
1.5 A
1.5 A
1.5 A
1.5 A
1.5 A
1.5 A
X
X
X
X
X
X
100 mA
120 mA
170 mA
470 mA
580 mA
1.1 A
1.2 A
1.5 A
1.5 A
1.5 A
1.5 A
1.5 A
X
X
X
X
X
X
130 mA
150 mA
200 mA
X
X
X
X
X
100 mA
190 mA
210 mA
280 mA
X
X
X
X
100 mA
160 mA
280 mA
310 mA
400 mA
X
X
270 mA
300 mA
380 mA
500 mA
740 mA
800 mA
970 mA
Device Quantity Standby Current
Per Device Total Standby Current
(Quantity x Standby
Current Per Device)
65 mA
10 mA
65 mA
127 mA
20 mA
Alarm Current
Per Device
65 mA
10 mA
80 mA*
127 mA
140mA
Total Alarm Current
(Quantity x Alarm
Current Per Device)
175 mA
1 175 mA 250 mA 250 mA
10 mA+ 40 mA** 10 mA + 40 mA**
7 mA
1 mA
1 mA
350 µA
350 µA
50 mA
1 mA
1 mA
350 µA
350 µA
20 mA 20 mA
75 mA
100 mA 75 mA
100 mA
10 mA 750 mAmax***
500 µA 560 µA
800 µA 800 µA
6 mA 35 mA
200 µA 200 µA
800 µA 800 µA
200 µA
200 µA
200 µA 200 µA
6 mA 35 mA
** = When calculatingStandby andAlarm Current for theOctal-Relay Module, use 10 mAplus 40 mAfor eachactivated relay.
Grand Total Grand Total
*** = Maximum current draw if using DS7400Xi panel power supply. Total of all outputs cannot exceed 750 mA.
DS7433 - 8 Input Direct
ARDIS Communications Module
DS7430 - Multiplex Expansion
DS7432 - 8 Input Remote
DS7420i - Dual Line/Bell Supervision
Control Panel
DS7450 & DS7452 - Contact Points
DS7460 - Dual Zone
DS7465 - Input/Output
DS7480 - Bell Supervision
DS7481 - Single Line Monitor
MX540 (DS7473) PIR Detector
MX835 TriTech Microwave/PIR Detector
MX775 (DS7470)PIR Detector
DS7457 - Single Zone Multiplex Input
MX794 (DS7474) PIR Detector
DS7445/DS7445i Keypad
DS7447/DS7447E Keypad
MX950 (DS7476)TriTech Microwave/PIR
2-Wire Smoke Detectors
Bells, Horns, etc.
Other sensors
Other
MX934 (DS7471) PIR Detector
MX938 (DS7472) Ceiling Mount PIR
DS7488 - Octal Relay*
DS7489 - Solid State Output Module
MX280 Series Multiplex Smoke Detectors
4-Wire Smoke Detectors
* = Add 15 mA for each additional zone in alarm.

DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 6
1.18 Options
•DS7412: RS232 Serial Interface module. The DS7412 module
allowsthe paneltosend event information, inanASCII
format, directly to a serial printer or computer. In
addition, the interface allows the direct connection of
a computer to the panel for programming via the
WDSRP programming software.
• Current Draw= 25 mA, 35 mA with LEDs on.
• DS7420i: Dual Phone Line/Bell Supervision Module (1 per
system).
The DS7420i allows the control to be used in NFPA
72 installations. It provides two supervised 12.0 VDC
signaling outputs, one Class A (Style D) input zone,
and dual phone line transmission and supervision.
• Current Draw = 20 mA, Standby. 140 mA, Alarm.
• DS7430: Multiplex Expansion Module (1 per system).
The DS7430 provides a two-wire multiplex bus for the
connection of additional remote zones. It also supplies
up to 200 mA for 4-wire multiplex devices such as the
DS7432.
• Current Draw = 65 mA, Standby. 65 mA, Alarm.
• DS7432: 8Input Remote Module (up to 15per system.Requires
a DS7430 Multiplex Expansion Module). The DS7432
providesameans of monitoring conventional Normally
Open or Normally Closed contacts. It reports their
status to the control panel as multiplex addresses. It
occupies eight multiplex zones on the system and can
monitor up to eight separate loops. It will support 4-
wire smoke detectors.
• Current Draw = 10 mA, Standby. 10 mA, Alarm.
• DS7433: 8 Input Direct Module (1 per system. Can not be used
with the DS7430 or DS7436 Multiplex Expansion
Modules).
The DS7433 provides a means of expanding the
system to include eight additional hard-wired zones.
Each zone can support up to twenty 2-wire smoke
detectors (can also support 4-wire smoke detectors).
• Current Draw = 65 mA, Standby. 80 mA,Alarm.Add
15 mA for each additional zone in alarm.
•DS7436: Multiplex Expansion Module (1 per system).
The DS7436 provides two two-wire multiplex buses
for the connection of up to 120 remote points. It also
supplies 200mA per bus.
• Current Draw = 130mA, Standby or Alarm
• DS7445/DS7445i: Control Station.
The DS7445/DS7445i is an LED keypad which has
LEDs representing the first 8 zones of the system. It
displays information on various control panel
functions. A built in sounder is used as an interior
warning device and to annunciate keystroke entries.
• Current Draw = 75 mA, Standby. 75 mA, Alarm.
• DS7447/DS7447E: Control Station.
The DS7447/DS7447E is an Alpha-Numeric LCD
keypad. It displays information on various control
panel functions. A built-in sounder is used as an
interior warning device and to annunciate keystroke
entries.
• Current Draw = 100 mA, Standby. 100 mA, Alarm.
• Keypad Access Output: The DS7447/DS7447E
Alpha Keypad will provide a ten (10) second access
relay output if equipped with the optional K800 Relay.
The relay will energize at the keypad if the user has a
master, unlimited, general, or access PIN.
The output will change only if the user has access to
thepartitionassigned to the keypad. SeetheDS7447/
DS7447E Keypad Installation Instructions (P/N
22235) for wiring information.
• DS7450: Flush Mount Single Multiplex Contact Point (requires
a DS7430 Multiplex Expansion Module).
The DS7450 is intended as a replacement for
conventional dry contacts, and to report an actual
multiplex address to the control panel. Occupies 1
zone.
• Current Draw = 350 µA, Standby. 350 µA, Alarm.
• DS7452: SurfaceMountSingleMultiplexContactPoint (requires
a DS7430 Multiplex Expansion Module).
The DS7452 is intended as a replacement for
conventional dry contacts, and to report an actual
multiplex address to the control panel. Occupies 1
zone.
• Current Draw = 350 µA, Standby. 350 µA, Alarm.
• DS7455: SurfaceMountSingleMultiplexContactPoint (requires
a DS7430 Multiplex Expansion Module).
The DS7455 is intended as a replacement for
conventional dry contacts, and to report an actual
multiplex address to the control panel. Occupies 1
zone.
• Current Draw = 350 µA, Standby. 350 µA, Alarm.
• DS7457: Single Zone Multiplex Input Module (requires a
DS7430 Multiplex Expansion Module).
The DS7457 provides a means of monitoring
conventionally Normally Open or Normally Closed
contacts. It reports their status to the control panel as
multiplex addresses. It occupies one multiplex zone
on the system and can monitor one loop. It also
includes a tamper loop.
• Current Draw = 350 µA, Standby. 350 µA, Alarm.
• DS7460: Dual Zone Module (up to 60 per system. Requires a
DS7430 Multiplex Expansion Module).
The DS7460 provides a means of monitoring
conventional Normally Open or Normally Closed
contacts. It reports their status to the control panel as
multiplex addresses. It occupies two multiplex zones
on the system and can monitor up to two separate
loops.
• Current Draw = 1 mA, Standby. 1 mA, Alarm.
• DS7465: Input/Output Module (up to 20 per system. Requires a
DS7430 Multiplex Expansion Module).
The DS7465 provides a Form “C” relay that may be
programmed to activate on system events, and an
input loop to monitor conventional Normally Open or
Normally Closed contacts. It reports their status to the
control panel as multiplex addresses.
• Current Draw = 1 mA, Standby.1 mA, with relay
energized.
• Occupies 2 zones.
• DS7480: Bell Supervision Module (1 per system).
The DS7480 provides a means of monitoring bells. It
provides a supervised (polarity reversing) output relay

DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 7
to activate the bell. It also provides a Form “C” Bell
Fault Output to be connected to the control panel.
• Current Draw = 7 mA @ 12 VDC, Standby. 50 mA@
12 VDC, Alarm.
• DS7481: Single Phone Line Monitor (1 per system).
The DS7481 provides a means of monitoring a single
phonelineforfaultconditions.Whenafaultisdetected,
the DS7481 automatically closes its Normally Open
relaycontactstoprovide a means of signaling the fault.
• Current Draw = 20 mA, Standby. 20 mA, Alarm.
• DS7488: Octal Relay Module (2 per system).
The DS7488 provides 8 Form “C” relay outputs for
addition to the system. The outputs are fully
programmableandcanbeactivatedby system events.
Eachoutputoperatesindividuallyoftheother7outputs
for complete flexibility.
• Current Draw = 10 mA + 40 mAfor each relay when
energized.
• DS7489: Solid State Output Module (2 per system).
The DS7489 is a Solid State Octal Driver Module that
provides 8 open collector transistor outputs. The
outputs are fully programmable and can be activated
by system events. Each output operates individually
of the other 7 outputs for complete flexibility. The
DS7489 Module has not been investigated by
Underwriters Laboratories, Inc.
• Current Draw: 10mA.
• Outputs: Provides a current sink (the output shorts
to common (-) when activated). The maximum current
draw for all 8 outputs combined cannot exceed 750
mA.
•MX280: Multiplexed Photoelectric Smoke Detector (up to 120
detectorsmaybeusedper system. Requires a DS7430
and occupies one multiplex zone). Detects smoke and
automatically determines the detector’s sensitivity
usingtheDetectionSystems “Chamber Check” feature.
The MX280 Detector has not been investigated by
Underwriters Laboratories, Inc.
• Current Draw: 500 µA Standby, 560 µA Alarm.
•MX280TH: MultiplexedPhotoelectricSmokeDetectorwitha135°F
(57° C) heat sensor (up to 120 detectors may be used
per system. Requires a DS7430 and occupies one
multiplex zone). Detects smoke and is equiped with a
135°F(57°C)heatsensorforhightemperaturealarms.
The Detection Systems “Chamber Check” feature
automaticallydeterminesthedetector’ssensitivity. The
MX280TH Detector has not been investigated by
Underwriters Laboratories, Inc.
• Current Draw: 500 µA Standby, 560 µA Alarm.
•MX280THL: Multiplexed Photoelectric Smoke Detector with a
135°F (57° C) heat sensor and a 45°F (7° C) freeze
alarm (up to 60 detectors may be used per system.
Requires a DS7430 and occupies two multiplex
zones). Detects smoke and is equiped with a 135°F
(57° C) heat sensor for high temperature alarms and
a 45°F (7° C) sensor for freeze alarms. Freeze alarms
are reported separately from smoke and high
temperaturealarms.The Detection Systems “Chamber
Check”featureautomaticallydeterminesthedetector’s
sensitivity. The MX280THL Detector has not been
investigated by Underwriters Laboratories, Inc.
• Current Draw: 500 µA Standby, 560 µA Alarm.
• MX540: Multiplexed Passive Infrared (PIR) Intrusion Detector
(DS7473) with a standard range of 40 by 50 feet (12 by 15
meters). Requires a DS7430 and occupies one
multiplex zone.
• Current Draw = 800 µA Standby and Alarm.
• MX835: TriTech Microwave/PIR Intrusion Detector with “Pet
Avoidance” technology and a standard range of 35 by
35 feet (10.7 by 10.7 m). Requires a DS7430 and
occupies one multiplex zone.
• Current Draw= 6 mA standby, 35 mA in “Trouble”
and walk test mode.
• MX775 MultiplexPassive Infrared (PIR) Intrusion Detector with
(DS7470) a standard range of 50 by 50 feet (15m by 15m).
Requires a DS7430 and occupies one multiplex zone.
• Current Draw= 200 µA standby, 2 µA in walk test
mode.
•MX794 The MX794 is a Long Range Multiplex PIR Intrusion
(DS7474) Detector with Self-test. The standard ranges are 80 ft.
by 50 ft. (24.0m by 15.0m) and 200 ft. by 10 ft. (61.0 m
by 3.1 m). Requires a DS7430 and occupies one
multiplex zone.
• Current Draw = 800 µA Standby and Alarm.
•MX934 MultiplexPassiveInfrared (PIR) intrusion detector with
(DS7471) a standard range of 35 by 35 feet (10.7m by 10.7m).
Requires a DS7430 and occupies one multiplex zone.
• Current Draw= 200 µA standby, 2 µA in walk test
mode.
•MX938 360° Ceiling Mount Multiplex PIR Intrusion Detector
(DS7472) with a 60 foot (18.3m) diameter range. Requires a
DS7430 and occupies one multiplex zone.
• Current Draw= 200 µA standby, 2.5 µA in walk test
mode.
• MX950 Multiplex TriTech Microwave/PIR Intrusion Detector
(DS7476) with motion monitor and anti-mask features and with
a standard range of 50 by 50 feet (15m by 15m).
Requires a DS7430 and occupies one multiplex zone.
• Current Draw= 6 mA standby, 35 mA in “Trouble”
and walk test mode.
• ARDISSM Communications Module. Various model numbers.
The Communications Module provides a means of
communicating alarm and supervision signals using
the ARDIS radio network. This can be a replacement
for, or a compliment to, the standard digital
communicator.
• Current draw: 127 mA Standby and Alarm.
The control/communicator is also available in three package
formats. The packages include the following:
• DS7400XiF: DS7400Xi in large red enclosure (manufactured
from 18 Ga., cold-rolled steel, and measures 15.0"
Wide, by 20.75" High, by 4.25" Deep (38.1 cm W, by
52.7 cm H, by 10.8 cm D)).
• DS7400XiFCP:DS7400XiF package with: DS7420i, DS7447/
DS7447E and a AE-TR16
• DS7400XiCC: DS7400Xi in an Attack Enclosure.
When installing a U. L. Listed system,
refer to the Installation Guide for U. L. Listed Systems.
See Section 12.0.

DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 8
2.0 Enclosure Installation
The DS7400Xi control/communicator and the enclosure are shipped
together. The control, however, still needs to be installed into the
enclosure. Hardware for mounting the enclosure to a wall, and the
control to the enclosure is located in its own hardware pack.
2.1 Install the Enclosure
• Use the enclosure as a template and mark the top mounting holes
on the mounting surface.
• Pre-start the mounting screws for these two holes. Slide the en-
closure onto these mounting screws so that the screws move up
into the thinner section of the holes. Tighten the screws.
• Screw in the remaining two screws in either set of bottom mount-
ing holes.
• Knock out the desired wire entrances on the enclosure.
2.2 Install the Control/Communicator
The control is static sensitive. Make sure you touch
earth ground before handling the control. This will dis-
charge any static electricity in your body. Example:
Run the ground wire to the enclosure before handling
the control. Then keep holding the ground wire while
installing the control.
• Insert the three support posts into the control retainer holes as
shown in the diagram.
• Slide the top of the control into the retainer tabs (the slots under
the top frame).
• Once in the retainer tabs, the control will rest on the three support
posts.
• Secure the bottom of the enclosure by screwing the bottom three
holes through the support posts and through to the control re-
tainer holes.
Once the control is installed, be sure to connect its
ground wire to the top hinge of the enclosure (the
unpainted tab).
C
ircuit board
Enclosure
Support Post Assembly Control/Communicator
Ground Wire
Progra
m
Pads
Retainer Tabs
Control Retainer Holes (3 places)
Wire Entrances (6)
Enclosure
Ground Tab
Flip-up view to show retainer tabs
Support Posts
IMPORTANT
NO STATIC

DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 9
3.0 Control Terminal Wiring
NO
Typical burglar
alarm loop wiring
Z– L+
Typical 2-wire
smoke detector
wiring
Z– L+
Alarm
Power
++
–
Loop +
or PO2
Zone
Input Aux. Power (—)
(terminal 5 or 7)
–
Alarm
Power
++
–
Typical 4-wire smoke
detector wiring.
For example:
Detection Systems’
DS250 in an MB4W base.
End-of-Line
Supervision Relay
(e.g. Detection Systems’
EOL200)
Z– L+
Loop +Zone
Input
Loop +Zone
Input
in out
in out
NC
TYPICAL BURGLAR AND FIRE WIRING
(for a list of
compatible 2-wire
smoke detectors,
see Technical Service
Note P/N 27685)
EARTH GROUND: Must be connected to
a good earth ground such as a cold water
pipe and also connected to the cabinet cover,
using the supplied wire jumper.
ALARM OUTPUT:
Provides 12 VDC, special application, up to
1.75 A for powering bells, siren drivers, etc.
Function programmed in address 0146.
AC INPUT: Use U. L. listed, 18 VAC 50
VA, class 2 transformer. Model TR-1850
requires 50/60 Hz. unswitched dedicated
outlet - do not share.
1
2
3
4
5
6
7
8
A
C
–
A
–
+
AUXILIARY POWER:
Provides 12 VDC, special application, up to
1.0 A for powering detectors.
A/C Power Indication LED
OPTION BUS:
Used for options such as the ARDIS
communications module, the DS7420i Dual
Phone Line module, etc.
Also for keypads #11 - #15.
For Commercial Fire Mode: Option Bus wiring
should be in conduit if run ouside the
enclosure.
O
P
T
I
O
N
R
B
G
Y
Shared cable is not recommended for keypad,
multiplex, options bus, telephone, or siren wiring.
ZONES 1-8: Zones 1-8 are intended for connection of Normally
Open or Normally Closed alarm contacts.They may also be used
for compatible 2-wire smoke detectors.These zones require a
2.21KΩresistor (P/N 25899) at the end of the loop. Power is
momentarily removed from L+ after a [PIN] + [System Reset] or
during a fire verification.
Zone 1-8 assignments are programmed in address 0018-0025.
17 18 19 20 21 22 23 24 25 26 27 28 29 30
PO1 PO2 1– L+ 2– 3– 5– 6– 7– 8–4–
L+ L+ L+
PROGRAMMABLE OUTPUTS:
PO1 shorts to aux. power negative when activated, PO1 can sink up to 1.0 A.
PO1 function programmed in address 0147.
PO2 supplies 12 V and up to 500 mA when activated.
PO2 function programmed in address 0148.
KEYPAD BUS*:
Up to 15 keypads**
may be used. Can be
“home-run” or
“daisy-chained.”
910 11 12 13 14 15 16
RBGYGBSR
Keypad
(#1 - #10)
PHONE LINE:
* = Maximum wire length each: 1000 ft. (305 m).
Maximum wire length total in system: 6000 ft. (1830 m) when using
#22 AWG (0.8 mm) or #18 AWG (1.0 mm) cable.
** = Keypads #1 - #10 connect to the Keypad Bus and keypads #11 - #15
connect to the Option Bus.
TTHRHR
Keypad
(#1 - #10)
An appropriate two pole disconnect device must be installed
by qualified service personnel, as part of the building installation.
Before servicing, remove all power
including the transformer, battery and
phone line.A complete functional test
is required after any programming.
WARNING
System is Power Limited except for
battery terminals.All wiring entering
this enclosure must be power limited.
Incorrect connections may
result in damage to the unit.
CAUTION
Danger of explosion if battery is incorrectly replaced.
Replace with the same or equivalent type
recommended by the manufacturer.
Dispose of used batteries according to the
manufacturer's instructions.
CAUTION
CAUTION
NOTE

DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 10
4.0 Hardware Layout Example
Armed
Status
Powe r
Fire
123
456
789
0
*#
On
No
Entry
Syste m
Reset
Bypa ss
Only
Perimeter
Off
Perimeter
Supervisory
Bell Sile nced
Trouble
12345678 ®
DS7488 Octal
Relay Board
DS7400Xi
+–+–
Power Bus
DS7420i Dual Phone
Line/Bell Supervision
Module
DS7447/DS7447E and
DS7445/DS7445i Keypads
R
ARDIS Interface Module
DS7450, DS7452 & DS7455 Series Contacts,
DS7460 Input Modules, DS7465 Input/Output
Modules, MX540, MX775, MX794, MX835, MX934
,
MX938, and MX950 motion detectors and MX28
0
Smoke Detectors
DS7430
Keypads #11 - #15 must be connected to
the Options Bus. Keypads #1 - #10 must
be connected to the Keypad Bus.
®
Note: Ensure at least 1/4" separation
between battery wires and all
other cabling.
Armed
Status
Power
Fire
123
456
789
0
*#
On
No
Entry
System
Reset
Bypa ss
Only
Peri mete r
Off
®
Armed
Status
Power
Fire
123
456
789
0
*#
On
No
Entr y
Syste m
Reset
Bypa ss
Only
Perimeter
Off
®
Armed
Status
Power
Fire
123
456
789
0
*#
On
No
Entry
System
Reset
Bypa ss
Only
Peri mete r
Off
®
Armed
Status
Power
Fire
123
456
789
0
*#
On
No
Entry
System
Reset
Bypa ss
Only
Peri mete r
Off
®
Armed
Status
Power
Fire
123
456
789
0
*#
On
No
Entry
System
Reset
Bypa ss
Only
Peri mete r
Off
®Armed
Status
Powe r
Fire
123
456
789
0
*#
On
No
Entry
Syste m
Reset
Bypa ss
Only
Perimeter
Off
Perimeter
Supervisory
Bell Sile nced
Trouble
12345678 ®
Armed
Status
Powe r
Fire
123
456
789
0
*#
On
No
Entry
Syste m
Reset
Bypa ss
Only
Perimeter
Off
Perimeter
Supervisory
Bell Sile nced
Trouble
12345678 ®
B
G
Y
–+––
–
–
Option
Bus
Battery
Bell Output
Auxiliary
Output
+
–++
+
–
+
–
G
R
B
1
2
3
4
5
6
7
8
9
10
Y
11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
Battery Battery
RTRT TTRR TRTR
DS7432 8 - Input
Remote Modules
47K
Dry contact inputs
+–+–12345678
POWER BUS
+–+–12345678
POWER BUS
+–+–12345678
POWER BUS
+–+–1234567 8
POWER BUS
12345
2G1-+
BUS
NO
+
123
CNC
• Up to 15 keypads may be used. Keypads #1 - #10 connect to the Keypad Bus and Keypads #11 - #15
connect to the Option Bus. One keypad must be designated as keypad #1 and connected to the Keypad
Bus. See the DS7447 and DS7445 Installation Instructions for further details.
• A DS7420i (Dual Phone Line/Bell Supervision Module) may be connected to the control panel, and
placed within the enclosure. Connect to the Options Bus of the control panel. See the DS7420i Installation
Instructions for further details.
• A DS7430 (Multiplex Expansion Module) may be connected to the control panel via the expansion port.
This will allow for the connection of additional zones. See the DS7430 Installation Instructions for further
details.
• Up to 15 DS7432s (8 Input Remote Modules) may be connected to the DS7430. Connect to the Power
and Bus terminals of the DS7430. This allows for a means of addressing up to 120 input loops of conventional
contacts to the control panel. See the DS7432 Installation Instructions for further details.
• A DS7488 (Octal Relay Module) may be connected to the control panel, and placed within the enclosure.
Connect to the Options Bus of the control panel. This provides an additional 8 Form “C” relay outputs for
the control panel. See the DS7488 Installation Instructions for further details.
• ACommunications Module may be connected to the control panel via the Options Bus. This allows for connection
to the ARDIS radio network.
• Up to 128 zones are available for the connection of Single, Multiple, Input/Output, and Multiplex devices.
• A DS7436 (Multiplex Expansion Module) may be connected to the control panel via the expansion port.
This will allow for the connection of additional zones. See the DS7436 Installation Instructions for further
details.
123
456
789
0
*#
On
No
Entry
System
Reset
Bypass
Only
Perimeter
Off
TEST WEEKLY
12345678
91011121314 15 16
Armed
Status
Power
Fire
Perimeter
Supervisory
Bell Sile nced
Trouble
123
456
789
0
*#
On
No
Entry
System
Reset
Bypass
Only
Perimeter
Off
TEST WEEKLY
12345678
91011121314 15 16
Armed
Status
Power
Fire
Perimeter
Supervisory
Bell Sile nced
Trouble
123
456
789
0
*#
On
No
Entry
System
Reset
Bypass
Only
Perimeter
Off
TEST WEEKLY
12345678
91011121314 15 16
Armed
Status
Power
Fire
Perimeter
Supervisory
Bell Sile nced
Trouble

DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 11
5.0 System Worksheet
Account Number Information
Name Contact Person
Address Voice Phone Number
Panel Phone Number
City, State, Zip Panel Answers Phone Armed Disarmed
Equipment Location and Notes
A
C Voltage VAC Battery Voltage VDC AUX Current A
B
attery Standby AH Bell Current A
C
ontrol Panel
T
ransformer
T
elephone Jack
T
elephone On Same Line as Panel
E
arth Ground Connection
A
larm Sounder (s)
Misc. Notes
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
Keypad Location and Notes
Example
Location Belongs Master/
to Partition Standard
Keypad # 1 Kitchen 2 Master
Location Belongs Master/ Location Belongs Master/
to Partition Standard to Partition Standa
rd
Keypad # 1 Keypad # 9
Keypad # 2 Keypad # 10
Keypad # 3 Keypad # 11
Keypad # 4 Keypad # 12
Keypad # 5 Keypad # 13
Keypad # 6 Keypad # 14
Keypad # 7 Keypad # 15
Keypad # 8

DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 12
5.0 System Worksheet (continued)
PIN Information
User Pin # Auth. Parti- Name
#Level tions
001
002
003
004
005
006
007
008
009
010
011
012
013
014
015
016
017
018
019
020
021
022
023
024
025
026
027
028
029
030
PIN Information
U
ser Pin # Auth. Parti- Name
#Level tions
Personal Identification Number Information
Example
002 1001 6 1, 2, 4 James L.
061
062
063
064
065
066
067
068
069
070
071
072
073
074
075
076
077
078
079
080
081
082
083
084
085
086
087
088
089
090
PIN Information
User Pin # Auth. Parti- Nam
e
#Level tions
031
032
033
034
035
036
037
038
039
040
041
042
043
044
045
046
047
048
049
050
051
052
053
054
055
056
057
058
059
060
PIN Information
User Pin # Auth. Parti- Name
#Level tions

DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 13
5.0 System Worksheet (continued)
Example
Type * Zone/Output Partition & Location
Function #
Zone # 1
Zone Location and Notes
Zn Funct. 1
Type * Zone/Output Partition & Location
Function #
Zone # 1
Zone # 2
Zone # 3
Zone # 4
Zone # 5
Zone # 6
Zone # 7
Zone # 8
Zone # 9
Zone # 10
Type * Zone/Output Partition & Locatio
n
Function #
Zone # 31
Zone # 32
Zone # 33
Zone # 34
Zone # 35
Zone # 36
Zone # 37
Zone # 38
Zone # 39
Zone # 40
2, KitchenSZ
* = SZ: Single Zone Input
MZ: Multiple Zone Input
IO: DS7465
(see section 11.2)
Zone # 41
Zone # 42
Zone # 43
Zone # 44
Zone # 45
Zone # 46
Zone # 47
Zone # 48
Zone # 49
Zone # 50
Zone # 51
Zone # 52
Zone # 53
Zone # 54
Zone # 55
Zone # 56
Zone # 57
Zone # 58
Zone # 59
Zone # 60
Zone # 11
Zone # 12
Zone # 13
Zone # 14
Zone # 15
Zone # 16
Zone # 17
Zone # 18
Zone # 19
Zone # 20
Zone # 21
Zone # 22
Zone # 23
Zone # 24
Zone # 25
Zone # 26
Zone # 27
Zone # 28
Zone # 29
Zone # 30

DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 14
5.0 System Worksheet (continued)
Type * Zone/Output Partition & Locatio
n
Function #
Zone # 95
Zone # 96
Zone # 97
Zone # 98
Zone # 99
Zone # 100
Zone # 101
Zone # 102
Zone # 103
Zone # 104
Zone # 105
Zone # 106
Zone # 107
Zone # 108
Zone # 109
Zone # 110
Zone # 111
Zone # 112
Zone # 113
Zone # 114
Zone # 115
Zone # 116
Zone # 117
Zone # 118
Zone # 119
Zone # 120
Zone # 121
Zone # 122
Zone # 123
Zone # 124
Zone Location and Notes (continued)
Type * Zone/Output Partition & Location
Function #
Zone # 61
Zone # 62
Zone # 63
Zone # 64
Zone # 65
Zone # 66
Zone # 67
Zone # 68
Zone # 69
Zone # 70
Zone # 71
Zone # 72
Zone # 73
Zone # 74
Zone # 75
Zone # 76
Zone # 77
Zone # 78
Zone # 79
Zone # 80
Zone # 81
Zone # 82
Zone # 83
Zone # 84
Zone # 85
Zone # 86
Zone # 87
Zone # 88
Zone # 89
Zone # 90
Zone # 125
Zone # 126
Zone # 127
Zone # 128
Zone # 91
Zone # 92
Zone # 93
Zone # 94

DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 15
6.0 Glossary
6.1 General Control Programming
• Normal Arming - [PIN] + [On]: If programmed, arms the entire
system while allowing entry delays for entry/exit zones.
• Perimeter Instant Arming - [PIN] + [No Entry] [Perimeter Only]:
If programmed, arms only the perimeter of the system and does
not allow entry delays for entry/exit zones.
• Perimeter Arming - [PIN] + [Perimeter Only]: If programmed,
arms only the perimeter of the system while allowing entry delays
for entry/exit zones.
•Custom Arming - [PIN] + [#] [4]: If programmed, allows custom
arming of the system and bypasses the zone functions specified
in data address 0183.
•Maximum Security Arming - [PIN] + [No Entry] [On]: If
programmed, arms the entire system and does not allow an entry
delay for entry/exit zones.
• General “Arm-Only” Authority by Partition
A general (level 2) authority can be programmed to have arm-
only authority by partition. This is done at addresses 0198 and
0199.
- Arm-only access by partition allows someone with a General
Authority to arm and/or bypass zones in a partition he can not
disarm.
- This level can still be used to arm, disarm, and bypass zones in
the other partitions that it has access to.
•Closing Ring-Back: If programmed, the keypad sounders and
Bell will activate for 2 seconds after the system is armed and the
closing report is successfully sent. This requires Closing Ring-
Back and Closing Report to be programmed.
- If a closing report is not programmed, the control will test for a
dial tone when the system is armed. If the test passes, the
system will arm normally. If the test fails, the system will arm,
but will indicate a trouble condition.
- The DS7447/DS7447E keypad will display “Communication
Err” after [#] [8] [7] is entered.
•Siren on Comm. Fail for Silent Zone: If programmed, a silent
zone will sound the alarm outputs if the zone is in an alarm
condition and the system fails to communicate with the central
station.
•Restore when Sounders Silence: If programmed, a zone sends
a restoral report and is ready to activate again only after the
burglary bell cut-off time expires or the bells are silenced.
- The zone can alarm multiple times per armed period.
•Restore when Zone Restores: If programmed, a zone sends a
restoral report and is ready to activate again as soon as it
physically restores.
- This zone can alarm multiple times per armed period.
•Restore when System Disarms: If programmed, a zone sends
a restoral report when the system is disarmed.
- It can only alarm once per armed period.
•Allow Swinger Shunts: If programmed, a zone can only alarm
or trouble up to three times per armed period.After the third alarm
or trouble, the zone will be bypassed and a trouble report will be
sent.
6.2 Zone Function Programming
• Zone Function
A Zone Function is the description of how a particular zone will
behave (e.g. steady alarm output, bypassing allowed, alarm on
short, trouble on open, perimeter instant).
- Zone functions may be custom made, but 8 default zone
functions already exist.
- There are many possible zone functions, but only up to 15
different zone functions are allowed per control.
- Each zone must be programmed as a specific zone function.
Any number and combination of zones may be programmed as
particular zone functions.
•Invisible Alarms: This is a zone programmed not to have an
alarm output or an alarm display at any keypad when activated.
An alarm signal will be sent, but the DS7447/DS7447E keypad
display will read “Not Ready” while this zone is violated.
- Invisible Alarm zones are recommended for holdup alarms.
•Silent Alarms: This is a zone programmed to activate the visual
display at the keypad, but not audible signals.
- If this zone is also an entry zone, an entry tone will sound when
this zone is activated.
• Bypassing Allowed: This is a zone programmed to allow
bypassing (shunting). This is done using the bypass command or
the force-arming sequence.
•Alarm on Short: This is a zone programmed to activate an alarm
when its loop is shorted.
•Alarm on Open: This is a zone programmed to activate an alarm
when its loop is opened.
•Trouble on Open: Thisisazoneprogrammedtoactivateatrouble
when its loop is opened and the system is disarmed.
- If the system is armed, this zone will activate an alarm if shorted
or opened.
- For 24-hour zones, regardless of the arming state of the panel,
this always remains as a Trouble on Open.
•Trouble on Short: Thisisazoneprogrammedtoactivateatrouble
when its loop is shorted and the system is disarmed.
- If the system is armed, this zone will activate an alarm if shorted
or opened.
- For 24-hour zones, regardless of the arming state of the panel,
this always remains as a Trouble on Short.
•Interior Delayed: Thisisazoneprogrammedtobeignored during
the entry/exit delay period. If it is violated when the system is
armed, it will activate a delay for the programmed entry delay
time. The keypad pre-alert sounders will activate and the system
may be disarmed during this delay period. If the system is not
disarmed during this delay period, this zone will activate an alarm.
This zone is bypassed by Perimeter Instant or Perimeter Armed.
•Perimeter Instant: This is a zone programmed to activate an
alarm even during the entry/exit delay period.
•24-Hour: This is a zone programmed to activate when its loop is
faulted, even if the system is disarmed.
• Entry/Exit Delay #1: This is a zone programmed to be ignored
during the entry/exit delay period.
- If it is violated while the system is armed, it will activate a delay
for the amount of time programmed for entry delay time #1
(address0191).The keypadpre-alertsounders will activate and
the system may be disarmed during this delay period.
- If the system is not disarmed during the entry period, this zone
will activate an alarm.
• Entry/Exit Delay #2: This is a zone programmed to behave
identical to the Entry/Exit Delay #1 zone function except that it
uses entry delay time #2 (address 0192).
If both entry delays have been activated, the control will
use the shorter entry delay.

DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 16
• Entry/Exit Delay Cancel Zone Functions
Entry/Exit Delay Cancel 1 and Entry/Exit Delay Cancel 2 Zone
Functions cause the exit delay to expire as soon as the premises
is vacated.
- If a zone is programmed as an Entry/Exit Delay Cancel zone,
and it is activated during the exit delay, the exit delay will expire
as soon as the zone has been restored.
- Entry/Exit Delay Cancel 1 follows entry delay 1.
- Entry/Exit Delay Cancel 2 follows entry delay 2.
- They are programmed at addresses 0001-0015.
•Interior Entry/Exit Follower: This is a zone programmed to be
ignored during an entry/exit delay and then become an interior
instant zone.
- If this zone is violated while the system is armed and no entry/
exit zones have been violated, it will activate an alarm.
- If this zone is violated after an entry/exit delay zone is violated,
it will follow that entry/exit delay time.
- ThiszoneisbypassedbyPerimeterInstantorPerimeterarming.
•Interior Home/Away: This is a zone programmed to become an
interior instant zone if the system is armed and an entry/exit delay
zone is violated during the exit delay time.
- If the system is armed and an entry/exit delay zone is not
violated, this zone will be bypassed.
- ThiszoneisbypassedbyPerimeterInstantorPerimeterarming.
•Interior Instant: This is a zone programmed to activate an alarm
even during the entry/exit delay periods.
- It is bypassed by Perimeter Instant or Perimeter arming.
•Day Monitor: Thisisa zone programmed to be a perimeter instant
zone when the system is armed.
- When the system is disarmed, any violation of this zone will
activate the keypad sounders which will sound continuously
until a disarm command sequence is entered.
- The alarm outputs for this zone will not activate and there will
be no report for this zone when the system is disarmed.
•Keyswitch Input: This is a zoneprogrammedtoallow the system
to be armed or disarmed using a Normally Open momentary
keyswitch.
- Outputs for keyswitch LEDs and sounders are available using
the programmable outputs or the Octal relay outputs.
- An output is needed for each LED and sounder.
- A keyswitch will only control the partition that these zones are
assigned to unless programmed as a master, then they will
control all at once. See Program Address 0001, Data Digit 1.
- Keyswitches and keypads may be used in the same partition, if
desired.
•Fire Zone: This is a zone programmed to activate if the system is
armed or disarmed.
- It can be silenced (not reset) by entering a valid [PIN] + [Off].
- Thedisplaywill indicate a FireAlarm for thiszone onallkeypads
in every partition.
- Afire reset command must be entered after silencing the alarm
to re-enable this zone.
- If this zone is programmed for trouble and the loop opens, the
DS7447/DS7447E keypad will display “Fire Trouble” and
“Control Trouble”. The keypad sounders will also beep once
every ten seconds.
- If the system is a combination fire and burglar alarm, the fire
alarm has priority over the burglar alarm.
• Fire Zone with Verification: This zone is identical to a Fire Zone
except that after the first alarm, it will perform a fire reset and
then wait up to two minutes for a second alarm.
- If a second alarm occurs within this two minute period, the
system will indicate a fire alarm.
- If there is no second alarm within this two minute period, the
control panel will reset back to its normal condition.
Use of this control’s alarm verification feature is not
permitted for applications in the state of California.
•Water Flow Zone: This is a zone programmed to operate like a
Fire Zone, but is specifically intended for water flow switches.
- An optional retard timer can be programmed to compensate
for changes in water pressure. If the timer is used, the water
flow zone must be activated for the complete time period; an
alarm will be initiated at the end of the timer period.
- The maximum combined water flow delay of the control panel
and the device must not exceed two minutes.
Any zone can be a water flow zone, but only zones 1
through 4 may be programmed as delayed water flow
zones.
•Supervisory Zone: This is a zone programmed to accommodate
shut-off valves.
- It will indicate a supervisory condition at the keypads when
activated.
6.3 Zone Programming
• Zone
A Zone is an input to the DS7400Xi Control/Communicator.
- There are 8 hardwired zones on the main circuit board.
- Additional zones may be added by using the DS7433 (8 zone
expansion module), the DS7430 (multiplex loop module), and/
or other modules.
•Single Zone Input: This is an individual zone such as the on-
board zones and multiplex contact zones.
•Multiple Zone Input: This is a zone connected to one of the 8-
Input Modules (DS7432 or DS7433) or to a Dual Zone Module
(DS7460).
- The inputs are programmed separately (see the separate
Programming Addresses Worksheet, P/N 29802).
- When using the Dual Zone Module (DS7460), loop A is always
programmed as an odd numbered program address (ending in
1, 3, 5, 7, or 9). Loop B is the even numbered program address
that follows loop A.
• DS7465: This is the input zone or the output relay on a DS7465.
Theoddnumberedzoneisprogrammedfortheinputzonefunction
and the even numbered zone is programmed for the output
function.
•Multiplex Smoke: This is a multiplexed input zone (zones 9-128)
that is used with a MX280 series smoke detector. This zone must
have a Zone Function of Fire Zone and Trouble on Open applied
to the multiplex smoke zone.
•Multiplex Smoke with Low Temperature: This zone is used with
the MX280 series smoke detectors with a low temperature alarm.
Making this selection requires the programming of two zones as
follows:
-Smoke Alarm. This must be the odd numbered zone of the
zone pair required for these devices. The zone must be
programmed with a zone function that is set for Fire Zone and
Trouble on Open.
-Low Temperature Alarm. This must be the even numbered
zone of the zone pair required for these devices. This zone
must be programmed with a zone function that is set as
Supervisory and Trouble on Open.

DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 17
6.4 Output Programming
•Latch on Any Zone Alarm: This is an output programmed to
activate upon any zone alarm (including invisible zones) and will
latch until the system has been disarmed.
- If this output responds to a fire zone, it will remain latched until
the fire reset command is performed.
•ON during Entry Pre-Alert: This is an output programmed to
activate when an entry/exit zone is violated while the system is
armed.
- It will remain activated until the system is disarmed, or until the
entry delay time has expired.
• ON for 10 seconds after [PIN] + [System Reset] is entered: This
is an output programmed to activate for 10 seconds after the fire
reset command is entered at the keypad or if a Fire Zone with
Verification activates.
- This output is intended to be used to power 4-wire smoke
detectors or any other device that requires a power interruption
to reset an alarm condition.
When Programmable Output 2 is programmed this way, it
will normally supply auxiliary power and will turn OFF for
10 seconds when the fire reset command is entered.
•ON when System is Armed: This is an output programmed to
activate when the system is armed.
•Armed Full: If selected, only fully arming the system will acti-
vate the output.
•Armed Partial: If selected, only the following arming condi-
tions will activate the output: arming with bypasses, custom
arming, force arming, any form of partial arming and perimeter
arming.
•Armed Any: If selected, any arming state will activate the out-
put.
- The output will remain activated until the system is disarmed.
•Ground Start: This is an output programmed to activate for 3
seconds when the phone line is seized. It is intended for use with
ground start phone systems that require a momentary short to
ground to obtain a dial tone.
- Connect a separate 12 VDC, DPDT relay.
- Connect both relay contact commons to ground, and connect
the Normally Open of each contact to terminal positions 13
and 16 (one to terminal 13, the other to 16) of the DS7400Xi.
- This output follows all partitions regardless of how data digit 2
of the output programming address is programmed.
- Not intended for U. L. Listed systems. Not for use with phone
line monitors.
•System Status (ready to arm): This is an output programmed to
follow the Status LED of the keypad.
- It will activate when the system is ready to arm with no zones
violated.
•Zone Alarm: This is an output programmed to activate when a
zone is in an alarm condition.
- It will remain activated until the system is disarmed or the bell
cut-off time expires.
- This output is intended to activate alarm bells and sirens.
- This will not activate from Silent or Invisible Zones.
•Zone Alarm Delayed by 20 sec.: This is an output programmed
to wait 20 seconds after a zone enters an alarm condition to
activate.
- It will remain activated until the system is disarmed or the bell
cut-off time expires.
- This output is intended to activate alarm bells and sirens, but
provides a delay to allow the user to silence the system before
it activates.
• Output Functions
Output Functions can be programmed to follow system events or
to follow one or two specific zones in a “cross-matrix” fashion
(see Input/Output Cross-Matrixing).
- These Output Functions can be programmed to control Octal
Relay outputs or Multiplex Bus outputs.
- Output Functions are programmed at addresses 1472 - 1516.
• Input/Output Cross Matrixing
Input/Output Cross Matrixing allows Output Functions to follow
the status of specific input zones (zones 1 through 99 only).
- Outputs can be programmed to follow any combination of one
or two zones, open or closed, with the system armed or
disarmed.
- If programmed to latch, the output will latch until a valid PIN is
entered at the keypad.
•Keypad Sounder Output: This is an output programmed to follow
the keypad sounder.
- Itactivatesduring the entry pre-alert andduring anydaymonitor
alarm. It does not follow momentary keypad beeps such as
keystrokes, chimes, etc.
•Access Output: This is an output programmed to activate for 10
seconds when an access control PIN is entered at the keypad.
- Not U. L. Listed for Access Control (UL294).
•Panic/Duress Output: All outputs, including the three on-board
outputs, the Octal Relays, and the Output Functions, support a
Panic/Duress function. To assign an output as a Panic/Duress
Output, program the first data digit as “*1”. Program data digit two
for the appropriate partition(s). This output will follow Duress
activations, Keypad Emergency Keys B and C, and Invisible and
Silent Zone alarms. It will reset after being acknowledged by a
user or after the burglary bell time-out expires.
• Multiplex Bus Outputs
The DS7400Xi supports up to 20 or 40 (when using a DS7436
Multiplex Module) DS7465 Input/Output Modules.
- These modules are connected to the multiplex bus and provide
one input loop and one Form “C” output relay.
- The input loop operates the same as all other multiplex inputs.
- Theoutputloop can be programmed tofollow OutputFunctions.
- Multiplex Bus outputs can be bypassed using the bypass
function. If an output zone is bypassed while it is ON, it will turn
OFF.The bypass will notberemoved when thesystemis armed
and then disarmed; it must be cancelled by entering the bypass
command again or by cancelling all bypasses.
DS7465Module outputs will not pulse,evenifprogrammed
to do so.
• Octal Relay Modules (DS7488)
The DS7400Xi can support two Octal Relay Modules.
- Each relay can be programmed to follow system-wide events
or Output Functions as described above.
• Solid State Output Modules (DS7489)
The DS7400Xi can support two Solid State Output Modules.
- Each output can be programmed to follow system-wide events
or Output Functions as described above.
6.5 Partition Control Programming
•Partition Control Programming: Up to eight partitions may be
used. They are assigned (program address 0165) in order.
- For example: When using only one partition, it is partition one.
When using three partitions, they are partitions one, two, and
three.

DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 18
- Partitioningallowsthesystemtoactasupto 8 different systems.
- Zones, keypads, outputs, and other items may be assigned to
particular partitions.
- Access to partitions may be through each partition’s keypad or
through a Master keypad (see the operating section for more
details).
•Common Area: Partition 1 can be programmed as a common
area, that is, common to other partitions. This allows it to be used
in an installation with one common entry area such as a foyer or
vestibule.
- When Partition 1 is programmed as a common area, it will only
arm when all the partitions it is common to are armed.
- The common area will disarm when any of the partitions it is
common to are disarmed - only if the user has access to the
common area.
- When using a common area, a Master keypad should be used
and assigned to the common area (see keypad assignment
programming).
6.6 Keypad Assignment Programming
•Keypad Assignment: The keypad type and the partition it is
assigned to must be programmed.
- Each program address (0173-0180) programs the keypad type
for two keypads. For example: data digit 1 of address 0173 is
for keypad 1, data digit 2 of address 0173 is for keypad 2.
- Each program address (0208-0215) programs the partition
assignmentfortwokeypads.Forexample:datadigit1ofaddress
0208 is for the partition assignment of keypad 1, data digit 2 of
address 0208 is for the partition assignment of keypad 2.
- Users must have access to the partition the keypad is assigned
to in order to use the keypad.
•Master Keypad Programming : A Master keypad can be used
to access all the partitions.
- It will display the arm/disarm status of all the partitions and can
be used to individually control each partition (see the operating
section for an explanation of the keypad displays).
- A Master keypad can be assigned to any of the partitions.
- Anynumberofthe15 allowable keypadscanbeMasterkeypads.
- When using the common area, it is suggested that a Master
keypad be used and that it is assigned to the common area.
6.7 Emergency Key Programming
Do not label these keys if they are unprogrammed. Only
the “A” key may be programmed and labeled as the Fire
key. These keys are not intended to substitute for Listed
manual pull boxes.
•Fire Key: The emergency key (key A) at the bottom left of the
keypad entry area is the Fire Key. If programmed, the key will
activate a fire alarm when pressed for 2 seconds.
- It may be programmed for a steady or pulsed alarm.
The Fire Key will generate the fire alarm sounders in the
partition that activated the Fire Key. Any other partitions in
use will only have their keypad sounders activated. All
keypad displays will be the same.
•Special Emergency Key: The emergency key (key B) at the
bottom center of the keypad entry area is the Emergency Key.
- If programmed, the key will activate a supplementary or an
auxiliary type alarm when pressed for 2 seconds.
- It may be programmed for a silent, steady, or pulsed alarm.
•Panic Key: The emergency key (key C) at the bottom right of the
keypad entry area is the Panic Key.
- Ifprogrammed,thekey will activate a panicalarm when pressed
for 2 seconds; the keypad display will not indicate an alarm.
- It may be programmed for a silent, steady, or pulsed alarm.
The Special Emergency Key and the Panic Key will
generate the alarm sounders only in the partition of the
keypad that activated that Key.
6.8 Custom Arming Programming
•Custom Arming - [PIN ] + [#] + [4]: If programmed, the [PIN] +
[#] + [4] command sequence may be used to custom arm the
system by arming only certain zone functions.
- For example: All interior zones plus some perimeter zones may
be bypassed while leaving some of the perimeter armed.
6.9 Force Arming
•Force Arming: If programmed, allows violated zones to be force
armed. When force arming, the user must enter the usual arming
command followed by the [Bypass] key. This automatically
bypasseszones that areviolated and programmedas bypassable.
- Fire zones, supervisory zones, keyswitch zones, and non-
bypassable zones can not be force armed.
- Not available in U. L. Listed systems.
- See Program Address 0185.
6.10 Ground Fault Detect Programming
•Ground Fault: If programmed, this function will allow the system
to detect ground faults. This function is required for fire panels
and will be forced on when the panel is in the commercial fire
mode.
- See Program Address 0185.
6.11 Commercial Fire Mode Programming
In a system that includes both fire alarm and burglar alarm
devices, the system must produce distinct sounds for fire
and burglar alarm conditions either by using different
indicating appliances or by using distinct cadences for the
same appliance.
•Commercial Fire Mode: When in Commercial Fire Mode, the
control panel will perform some functions (e.g. communications)
differently to conform with commercial fire regulations.
- See Commercial Fire Mode Programming, program address
0186.
•Water Flow Zone Delay: This is the amount of time a water flow
zonemustbeviolatedbeforethecontrolpanelwillinitiateanalarm.
- The delay is necessary to accommodate normal changes in
water pressure.
- Ifthe water flowinitiatingdevice incorporates itsown time delay,
do not program the control panel unit to exceed 120 seconds
combined time delay.
•Pulsing Fire Zone: This is a zone programmed to output a pulse
fora fire alarminthenormal manner (onesecondON, one second
OFF).
•California March Time: This is a zone programmed to output a
pulse for a fire alarm in the California Time cadence (ten 1/2
second pulses, followed by one second of quiet time).
•Temporal: This is a zone programmed to output a pulse for a fire
alarm in the Temporal cadence (three 1/2 second pulses, followed
by one second of quiet time).
•Single Keypad Use: The keypad should be used on the keypad
bus and be mounted to the front of the control enclosure OR if
within the same room as the control equipment with the wire run
in conduit (or equivalently protected against mechanical injury)
within 20 ft. (6.1 m) of the control equipment.
- This keypad should be assigned as address 1.

DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 19
•Multiple Keypad Use: One keypad only must be used on the
option bus, at any address from 11 - 14, and must meet the
following requirements:
- The keypad must be mounted to the front of the control
enclosure OR mounted within the same room as the control
equipment. The wire is run in conduit (or equivalently protected
against mechanical injury) within 20 ft. (6.1m) of the control
equipment.
- All other keypads should be connected to the keypad bus and
may be placed as needed (within the noted wiring limitations in
the installation manual).
- One keypad must be assigned as address 1.
6.12 Open/Close Report Control Programming
•Open and Close Reports: If programmed, these reports are
sent when the system is armed or disarmed. They may be sent
independently for the opening and closing of each partition, or
the first partition to open and the last partition to close may send
the reports.
•Alternate between both Phone Numbers: If programmed, open
and close reports will be sent to phone number one first. If phone
number one does not pick-up, the control panel will alternate to
phone number two. If phone number two does not pick-up, the
control panel will alternate back to phone number one. It will
alternate between both phone numbers until successful.
6.13 Report Programming
•Reports: For pulse formats, reports are programmed by entering
data in the reporting and extended digits. The report will send the
data programmed for each event. For SIA and Contact ID, the
report formats are fixed and may be activated by placing a 1 in
the reporting digit.
- To disable a report, enter a 0 in the reporting digit.
- To send the Man No. along with Open and Close reports,
program an "F" (enter [*] [5] at the keypad) in the extended
digit.
•Keypad Fire Alarm: This report is sent when a fire alarm has
been activated by the “A” emergency key.
•Keypad Fire Restoral: This report is sent when a keypad fire
alarm has been restored using the [System Reset] command.
•Keypad Emergency Alarm: This report is sent when an
emergency alarm has been activated using the “B” emergency
key.
•Keypad Panic: This report is sent when an emergency alarm
has been activated using the “C” emergency key.
•Keypad Tamper: For keypads fitted with a wall tamper switch,
this report is sent when the keypad is removed from the wall.
•Keypad Tamper Restoral: For keypads fitted with a wall tamper
switch, this report is sent when the keypad is properly replaced
on the wall after experiencing a tamper condition.
•Zone Function Alarm: An alarm report is sent when a zone
alarmoccurs.Alarm reportsareenabledbyzonefunction.Program
this report for any zone functions you wish to send an alarm report
about. For local zones (no reports), do not program an alarm
report. The zone number will automatically be sent for this report
in SIA or Contact ID format.
•Zone Function Restoral: Thisreportissentwhen the zone alarm
is cleared. The zone number will automatically be sent for this
report in SIA or Contact ID format.
•Zone Function Trouble: This report is sent when a zone trouble
condition occurs. This can be an open circuit, if the zone is
programmedfor“troubleonopen”,a multiplex tamperswitchbeing
activated, or a multiplex zone not communicating with the control
panel. The zone number will automatically be sent for this report
in SIA or Contact ID format.
•Zone Function Trouble Restoral: This report is sent when the
trouble condition is cleared. The zone number will automatically
be sent for this report in SIA or Contact ID format.
•Zone Function Bypass: This report is sent when a zone is
bypassed.(Note: Fire zones can never be bypassed.)Zonebypass
reports for non-24 hour zones are sent with the closing report.
Bypass reports for 24 hour zones are sent when the zone is
bypassed. If a zone is force armed, the bypass report is sent with
the partial close report. If a 24 hour or non-24 hour zone is custom
armed, the bypass report is sent with the partial close report.
•Zone Function Bypass Restoral: This report is sent when the
zonebypassis cleared.For non-24 hourzones the bypassrestoral
is sent with the open report. Bypass restoral reports for 24 hour
zones are sent when the zone is manually restored. The bypass
restoral report for a zone that was force armed is sent when the
zone is restored. If a 24 hour or non-24 hour zone was custom
armed, the bypass restoral is sent with the open report.
•Open: This report is sent when the system has been disarmed.
In SIA or Contact ID formats, the user number for the person who
disarmed the system will be sent with this report. To send the
user number along with an Open report in other formats, program
the extended digit of the report as *5. In Contact ID format, the
partition number will also be sent along with this report. The Open
report will only be sent if a Close report was sent previously.
•Close: This report is sent when the system has been armed. In
SIA or Contact ID formats, the user number for the person who
armed the system will be sent with this report. To send the user
number along with a Close report in other formats, program the
extendeddigitofthereportas *5. In ContactIDformat,thepartition
number will also be sent along with this report.
•Duress: This report is sent when the system is disarmed using a
duress code. The user number is not sent with this report.
•Partial Close: This report is sent when the system is armed
partially, or force armed.
•First Open After Alarm: This report is sent when the system is
disarmed after an alarm has occurred.
•Low Battery: This report is sent when a low battery condition
occurs.
•Battery Restoral: This report issentwhen a low batterycondition
restores.
•AC Fail: This report is sent when an AC failure condition occurs.
This report may be delayed in address 0197.
• AC Failure Report Delay
The AC power loss report can be programmed to delay for up to
254 minutes (see address 0197). (The same delay would also
apply to the AC restoral report.)
- If another report is sent during this delay period, the AC fail
report will be sent along with this report.
- If the AC power restores during this delay period, the AC loss
report will not be sent.
- Programming address 0197 as FF causes the report to be sent
at a random interval of at least 15 minutes, but no more than 2
hours after the AC failure occurs.
•AC Restoral: This report is sent when an AC failure condition
restores.
•Communicator Test/System Normal: This report is sent at the

DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 20
24-hour check-in time if there is not a control trouble, an active
fire alarm that has not been acknowledged, a fire trouble, or a
supervisory condition. Note: To send a Communicator Test even
if one of these conditions exists, program the Communicator Test/
System Off Normal.
•Remote Program Successful: This report is sent after a Remote
Program session, if the session was terminated properly.
•Remote Program Unsuccessful: This report is sent after a
Remote Program session, if some error has occurred or the
session did not terminate properly.
•Local Program Successful: This report is sent when local
programmer’s mode is exited and there is no error associated
with the programming.
•Local Program Unsuccessful: This report is sent when local
programmer’s mode is exited and there has been some error
associated with the programming.
•System Trouble: This report is sent when a control trouble
condition occurs.
•System Trouble Restoral: This report is sent when all system
trouble conditions restore.
•Communicator Test/System Off Normal: This report is sent at
the 24-hour check-in time if there is a control trouble, an active
fire alarm that has not been acknowledged, a fire trouble, or a
supervisory condition.
•Exit Error: This report is sent if an exit error occurs. An exit error
occurs when an entry/exit zone is still violated at the end of the
exit delay. If this happens, the entry delay will begin. If the system
is not disarmed before the entry delay expires, an alarm report
for the effected zone will be sent and the Exit Error report will be
sent. If this report is not programmed, the control will not sound
the exit error warning.
•Recent Closing: This report is sent, alongwithanyalarm reports,
whenthere is an alarmwithinthefirst five minutes afterthe system
has been armed.
•System Walk Test: This report is sent when a system test has
been started (#81 key sequence). Zone reports are sent during a
system test.
•System Walk Test Restoral: This report is sent when the system
test has been completed or has timed-out.
•Fire Walk Test: This report is sent when a Fire Walk Test has
beenstarted(#91keysequence). Zone reports are not sent during
a Fire Walk Test.
•Fire Walk Test Restoral: This report is sent when the Fire Walk
Test has been completed or has timed-out.
•Mux. Smoke Low Temperature Report: This supervisory report
is sent when a MX280 Series smoke detector with a low
temperature feature detects a temperature of 45°F (7.5°C) or less
for a period of 30 minutes or more.
•Mux. Smoke Low Temperature Restoral: This report is sent
when a MX280 Series smoke detector with a low temperature
alarm determines that the temperature has risen above 45°F
(7.5°C).
•Dirty Chamber Report: This report is sent when a MX280 Series
smoke detector fails to pass the “Chamber Check” sensitivity test.
•Dirty Chamber Restoral:This report is sent when a MX280 Series
smoke detector has been returned to normal operation after
service.
6.14 Phone Number General Control
Programming
•Enable Remote Programmer Callback: If programmed, when
the remote programmer tries to initiate a session with the panel,
the panel will hang up and call the remote programmer phone
number.
- This ensures the correct remote programmer is initiating the
call.
•Dial Pulse on all Phone Numbers: If programmed, the panel
will use the pulse format to dial phone number 1, 2 and the remote
programmer phone number 3.
•Dial Tone on all Phone Numbers: If programmed, the panel will
use the tone format to dial phone number 1, 2 and the remote
programmer phone number 3.
6.15 Phone Answering Programming
•Answering Machine Bypass: This feature allows the panel to
answer incoming calls when answering machines are used. If the
line rings, stops ringing, then rings again within one minute, the
panel will seize the phone line on the first ring.
•PhoneAnswering Programming: The panelcanbeprogrammed
to answer the phone after a selected number of rings for remote
programming access. It can also be programmed to answer the
phoneaftera different numberofrings when inarmed or disarmed
states.
- This can be used to call the panel location and determine its
arming state.
6.16 FCC Compliance Notice
This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to Part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment
generates, uses and can radiate radio frequency energy and if not
installed and used in accordance with the instructions, may cause
harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation.
If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
• Re-orient or relocate the receiving antenna.
• Increase the separation between the equipment and the receiver.
• Connect the equipment into an outlet on a circuit different from
that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
6.17 FCC Phone Connection Notice To Users
This control complies with Part 68 of the FCC rules.
On the inside of the enclosure is a label that contains, among other
information, the FCC Registration Number and the Ringer
Equivalence Number (REN) for this equipment. You must, upon
request, provide this information to your local telephone company.
The REN is useful to determine the quantity of devices that may be
connected to your telephone line and still have all of those devices
ring when your telephone number is called. In most, but not all
areas, the sum of the REN's of all devices connected to one line
should not exceed five (5.0). To be certain of the number of devices
that you may connect to your line, you may want to contact your
local telephone company to determine the max. REN for your local
calling area.
Other manuals for DS7400Xi
4
Table of contents
Other Detection Systems Keypad manuals