Table of Parameters
DIXELL XR60CH c/ prog. XR 70 CH
DC-09.151-PRD
R02/22.04.2021
MAIN FUNCTIONS:
How to see the set point:
Push and immediately release the SET key: The display will show the Set Point value;
Push and immediately release the SET key or wait for 5 sec to display the probe value again;
How to change the set point
Push the SET key more than 2 second to change the set point value;
The value of the set point will be displayed and the ºC or ºF led will start blinking
To change the set value, push the UP or DOWN arrows within 10 sec
How to start a manual defrost
Push the DEF key for more than 2 sec and a manual defrost will start
How to change a parameter value
To change a parameter value, operate follows:
Enter the programming mode by pressing the SET + DOWN buttons for 3s (the ºC or ºF LED will start blinking)
Select the required parameter. Press the SET button to display its actual value
Use UP or DOWN buttons to change its value.
Press SET button to store the new value move to the following parameter.
To exit: Press SET + UP buttons or waiting for 15 s without pressing any key.
NOTE: the set value is stored even when the procedure is exited by waiting for the time-out expire.
The hidden menu
The hidden menu includes all the parameters of the instrument
-How to enter the hidden menu
Enter the programming mode by pressing the SET + DOWN buttons for 3 sec (the ºC or ºF LED will star
blinking)
Release the buttons and then push again the SET + DOWN buttons for more than 7 s. The Pr2 label will be
displayed immediately followed from HT parameter.
Now i tis possible to browse the hidden menu
Select the required parameter
Press the SET button to display its value
Use UP or DOWN to change its value
Press SET to store the new value and move to the following parameter
To exit: Press SET + DOWN or wait 15 sec without pressing a key
Note1: If no parameter is present in Pr1 menu, after 3 sec the “nop” message will be displayed.
Keep the buttons pushed til the Pr2 message will be displayed
Note2: The set value is stored even when the procedure is exited by waiting for the time-out to expire.