manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Digi-Sense
  6. •
  7. Measuring Instrument
  8. •
  9. Digi-Sense 3622566 User manual

Digi-Sense 3622566 User manual

12/10 1 Rev.1
Operation Manual
Instruction Notes for 3622566, 3622567, 3622568, 3622569
Figure 1 Figure 2
General Description
If your heating process requires several steps, this is the control for you. The Ramp/Soak feature of this control allows up
to a 40-step profile, which can be configured from the provided software. You can profile Temperature, Time, Hold, Soak
and End steps to create the ideal profile for your process. The built in adaptive control technology provides even tighter
control for these demanding applications. Several input types are available. This unit comes with 6’ detachable power
cord, communication port, audible alarm function and grid support bracket, which is ideal for fume hood mounting to
maximize bench space.
This control is a microprocessor-based, digital indicating, automatic temperature control with a single input and a single
output. It features an auto-tuning function that allows automatic setting of control parameters with a minimum of user input
required. This family of control accepts a type "J", “K”, “T” thermocouples or RTD input depending on the model ordered.
The control automatically sets the PID parameters through a "learning" sequence in the auto-tuning mode. PID
parameters include proportional band, reset/integral and rate/derivative. User-friendly features include automatic LED
indicators to aid in monitoring and setup, as well as dual LED displays for process temperature and set point indication.
This control automatically stores all information in a non-volatile memory.,
Control Features
1. On/Off power switch.
2. On/Off alarm switch.
3. 12-amp output.
4. Control PID with Auto-tune algorithm, solid state relay
5. Circuit protection (fuse)
6. Low profile housing.
Power
Inlet
Grid
Support
Load
Fuse
Load
Outlet
Sensor
Input
ON/OFF
Switch
Digital
Control
Module
Alarm
RS-232
Port
ON/OFF
Alarm
Switch
12/10 2 Rev.1
How to Setup and Operate
First, connect the heater load and the sensor to the load and sensor receptacles on the front panel. Next, plug the control
line cord into an appropriate 3-wire grounded power receptacle. Push the power switch to the "ON" position. Wait five
seconds for the control unit to energize.
The control is shipped from the factory with the display reading in degrees C. If a display in degrees F is desirable, press
the UP/DOWN arrow keys simultaneously for three seconds to access the Setup Page. Press the Advance key until the
Celsius_Fahrenheit parameter [C-F] is shown in the lower display. Press the UP arrow key to change from C to F.
After changing the display, press the Infinity key to display the set point temperature and the process temperature
(temperature at the sensor).
To begin the heating application, use the Up/Down arrow keys to enter the desired set point temperature. This is shown
in the lower display. Press the Advance key to cycle through the Operations Page until the auto-tuning parameter [Aut] is
shown in the lower display. Auto-tuning is recommended in most applications. Auto-tuning allows the control to set the
parameters without those parameters being input by the user. It also minimizes the amount of temperature overshoot of
the set point and decreases the time required for the process to stabilize. To use the Ramp feature, refer to the
Ramp/Soak Operation section.
EZ button –User defined
12/10 3 Rev.1
After setting the auto-tuning parameter [Aut] to ON, press the Infinity key to display the set point and process
temperatures. While the control is in the auto-tuning mode, the lower display alternately flashes the set point and the "Aut"
prompt. When tuning is complete, the lower display indicates only the set point.
The auto-tuning function can be aborted by setting auto-tuning [Aut] to OFF or switching off power to the control.
It is recommended that auto-tuning be used each time a process is being run. If the process is being duplicated, the
parameters learned in the initial setup are stored in the memory of the control and no repeat of auto-tuning is required.
Auto-tuning feature allows quick and simple automatic control for the majority of heating applications. This control is
capable of performing other control functions and has a variety of features.
Control Sensor
Proper placement of the sensor can eliminate many problems in the total system. The probe should be placed so that it
can detect any temperature change with little thermal lag. In a process that requires fairly constant heat output, the probe
should be close to the heater. In processes where heat demand is variable, the probe should be close to the work area.
Some experimenting with probe location can be tried to provide optimum results.
Specifications
Control Mode
- Microprocessor-based, single input, single output.
- PID parameters
Proportional band: 1 to 999o F
Reset: 0.00 to 99.99 repeats per minute.
Integral: 0.00 to 99.99 minutes per repeat.
Rate or Derivative: 0.00 to 9.99 minutes.
Operator Interface
- Advance, Infinity, Up and Down keys and ON/OFF switch.
- Dual, four digit LED displays.
- Thermocouple receptacle or (RTD) and 3-wire load receptacle.
Input
- Type J, K , T thermocouple or (RTD): input grounded or ungrounded.
- Automatic cold junction compensation and break protection for sensor.
- Degrees F or degrees C display; user selectable (preset for degrees C)
Range Type J:
-200°C to 1200°C
Range Type K:
-200°C to 1370°C
Range Type T:
-200°C to 400°C
Range Type RTD:
-200°C to 800°C
Primary Output (Heating or Cooling)
- 15 Amp, 120 Volts.
Accuracy
- Calibration accuracy: 0.1% of span.
- Temperature stability: 0.2 oF /oF rise in ambient maximum.
- Voltage stability: 0.01% of span / % of rated line voltage.
Power
- 50/60 Hz 5%
- Data retention upon power failure via nonvolatile memory.
12/10 4 Rev.1
Operating Environment
- 32 to 149 oF / 0 to 65 oC; 0 to 90% RH, non-condensing.
Setup Menu
12/10 5 Rev.1
12/10 6 Rev.1
12/10 7 Rev.1
Operations Menu
How to Tune and Operate
Manual operation provides direct (time proportioned % time) control from -100% to 100%. A negative value is allowed
only when Ot 1=Cool. Automatic operation provides sensory feedback ON/OFF or PID control. When the operation
transfers from automatic to manual operation, the power level from automatic operation is retained and restored to the
previous set point.
The % LED indicates manual operation. The LED is on when in Manual operation and off when in AUTO operation.
When the LED is flashing, press the Infinity key again within 5 seconds to complete the change in operation. It the
sensor is open and LOC=0, 1 or 2, the control switches to Manual operation if the output was stable before the break
occurred.
12/10 8 Rev.1
Tuning-Automatic
Auto-tuning: This control can automatically tune the PID parameters to fit the characteristics of your particular thermal
system.
Auto-tune can only be used when Output 1 is hEAt. Once the auto-tune sequence has begun, the lower display flashes
between AUt and the set point. The displayed set point remains unchanged.
Once the control finished "learning" the system, it returns to standard PID control with the values automatically set. Auto-
tuning is complete within 80 minutes. Any change of the set point, while in auto-tune, re-initiates the auto-tune procedure.
In order for the control to successfully complete auto-tune, the process must cross set point four times within 80 minutes
after auto-tune has started. If this does not happen within the 80 minute time limit, Pb1 remains at 0 and the control
functions in an ON/OFF mode.
To start auto-tuning:
1. Press the Advance key until the Aut prompt appears in the lower display.
2. Change the parameter to On.
3. Press the Infinity key to display the set point and sensor temperatures. While the control is in the tuning mode,
the lower display alternately displays set point and the "Aut" prompt.
4. When tuning is complete, the lower display indicates setpoint only and Aut reverts to OFF. The control installs
appropriate PID tuning parameters and saves them in the non-volatile memory.
*To abort auto-tuning, the operator must reset Aut to OFF. Auto-tuning may also be aborted by cycling power off and on.
In all cases, aborting auto-tuning restores all original values.
Error Code Definitions and Actions:
Er.In - An open or reversed polarity sensor is the most likely cause. Check the sensor; if the connection is good and
functions properly, call the factory. Make sure the input parameter [SEn] is set to the correct type thermocouple.
Er.Ab –Ambient temperature may be too hot or too cold. Make sure that the temperature surrounding the control is –18 to
65C.
Er.CS –Checksum Error. Settings may have changed unexpectedly. Press the Infinity key to clear the error. Verify
settings. If error message persists, contact the factory.
To clear a corrected error, cycle power to the control.
12/10 9 Rev.1
Ramp/Soak Operation
The control is furnished with a CD for installation of a USB 2.0 to RS-485 driver. Before communicating with the control
through a pc this driver must be installed. Insert the CD into you pc and follow the instructions.
Once this is accomplished it is recommended to go to the Watlow web site, www.watlow.com and under the download
center tab, click on Software Download and install the EZ-Zone configuration software. This software will allow you to
easily set any parameter in the control and allow simple profile setup.
Once the software has been installed you can now attach the control to a pc and open the EZ-Zone configuration
software.
First Screen
12/10 10 Rev.1
Second Screen
Third Screen
12/10 11 Rev.1
Forth Screen
12/10 12 Rev.1
EZ-Zone Configurator software will now open and the following will appear on the screen:
12/10 13 Rev.1
Continued:
12/10 14 Rev.1
To activate the Ramp action, follow the below setup:
12/10 15 Rev.1
Ramp Action Continued:
12/10 16 Rev.1
12/10 17 Rev.1
Select What Type this Step Will Be
Use Step Type to select what this step will do. The parameter list updates in a few seconds after the Step Type setting is changed.
• An Unused Step is, in effect, an empty step that can be used to erase a step in the profile.
• A Time step ramps to a Target Set Point over a specified time and maintains up to two Event states for the designated time.
• A Rate step ramps the process value to the Target Set Point without exceeding the Rate, while maintaining up to two Event outputs.
• A Soak step maintains the last Target Set Point and up to two Event states for the designated time.
• A Wait for Event step will wait for up to two Wait Events to be satisfied while maintaining up to two Event outputs.
• A Wait for Process step will wait for the process value to match the Wait for Process value, while maintaining up to two Event outputs.
• A Wait for Both step will wait for the process value to match the Wait for Process value and up to two Wait Events to be satisfied while
maintaining up to two Event outputs.
• A Jump Loop step will jump to the Jump Step the number of times designated in Jump Count, while maintaining up to two Event outputs.
• An End step will set up to two Event outputs and end the profile. If a profile doesn’t include an End step, control will move to the next step. If no
End step in encountered, after step 40 control will default to the set point in effect before the profile started.
12/10 18 Rev.1
Profiling Page:
12/10 19 Rev.1
Profiling Page Continued:
12/10 20 Rev.1
Profiling Page Continued:

This manual suits for next models

3

Other Digi-Sense Measuring Instrument manuals

Digi-Sense 20250-63 User manual

Digi-Sense

Digi-Sense 20250-63 User manual

Digi-Sense 20250-61 User manual

Digi-Sense

Digi-Sense 20250-61 User manual

Digi-Sense 20250-12 User manual

Digi-Sense

Digi-Sense 20250-12 User manual

Digi-Sense 20250-11 User manual

Digi-Sense

Digi-Sense 20250-11 User manual

Digi-Sense 20250-00 User manual

Digi-Sense

Digi-Sense 20250-00 User manual

Digi-Sense 20250-29 User manual

Digi-Sense

Digi-Sense 20250-29 User manual

Digi-Sense 20250-26 User manual

Digi-Sense

Digi-Sense 20250-26 User manual

Digi-Sense 20250-15 User manual

Digi-Sense

Digi-Sense 20250-15 User manual

Digi-Sense 20250-16 User manual

Digi-Sense

Digi-Sense 20250-16 User manual

Digi-Sense 20250-55 User manual

Digi-Sense

Digi-Sense 20250-55 User manual

Digi-Sense 20250-31 User manual

Digi-Sense

Digi-Sense 20250-31 User manual

Digi-Sense 20250-65 User manual

Digi-Sense

Digi-Sense 20250-65 User manual

Digi-Sense 20250-13 User manual

Digi-Sense

Digi-Sense 20250-13 User manual

Digi-Sense 20250-40 User manual

Digi-Sense

Digi-Sense 20250-40 User manual

Digi-Sense 20250-63 User manual

Digi-Sense

Digi-Sense 20250-63 User manual

Digi-Sense 20250-23 User manual

Digi-Sense

Digi-Sense 20250-23 User manual

Digi-Sense 20250-19 User manual

Digi-Sense

Digi-Sense 20250-19 User manual

Digi-Sense 20250-22 User manual

Digi-Sense

Digi-Sense 20250-22 User manual

Digi-Sense 20250-57 User manual

Digi-Sense

Digi-Sense 20250-57 User manual

Digi-Sense 20250-14 User manual

Digi-Sense

Digi-Sense 20250-14 User manual

Digi-Sense 20250-35 User manual

Digi-Sense

Digi-Sense 20250-35 User manual

Digi-Sense 20250-21 User manual

Digi-Sense

Digi-Sense 20250-21 User manual

Popular Measuring Instrument manuals by other brands

Sper scientific 800015 instruction manual

Sper scientific

Sper scientific 800015 instruction manual

SOMMY EL801 Series user manual

SOMMY

SOMMY EL801 Series user manual

MONARCH INSTRUMENT PLS instruction manual

MONARCH INSTRUMENT

MONARCH INSTRUMENT PLS instruction manual

Fluke NORMA 6003 user manual

Fluke

Fluke NORMA 6003 user manual

Thermo Electron Nicolet 380 user guide

Thermo Electron

Thermo Electron Nicolet 380 user guide

Powerfix Profi 288019 Operation and safety notes

Powerfix Profi

Powerfix Profi 288019 Operation and safety notes

AMERITECH AM8a instruction manual

AMERITECH

AMERITECH AM8a instruction manual

Unipulse F370 Operation manual

Unipulse

Unipulse F370 Operation manual

SCHUTZ GPD 3000 user manual

SCHUTZ

SCHUTZ GPD 3000 user manual

Deviser TC500 Operation manual

Deviser

Deviser TC500 Operation manual

Rae MultiRAE Plus Using

Rae

Rae MultiRAE Plus Using

3M 701 CALIBRATION PROCEDURE

3M

3M 701 CALIBRATION PROCEDURE

Chroma 66203 user manual

Chroma

Chroma 66203 user manual

Brainchild PM1600 user manual

Brainchild

Brainchild PM1600 user manual

Sonic KDG-300 instruction manual

Sonic

Sonic KDG-300 instruction manual

TRAP-IT ABD-075 Operation manual

TRAP-IT

TRAP-IT ABD-075 Operation manual

ABB Sensyflow iG operating manual

ABB

ABB Sensyflow iG operating manual

DeWalt DW099E user manual

DeWalt

DeWalt DW099E user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.