Manual EDS-C V1.0
Congratulations on the purchase of your Dimetix EDS-C distance sensor.
1 Overview
2 Dimensions
3 First Start-Up
To configure the EDS-C, you need the sensor, a connection cable (see
chapter accessories), a power supply and the easy to apply "Start-Up
Software". The "Start-Up Software" for configuration is available as free
ware on our web-page: www.dimetix.com
Connect the EDS-C to a PC/Laptop using the RS-232 interface, define and
download your configuration and install the sensor in your application.
4 Connection for configuration
We propose to use our standard configuration cable (see Accessories).
Please note, that some "USB to RS-232 converter" can cause problems.
5 DIMETIX Start-Up Software for EDS-C
On the sensor you can configure the following by using the "Start-Up
Software" ( www.dimetix.com )
6 Configuration of the EDS-C
To achieve the maximum possible analog output accuracy, we suggest to
configure the span as short as possible. For example, if you measure
distances of 12 to 19 meters, you should configure a span of 10m to 20m
(corresponding to 0/4...20mA)
Configuration limits:
minimum Level (mA): 0 or 4mA
error Level (mA): 0 to 20mA
minimum Distance (mm): 0 to 30'000mm
maximum Distance (mm): 1000 to 30'000mm
Measuring interval (s): max. Speed (0) to 65'000s
Command Set (if not using the free "Start-Up Software")
Baud Rate: 19'200; Data Bits: 7; Parity: even; Stopbits: 1
Command Terminator is: <CR> <LF> (Carriage return, Line feed)
The first two characters in the commands are s0 (s, zero)
For further information about the command-set read the COM- trace in
our "Start-Up Software".
7 Connection diagram EDS-C to control unit
The load resistor must be less than 500Ωfor a power supply of 24V. If the
power supply is less then 24V, the max load resistor is reduced. At 12V the
load resistor must be less than 350Ω.
8 Measuring conditions
The EDS is an optical instrument, whose operation is influenced by
environmental conditions. Therefore, the measuring range may vary. The
following conditions may influence speed and range of the measurements:
Key Factors increasing range
and/or distance
Factors reducing range
and/or distance
Target
surface
Bright and/or reflective
surfaces such as our target
plates
Matt and/or dark surfaces
green / blue / black
surfaces
Airborne
particles
Clean air Dust, fog, heavy rainfall,
heavy snowfall
Sunshine Darkness Bright sunshine on the
target
Laser Distance Sensors
Not the final picture
All dimensions in mm
Laser Beam
Measuring reference
M12 5pole
Sensor Plug
77.5
105.5
62
91.5 24.25
33.44
21.3
45
4.5
Tx (RS-232)
Rx (RS-232)
4
5
GND
Vcc
24VDC
+
2
1
EDS
Analog Out (mA)
3
-
Load
0...20mA
Input
(brown) Vcc 1 2 Gnd (white)
3 AO (blue)
(black) Rx 4 5 Tx (grey)
M12 5-Pin:
Customers
Control Unit
0/4...20mA current loop
{
for configuration
9 pin D-Sub
female
Tx
Gnd
3
5
2
Tx (RS-232)
Rx (RS-232)
4
5
GND
Vcc
Rx
24VDC
+-
2
1
COM1 or COM?
EDS
Analog Out (mA)
3
-
(brown) Vcc 1 2 Gnd (white)
3 AO (blue)
(black) Rx 4 5 Tx (grey)
M12 5-Pin:
Start-Up Software
www.dimetix.com
9 Product specifications
Measuring accuracy
EDS-C 30
± 3.0mm @ 2sigma
Analog Output 0.3% full scale, including
temperature drift and target property
Typical repeatability approx. 1.5mm
Measuring range (on natural
surfaces)
0.05 to 30 m (matt, dark surfaces up to about
20m)
Measuring reference from front edge (see picture schematic)
approx. Ø of laser spot 6mm @5m; 7mm @10m; 15mm @30m
Time for a measurement 0.4 to approx. 4 sec
Light source Laser diode visible 620-690 nm (red)
IEC 60825-1:2001; Class 2
FDA 21CFR 1040.10 and 1040.11
Beam divergence:0.16 x 0.6 mrad
Pulse duration: 0.45x10-9 s
Maximum radiant power: 0.95 mW
Laser Life Time > 50'000h @ 20°C
ESD IEC 61000-4-2 : 1995 +A1 +A2
EMC EN 61000-6-4; EN 61000-6-2
Power supply 24V DC+/-10%, 0.1A max.
Dimensions 106 x 62 x 45 mm
Operating Temperature -10 °C to +50 °C
Storage Temperature -40 °C to +70 °C
Environment Humidity 0...80%RH non-condensing;
no aggressive vapors
Degree of Protection P65; IEC60529
(protected against ingress of dust / water)
Weight 280g
Interface 1 RS-232 Interface to configure the sensor
1 program. analog output 0/4 .. 20mA
10 Error codes
No. Format Meaning and elimination
200 @E200 Device startup information (only for error stack), successful
power on cycle or power-line not stable
203 @E203 Wrong syntax in command, prohibited parameter in command
entry or non-valid result, check command
210 @E210 Not in tracking mode, start tracking first
211 @E211 Sampling too fast for the used target, configure a slower
sampling rate (or use a more reflective target)
212 @E212 In Tracking Mode,command not executable,
Stop tracking first with s0c-command
220 @E220 Error on serial communication, check com settings
234 @E234 Distance out of range, Measure a distance within the specified
limits
252 @E252 Temperature to high, cool down the sensor
253 @E253 Temperature to low, heat up the sensor
255 @E255 Received signal to low, use a brighter target or a target plate
256 @E256 Received signal to high, use a darker target, mind reflective parts
along the laser beam
257 @E257 To much background light, cover bright light sources, use a
darker target, mind reflective parts along the laser beam
260 @E260 Strange distance result, maybe distance jump during measuring
cycle, measure to a defined target
not listed contact your Distributor or DIMETIX
11 Accessories
On our web-page www.dimetix.com you can find some helpful accessories
for the EDS-C.
- configuration cable 3m (500 204) - Connection cable 5m (500 205)
- Accessory for Starter Kit (500 592) - Alignment jig (500 213)
12 Quality certificate
We hereby certify, that the EDS-C has been tested and complies with the
specifications as stated in this manual'. The test equipment used is
traceable to national standards, which are established by our Quality
Management System. The EDS-C is made in Switzerland.
13 Labeling
Location:
The device label is placed on the
top of the device, while the type
label can be found on the back.
14 Safety instructions
The following instructions are to enable the person responsible for the EDS-
C, and the user of the instrument, to anticipate and avoid operational
hazards.
The EDS-C is made to be integrated into technical systems. Basic technical
training is therefore essential. This device may only be operated by trained
personnel.
The person responsible for the instrument must ensure that all users
understand these instructions and adhere to them.
If the EDS-C is part of a system, the manufacturer of such a system is
responsible for all safety-related issues, such as the manual, labeling and
instruction.
15 Laser classification
The EDS-C produces a visible laser beam, which emerges from the front of
the instrument. It is a Class 2 laser product in accordance with:
1) IEC60825-1 (2001) ”Radiation safety of laser products”
2) EN60825-1 (2001) ”Radiation safety of laser products”
It is a Class II laser product in accordance with:
1) FDA 21CFR 1040.10 and 1040.11 (US Department of Health and
Human Service, Code of Federal Regulations)
Laser Class 2/II products:
Do not stare into the laser beam or direct it towards other people
unnecessarily. Eye protection is normally afforded by aversion responses
including the blink reflex.
WARNING: Looking directly into the beam with optical aids
(binoculars, telescopes) can be hazardous.
Precautions: Do not look into the laser beam. Make sure the laser is
aimed above or below eye level. (particularly with fixed
installations, in machines, etc.).
CAUTION: Looking into the laser beam may be hazardous to the eyes.
Precautions: Do not look into the laser beam. Make sure the laser is
aimed above or below eye level (particularly with fixed
installations, in machines, etc.).
16 Service information
All warranty returns and repairs have to be returned with a RMA Report
provided on our web-page www.dimetix.com .
17 Disclaimer
Information in this document is subject to change without notice and does
not represent a commitment on the part of Dimetix AG.
Dimetix AG
Degersheimerstr. 14
CH-9100 Herisau
Switzerland
Tel. +41-71-353 00 00
Fax +41-71-353 00 01
info@dimetix.com
www.dimetix.com
© Copyright by Dimetix AG
Laser Distance Sensors
Fig. 2: Type Label
Dimetix EDS-C 30
Serial No.:
Part No.:
green: OK
blinking: Error
Power: 24V DC
Swiss Made
www.dimetix.com
Date:
10/2009
550502
12345678
Fig. 1: Device label
(brown) Vcc 1 2 Gnd (white)
3 AO (blue)
(black) Rx 4 5 Tx (grey)
M12 5-Pin:
Dimetix AG CH-9100 Herisau
www.dimetix.com
Swiss Made
LASER RADIATION
DO NOT STARE INTO BEAM
CLASS 2 LASER PRODUCT
Complies with 21CFR 1040.10 and
1040.11 exceptfordeviationspursuant
to Laser Notice no.50, dated May 2001,
with IEC 60825-1 (2001) and
EN 60825-1 (2001)
620-690nm
0.95mW max.
Class 2
Laser Product
LASER RADIATION
DO NOT STARE INTO BEAM
CLASS 2 LASER PRODUCT

Other Dimetix Measuring Instrument manuals

Dimetix FLS-C Installation and operating instructions

Dimetix

Dimetix FLS-C Installation and operating instructions

Dimetix DLS-C 15 Product manual

Dimetix

Dimetix DLS-C 15 Product manual

Dimetix DLS-B 15 Product manual

Dimetix

Dimetix DLS-B 15 Product manual

Dimetix DLS-C 15 Product manual

Dimetix

Dimetix DLS-C 15 Product manual

Popular Measuring Instrument manuals by other brands

TRAMEX CME5 manual

TRAMEX

TRAMEX CME5 manual

Hach POCKET COLORIMETER II instruction manual

Hach

Hach POCKET COLORIMETER II instruction manual

Callaway Micro manual

Callaway

Callaway Micro manual

Bosch GAM 270 MFL Operating/safety instructions

Bosch

Bosch GAM 270 MFL Operating/safety instructions

ennoLogic eH710T user manual

ennoLogic

ennoLogic eH710T user manual

Badger Meter Primo Advanced BMAG-350-icpf Instruction and operation manual

Badger Meter

Badger Meter Primo Advanced BMAG-350-icpf Instruction and operation manual

Agilent Technologies ESA-L1500A Installation notes

Agilent Technologies

Agilent Technologies ESA-L1500A Installation notes

Schmidt MST Series instruction manual

Schmidt

Schmidt MST Series instruction manual

Mindfield eSense Muscle quick guide

Mindfield

Mindfield eSense Muscle quick guide

Rohde & Schwarz FSMR26 Getting started

Rohde & Schwarz

Rohde & Schwarz FSMR26 Getting started

SSI Digital Fluid-Trac DFT-110 Application note

SSI

SSI Digital Fluid-Trac DFT-110 Application note

ATAGO RePo-1 instruction manual

ATAGO

ATAGO RePo-1 instruction manual

forede ZDMS 0.6/5S manual

forede

forede ZDMS 0.6/5S manual

Hesai PandarXT-16 user manual

Hesai

Hesai PandarXT-16 user manual

Kobold HND-P105 operating instructions

Kobold

Kobold HND-P105 operating instructions

DeFelsko PosiTector 200 instruction manual

DeFelsko

DeFelsko PosiTector 200 instruction manual

MULTI MEASURING INSTRUMENTS M-3000 instruction manual

MULTI MEASURING INSTRUMENTS

MULTI MEASURING INSTRUMENTS M-3000 instruction manual

Bedfont Micro Plus Smokerlyzer quick start guide

Bedfont

Bedfont Micro Plus Smokerlyzer quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.