10
Assembling the Outdoor Unit
The outdoor unit should be attached firmly to a
suitable surface or a suitable wall of sufficient
strength (see also “Wall bracket accessory”).
It should be installed in a place where there is
unimpeded air inflow and outflow An air short
circuit must be avoided. Please observe minimum
clearances and the sound power levels given in
the technical data (distances from bedrooms or
third-party rooms etc.).
Condensation drainage in the outdoor unit
When the heat pump is in operation, condensation
is formed in the outdoor unit, which must be
drained off in a manner appropriate to the
location.
There is a hole (diam. 25) for condensation
drainage in the base plate of the outdoor unit into
which the condensation drainage plug supplied is
inserted. If the installation location allows it, the
condensation formed can simply drip away,
otherwise it must be led off through a pipe
attached to the drainage plug.
Caution:
During heating operation at temperatures below
+4 °C the condensation outlet can freeze up
under unfavourable conditions and this can block
the condensation fan. If temperatures below +4 °C
are to be expected at the condensation outlet
during heating operation, appropriate measures,
e.g. insulation (insulation of the base of the casing
and the condensation drainage area) should be
taken, or, if possible, the drainage plug should not
be installed. If a condensation pipe is used, it
must always slope downwards.
Distances between the drilling holes for
mounting the outdoor unit
Type Dim. A (mm) Dim. B (mm) Dim. C (mm)
KSS 2504A/3204A 275 540 848
KSS 4504C 375 572 950
KSS 6004C 375 572 950
Connecting the cooling system for
devices with pre-filled refrigerant
pipes KMSL… .
The refrigerant pipes of the indoor and outdoor
units are pre-filled with refrigerant R407C or
R410A.
Please observe the safety regulations for
handling CFC (HCFC) in the section “Pre-filled
refrigerant pipes KMSL…” when installing the
air conditioners and the split pipes.
(see page 12f.)
Split pipes of the KMSL series
Care must be taken to connect the refrigerant
pipes correctly. It is particularly important to
observe the torques specified (see page 14).
Incorrect connection of the split pipes, which can
be ordered as accessories, is impossible,
because each half of the coupling fits only to its
other half in the indoor or outdoor unit.
Ready-to-use refrigerant pipes in various lengths
are available (see Essential Accessories in
“Technical Data”). Excessively long pipes should
be avoided when selecting split pipes (loss of
cooling capacity). Reductions or extensions to
length may be made by the authorised after-sales
service only.
Please observe the assembly steps and the
notes in the section “Pre-filled refrigerant
pipes KMSL” on page 12ff. for installation and
the connection of the cooling system.
View from
above