Operating Instructions XWA11V
dIXELV8.8-KIT
5
Weiss Instruments,LLC. 905 Waverly Ave. Holtsville, NY 11742 631-207-1200 www.weissinstruments.com
8. ELECTRICAL CONNECTIONS
The instrument is provided with ¼” (.250”) fast-on terminal blocks to connect the digital and analog inputs.
Relays and power supply have a Fast-on connection ¼” (.250”). For supply connections use 14 AWG or
larger copper or CU wire only, rated to at least 90°C (194°F). Before connecting cables make sure the power
supply complies with the instrument requirements. Separate the probe cables from the power supply and
output power connections. Do not exceed the maximum current allowed on each relay and in case of heavier
loads use a suitable external relay.
Note: Maximum current allowed for all the loads is 15A.
8.1 PROBE CONNECTIONS
The probe shall be mounted with the bulb upwards to prevent damage due to casual liquid infiltration. It is
recommended to place the thermostat probe away from air streams to correctly measure the average room
temperature. The probe can be extended up to 300 ft. Check calibration when running long lengths over
100ft.
8.2 BATTERY BACK-UP
Battery Back-up will automatically power the XWA display in case of a power failure for up to 36 hours.
Display will flash when battery runs low. (Battery not included)
9. USE OF THE PROGRAMMING “HOT KEY”
The XWA11V units can UPLOAD or DOWNLOAD the parameter list from its own E2 internal memory to the
“HOT KEY” and vice versa.
9.1 TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)
1. Program one controller with the front keypad.
2. When the controller is ON, insert the “Hot key” and push UP key; the "uPL" message appears followed a
by flashing “End”
3. Push
“SET” key and the End will stop flashing.
4. Turn
OFF the instrument and remove the “Hot Key”, then turn it ON again.
NOTE: the “Err” message is displayed for failed programming. In this case push again key if you want
to restart the upload again or remove the “Hot key” to abort the operation.
9.2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD)
1. Turn OFF the instrument.
2. Insert a programmed “Hot Key” into the 5 PIN receptacle and then turn the Controller ON.
3. Automatically the parameter list of the “Hot Key” is downloaded into the Controller memory, the “doL”
message is blinking followed a by flashing “End”.
4. After 10 seconds the instrument will restart operation with the new parameters.
5. Remove
the “Hot Key”.
NOTE the message “Err” is displayed for failed programming. In this case turn the unit off and then on if
you want to restart the download again or remove the “Hot key” to abort the operation.
10. ALARM SIGNALS
Message Mode Cause Outputs
“P1” Flashing Probe failure Alarm output ON
“PoF” Flashing (3s) Keyboard locked Not changed
“Pon” Flashing (3s) Keyboard un-locked Not changed
“HA” Alternated with temp Maximum temperature alarm Alarm output ON
“LA” Alternated with temp Minimum temperature alarm Alarm output ON
“dA” Alternated with temp Door switch alarm Alarm output ON
“EA” Alternated with temp External alarm Alarm output ON
“PAn” Alternated with temp Serious external alarm Alarm output ON
dEF Alternated with temp Defrost is running Not changed
The alarm message is displayed until the alarm condition is reset.
10.1 SILENCING BUZZER
Once the alarm signal is detected the buzzer can be silenced by pressing the (UP) key. (tbA=y)