DOLD VARIMETER MK 9064N User manual

111.01.21 en / 335A
Your Advantages
• Preventive maintenance
• For better productivity
• Quicker fault locating
• Precise and reliable
• Min-, Max. value or window monitoring
• Measuring range up to AC/DC 600 V
• Large measuring ranges
• Simple configuration and fault diagnostic
• Auxiliary voltage ranges DC 24 V, AC 230 V, AC/DC 24 ... 230 V or
AC/DC 110 ... 400 V
Features
• According to IEC/EN 60255-1
• AC/DC voltage measuring (single-phase)
• Start up delay, on delay
• Manual reset
• LCD for indication of the measuring values
• Relay output
MK 9064N: 1 changeover contact
MH 9064: 2 x 1 changeover contacts
• Relay function selectable (energized/de-energized on trip)
• As option with plugable terminal blocks for easy exchange of devices
- With screw terminals
- Or with cage clamp terminals
• Width MK 9064N: 22.5 mm
• Width MH 9064: 45.0 mm
• Voltage monitoring AC/DC single-phase
• Voltage dependent switching at under- or overvoltage
0269462
MH 9064MK 9064N
• MH 9064
The MH 9064 has 2 relay outputs.
The voltage monitoring can be assigned ro relay 1 and /or relay 2
t
t
t
tatvM10858
>U
Hyst
11
14
U
UH
Example: Overvoltage monitoring with closed circuit operation
MK 9064N.11 MH 9064.12
ef
11
A1
+
12
A2
14
M10848
11
12 14
2111
A1
f
2212 24
14
A2
M10849
11
12 14
21
22 24
e
Monitoring technique
VARIMETER
Voltage relay
MK 9064N, MH 9064
Function Diagram
Circuit Diagrams
Applications
Approvals and Markings
More Information
The voltage relays MK 9064N and MH 9064 of the varimeter family pro-
vide a solution for an optimised monitoring of the function of an electrical
device. Single-phase AC and also DC can be measured, undervoltage,
overvoltage and voltage window are monitored and the measured value
is displayed on the front.
Product Description
Terminal designation Signal description
A1(+), A2 Auxiliary voltage AC or DC
e, f Voltage measuring input AC, DC
11,12,14 Indicator relay (C/O contact)
21, 22, 24 Indicator relay (C/O contact)
Connection Terminals
Translation
of the original instructions
All technical data in this list relate to the state at the moment of edition. We reserve the right for
technical improvements and changes at any time.

211.01.21 en / 335A
The unit needs a connected auxiliary supply.
It is designed for single phase AC/DC measurement.
The LED indicate the state.
Green: On, when auxiliary voltage present
Orange (flashes): No measurement;
unit in input mode
Red (short On, short Off): Failure overvoltage
If the measured value is higher then the upper end of scale value, the
display shows the fault message "OL"
The Device is programmable for AC- or DC- measuring.
On AC-measurement the rectified mean value is measured.
On sinusoidal input signals the RMS value is displayed.
After connecting the auxiliary supply to terminals A1-A2 the startup delay
disables the monitoring function so that changes on the input have no
influence on the relay output of the VARIMETER.
The device is in display (RUN) mode and continuously measures the actu-
al values. Pressing
Esc
for more than 3 sec starts the input mode.
If the setting value is exceeded the relay switches and the display indica-
tes this state. The display is inverted, flashes and shows the error.
The fault memory is selectable
With button the fault memory can be deleted.
On the unit MH 9064it is possible to assign different functions to the diffe-
rent relays so one can be used as pre-warning and the other as alarm out-
put. Relay output 1 switches when actual value exceeds the pre-warning
setting. If a second setting assigned to relay output 2 the unit gives an
Alarm signal. M11095
ef
Display “Rel.2” active
Display “Rel.1” active
Selection of
Functions / Setting and
measuring values
Change to setup mode (3...6s)
Change to Run mode (3...6s)
LED status indication
Error memory 1 active
Error memory 2 active
Active manual reset
Manual reset activated: flashes when me-
mory mode is ON and relay in failure state.
Reset with button " "
Contact state of the output relays
Function
Functional Notes
Setting
Indicators
Cursor LCD Display

311.01.21 en / 335A
Display (Run) - Mode Input-Mode
UP /
DOWN
After power up the relay is in display (Run) mode. The measurement is interrupted, the relays are in failure state and the
indicator LED has orange color
Buttons have no function Selection of parameters and setting of thresholds
ENTER
Manual reset, when manual reset is selected for output relay - Shifts cursor to the right
Reset works only when fault is removed - Saves the value no-voltage safe
- Pressing for more than 3 sec: Change to display (Run) mode.
Esc
Esc
- Pressing for more than 3 sec: Change to input mode - Shifts cursor to the left
- Leave setting without saving
LCD-Display
Rel.1Rel.2 Sp1Sp2
Rel.1Rel.2 Sp1Sp2
<U
Rel.1Rel.2 Sp1Sp2
>U
Rel.1Rel.2 Sp1Sp2
<U
Setting Parameter
< U Fault, when value drops under set point
> U Fault, when value exceeds set point
OFF Measurement disabled
If the adjusted threshold of at least one measuring function is exceeded, the corresponding relay output switches after the selected time delay tv and
the fault is indicated on the display.
Manual reset can be activated or de-activated and is operated with on the unit.
Limit values for Rel.1 and Rel.2
Selectable with buttons
.
Factory
setting
<U: Response value undervoltage
(Undervoltage relay) OFF
>U: Response value overvoltage,,
(Overvoltage relay) *
Hyst: response value hysteresis 5 %
tv: On delay for relays ( 0 ... 10 sec ) 0 s
A / R: Seting open- / closed circuit operation R
Sp: Error storage ( ON / OFF ) OFF
Response values can be deactivated. (OFF)
*) dependent to device-variant (measuring range)
Selectable with buttons
.
Factory
setting
ta:Start up delay, when auxiliary voltage connected
( 0.2 ... 10 s) 0.2 s
AC/DC Measuring voltage AC or DC AC
(Restore factory settings)
Before auxiliary voltage connected press button
Esc
.
During start press and hold.
The switching mode energized or de-energized on trip can be set in input
mode. The MH 9064 has 2 relay outputs. Monitoring function can be assig-
ned to Relay 1 and/or to Relay 2.
Operating
Adjustable Parameter Further Setting Parameter
Restore Factory Settings
Indicator output

411.01.21 en / 335A
Display (Run) - Modus Input-Mode
Display inverted when the actual value is in failure state. Measurement interrupted, relays are in failure state,
indicator LED orange color
No function Chose Rel1, Rel2, Ta, AC/DC and RUN
Chose parameter
Change and set response values for Rel1 and Rel2.
Reset fault memory:
Esc
Shift cursor to the left
Shift cursor to the right
Esc
For more the 3 sec, change to input mode For more than 3 sec, change to display mode
After connecting the auxiliary supply A1/A2 the unit is in display (Run)
mode:
The actual measured value is displayed continuously (AC or DC)
The display is inverted when a measured value is exceeds the settings..
With button the fault memory is reset.
Pressing button
Esc
for more than 3 sec the unit changes to input mode.
In input mode the measurement is disabled, the relays are in failure mode
and the indicator LED is orange.
With the buttons the different setting values can be chosen.
Move cursor position
One character to the right
Esc
One character to the left
Back to the Display (Run)-Mode
Press button 3 s OK New values stored
or
Press button
Esc
3 s; Break Values unchanged
RUN
on the display confirm with to change to display (Run) mode.
Ta
AC/DC
Rel2
Rel1
Esc 3s
Esc (Break) 3s Break
(cancel changes)
OK-
(return with new settings)
(OK) 3s
Start up delay
Measuring principle
AC or DC
Input-modeDisplay (Run) -
mode
Response value for Rel2
<U
RUN
U
AC [V]
DC [V]
M11096
Response value for Rel1
<U
>U
>U
Hysteresis
Hysteresis
A/R
A/R
Sp1
Sp2
t1
v
t2
v
Operating

511.01.21 en / 335A
Auxiliary voltage A1/A2
Nominal auxiliary voltage UH
MK 9064N, MH 9064: DC 24 V (0,9 ... 1,1 x UH)
MH 9064: AC 230 V (0,8 ... 1,1 x UH)
AC/DC 24 ... 230 V (0,8 ... 1,1 x UH)
AC/DC 110 ... 400 V (0,8 ... 1,1 x UH)
Nominal frequency: 50 / 60 Hz
Frequency range: 45 ... 400 Hz
Input current
At DC 24 V: 50 mA
At AC 230 V: 15 mA
Voltage Measuring Input L+/L
MK 9064N:
Nominal voltage: AC/DC 150 mV,
AC/DC 5, 80, 300 V
Measuring range UM: AC/DC 6 ... 150 mV,
AC/DC 0,2 ... 5, 5 ... 80 , 12 ... 300 V
(0.8 ... 1.1 x UM)
MH 9064:
Nominal voltage: AC/DC 150 mV,
AC/DC 5, 80, 600 V
Measuring range UM: AC/DC 6 ... 150 mV,
AC/DC 0,2 ... 5, 5 ... 80, 24 ... 600 V
(0,8 ... 1,1 x UM)
Nominal frequency: 50 / 60 Hz
Frequency range: 10 ... 400 Hz
Setting Range (absolute, via button and LCD-display)
Measuring accuracy
at nominal frequency
(in % of setting value): ±2 % ± 2 Digit
Hysteresis
(in % of setting value): 2 ... 50 %
Reaction time: < 350 ms
Adjustable on delay (tv): 0 ... 10 s (in steps of 0.1 s)
Adjustable start up delay (ta): 0.2 ... 10 s (in steps of 0.1 s)
Output Circuit (Rel1: 11/12/14; Rel2: 21/22/24)
Contacts:
MK 9064N: 1 changeover contact
MH 9064: 1 changeover contact (Rel1) and
1 changeover contact (Rel2)
Thermal current I th:2 x 4 A
Switching capacity
To AC 15
NO contacts: 3 A / AC 230 V IEC/EN 60947-5-1
NC contacts: 1 A / AC 230 V IEC/EN 60947-5-1
To DC 13
NO contacts: 1 A / DC 24 V IEC/EN 60947-5-1
NC contacts: 1 A / DC 24 V IEC/EN 60947-5-1
Electrical life
To AC 15 at 3 A, AC 230 V: 2 x 105switch. cycl. IEC/EN 60947-5-1
Permissible switching
frequency: 1800 / h
Short circuit strength
Max. fuse rating: 4 A gG / gL IEC/EN 60947-5-1
Mechanical life: 30 x 106switching cycles
General Data
Nominal operating mode: Continuous operation
Temperature range
Operation: - 20... + 60°C
(at range 0 ... - 20°C limited
function of the LCD display)
Storage: - 25... + 60°C
Altitude: < 2000 m
Clearance and creepage distance
Overvoltage category: III
Rated impulse voltage /
pollution degree: IEC/EN 60664-1
MK:
Aux. voltage / measuring input: 4 kV / 2
Aux. voltage / contacts: 6 kV / 2
Measuring input / contacts: 6 kV / 2
MH:
Aux. voltage / measuring input: 4 kV / 2 (UH= DC 24 V)
Aux. voltage / measuring input: 6 kV / 2
Aux. voltage / contacts: 6 kV / 2
Measuring input / contacts: 6 kV / 2
Contacts 11,12,14 / 21,22,24: 4 kV / 2
EMC
Electrostatic discharge (ESD): 8 kV (air) IEC/EN 61000-4-2
HF irradiation
80 MHz … 6.0 GHz: 20 V / m IEC/EN 61000-4-3
Damped oscillatory wave
immunity test
Differential mode voltage: 1 kV IEC/EN 61000-4-18
Common mode voltage: 2.5 kV IEC/EN 61000-4-18
Fast transients: 2 kV IEC/EN 61000-4-4
Surge voltage
Between
wires for power supply: 1 kV IEC/EN 61000-4-5
Between wire and ground: 2 kV IEC/EN 61000-4-5
HF-wire guided: 10 V IEC/EN 61000-4-6
Interference suppression: Limit value class A*)
*) The device is designed for the usage
under industrial conditions (Class A,
EN 55011).
When connected to a low voltage public
system (Class B, EN 55011) radio inter-
ference can be generated. To avoid this,
appropriate measures have to be taken.
Degree of protection
Housing: IP 40 DIN EN 60529
Terminals: IP 20 DIN EN 60529
Housing: Thermoplastic with VO behaviour
according to UL Subject 94
Vibration resistance: Amplitude 0.35 mm,
frequency 10 ... 55 Hz IEC/EN 60068-2-6
Climate resistance: 20 / 060 / 04 EN 60068-1
Wire connection: DIN 46228-1/-2/-3/-4
Screw terminal
(fixed): 1 x 4 mm2solid or
1 x 2.5 mm2stranded ferruled (isolated) or
2 x 1.5 mm2stranded ferruled (isolated) or
2 x 2.5 mm2solid
Insulation of wires or
sleeve length: 8 mm
Terminal block
with screw terminals
Max. cross section: 1 x 2.5 mm2
solid or
1 x 2.5 mm2stranded ferruled (isolated)
Insulation of wires or
sleeve length: 8 mm
Terminal block
with cage clamp terminals
Max. cross section: 1 x 4 mm2solid or
1 x 2.5 mm2stranded ferruled (isolated)
Min. cross section: 0.5 mm2
Insulation of wires or
sleeve length: 12 +0.5 mm
Wire fixing: Plus-minus terminal screws M3,5 box
terminals with wire protection
or cage clamp terminals
Fixing torque: 0.8 Nm
Mounting: DIN rail EN 60715
Weight:
MK 9064N: Approx. 140 g
MH 9064: Approx. 250 g
Dimensions
Width x height x depth:
MK 9064N: 22.5 x 90 x 99 mm
MH 9064: 45 x 90 x 99 mm
Technical Data Technical Data
Vibration and
shock resistance: Category 1, Class B IEC/EN 61373
Ambient temperature: T1 compliant
T2, T3 and TX with operational limitations
Protective coating of the PCB: No
Classification to DIN EN 50155

611.01.21 en / 335A
The connection has to be made according to the connection example.
M10860
L1
L
N
L2
11
11 21
12
12 22
14
14 24
21 22 24
MH9064.12
f
eA1
(+)
A2
Removing the terminal blocks with cage clamp terminals
1. The unit has to be disconnected.
2. Insert a screwdriver in the side recess of the front plate.
3. Turn the screwdriver to the right and left.
4. Please note that the terminal blocks have to be mounted on the
belonging plug in terminations.
Screw terminal
(PS/plugin screw)
Cage clamp terminal
(PC/plugin cage clamp)
Dangerous voltage.
Electric shock will result in death or serious injury.
Disconnect all power supplies before servicing equipment.
- Faults must only be removed when the relay is disconnected
- The user has to make sure that the device and corresponding compo-
nents are installed and wired according to the local rules and law
(TUEV, VDE, Health and safety).
- Settings must only be changed by trained staff taking into account the
safety regulations. Installation work must only be done when power is
disconnected.
- Observe proper grounding of all components
Options with Pluggable Terminal Blocks
Notes
Connection Examples
Set Up Procedure
Safety Notes
MK 9064N.11 AC/DC 12 ... 300 V DC 24 V
Article number: 0065254
•Measuring range: AC/DC 12 ... 300 V
•Auxiliary voltage UH: DC 24 V
•Output: 1 changeover contact
•Width: 22.5 mm
MH 9064.12 AC/DC 24 ... 600 V AC/DC 110 ... 400 V
Article number: 0065256
•Measuring range: AC/DC 24 ... 600 V
•Auxiliary voltage UH: AC/DC 110 ... 400 V
•Output: 1 changeover contact (Rel1) and
1 changeover contact (Rel2)
•Width: 45 mm
MK 9064N .11 _ _ AC/DC 12 ... 300 V DC 24 V
Auxiliary voltage UH
Measuring range UM
Type of terminals
Without indication:
Terminal
blocks fixed
with screw terminals
PC (plug in cage clamp):
Pluggable
terminalblocks
withcageclampterminals
PS (plug in screw):
Pluggableterminalblocks
with screw terminals
Contacts
Type
Standard Types
Ordering Example
E. Dold & Söhne GmbH & Co. KG • D-78120 Furtwangen
dold-relays
@dold.com • www.dold.com
• Bregstraße 18 • Phone +49 7723 654-0 • Fax +49 7723 654356
This manual suits for next models
1
Table of contents
Other DOLD Relay manuals
Popular Relay manuals by other brands

BECKWITH ELECTRIC
BECKWITH ELECTRIC Syncrocloser M-3410A Instruction book

Hella
Hella 4RD 980 830-001 / 3099 Operation and installation instructions

Vitals
Vitals Rs 50k Manual For Technical Use

VAMP
VAMP 265 Operation and configuration instructions

Schrack
Schrack Amparo URAU3N11 Assembly and installation instructions

Metz Connect
Metz Connect C Logline MARK-E08 Mounting Note