DOLD VARIMETER RCM User manual

104.03.20 en / 201A
0272374
Your Advantage
• Preventive fire and system protection
• Increasing the availability of plants by early fault detection
• Universal usage at AC/DC mains
• Protection against manipulation by sealable transparent cover
over setting switches
Features
• According to IEC/EN 62020, VDE 0663
• For AC and DC systems Type B
• To detect earth faults in grounded voltage systems
• 4 setting ranges from 10 mA to 3 A
• Manual reset, with alarm and pre-warning
• With adjustable switching delay
• Energized or de-energized on trip
• LED indicator for operation, pre-alarm and alarm
• With test function
• LED-chain indicates fault current
• As option with analogue output
• Broken wire detection
• Width: 52.5 mm
The residual current monitor type B is designed to monitor DC systems
and AC systems up to 250 Hz.
green LED „ON“: On, when auxiliary supply connected
yellow LED „Pre-Alarm“: Flashes during time delay tv
On, when pre-alarm active
red LED „Alarm“: Flashes during time delay tv
On, when alarm active
yellow and red LED: Flashes on broken wire or extremely high input
signal
yellow LED-chain: LED chain indicates fault current in % of adjusted
alarm value
1) RN 5883 Variant /61; 2) ND 5015
The devices measure AC and DC current (AC / DC sensitive. Due to the
measurement principle they also detect magnetic fields in the next to the
current transformer.
When planning a panel with AC/DC sensitive residual current monitors
please make sure that no components are placed next to the CT that
create a magnetic field, e.g. contactors, transformers etc.
If an influence is detected, also a rotation of the CT by 90° could positively
reduce the influence.
The AC/DC sensitive residual current monitor RN 5883 allows an early
detection of insulation faults and detects differential currents with AC
as well as DC components in grounded voltage systems (type B). The
measurement takes place via an external current transformer.
Contrary to an RCD the residual current monitor RN 5883 does not dis-
connect the mains when detecting a fault but only indicates it. Besides
the easy to read LED chain indicating the actual current several LEDs
display operation, pre-alarm and alarm. The 4 measuring ranges cover
10 to 3 A. Additional features are broken wire detection, test function and
adjustable pre-alarm.
The residual current monitor RN 5883 provides early information for precise
and cost effective maintenance before the plant stops.
RN 5883
M11213
11 14
A1 k1 k2
12 21 22 24 U+ U-
A2 i1 i2 X1 X2
A1
X1
i1
i2
k1
k2
A2
X2
11
21
12
22
14
24
Alarm
Pre - Alarm
IF
0...10V
U+ U-
Installations- / Monitoring Technique
VARIMETER RCM
Residual Current Monitor,Type B for AC and DC Systems
RN 5883
Approvals and Markings
Product Description
Circuit Diagram
Application
Indication
NotesConnection Terminals
Terminal designation Signal description
A1, A2 Auxiliary voltage UH
i1, k1, i2, k2 Connection of an external
residual current transformer
X1, X2 Parameterization input
energized or de-energized on trip
11, 12, 14 Contacts alarm signal
21, 22, 24 Contacts pre-alarm signal
U-, U+ Analogue output (option)
ND 5015/035 ND 5015/070
Canada / USA
1)
A025518
Canada / USA
2)
All Technical Data in this list relate to the state at the moment of edition. We reserve the rigth for
technical improvements and changes at any time.

204.03.20 en / 201A
The Measuring circuit includes an external residual current transformer.
All conductors of a voltage system are fed through the transformer except
the ground wire. In a healthy system the sum of all flowing currents is zero,
so that no voltage is induced in the CT. If an earth fault occurs, sourcing a
current flowing to ground, the current difference induces a current in the
CT that is detected by the RN 5883.
If an earth fault occurs, sourcing a current flowing to ground, the current
difference induces a current in the CT that is detected by the RP 5883.
On broken sensor wires and broken CT coils the unit goes into alarm state
and the LEDs for pre-alarm (yellow) and alarm (red) flashes.
The unit has 2 changeover output contacts. One for alarm 11, 12, 14 and
21, 22, 24 and one for pre-alarm.
4 Setting Ranges can be slected from 10 mA to 3 A. The fine adjustment
is made via potentiometer „Factor“
Measuring range = Range x Factor.
The alarm relay switches at 100 % of the adjusted response value.
The pre-alarm can be set in 10% steps between 10 and 100% of the
alarm value.
Potentiometer tvsets the switching delay between 0 and 10 seconds. The
delay reacts on pre-alarm and alarm.
The different CT sizes require a correct adaption of the residual current
monitor. 3 models are available:
Type
Suitable
residual current
transformer
Frequeny range
RN 5883.12/61 ND 5015/024
ND 5015/035 DC + AC up to 250 Hz
RN 5883.12/010/61 ND 5015/070 DC + AC up to 180 Hz
RN 5883.12/020
ND 5018/105
ND 5018/140
ND 5018/210
DC + AC up to 60 Hz
Table 1
An external link on X1-X2 allows the change between energized and de-
energized on trip. A change of the function will only be valid after interrup-
tion of the supply voltage.
Terminal X1 / X2: external link = De-energized on trip,
open = Energized on trip
De-energized on trip: In the case of groundfault or missing auxiliary supply
the relays are de-energized,
the NC contacts 11/12; 21/22 are closed
In fault free state the relays are energized,
the NO contacts 11/14; 21/24 are closed
Energized on trip: In the case of groundfault the relays are energized,
the NO contacts 11/14; 21/24 are closed
in fault free state the relays are de-energized,
the NC contacts 11/12; 21/22 are closed
If an adjusted value is reached on the measuring input (alarm or pre-
warning)at the standard type RN 5883 the signal is stored. Reset is made
by pressing the button „Test/Reset“ for < 3 s s or by disconnecting the
auxiliary supply (approx. 30 s).
If the „Test/Reset“ button is pressed for > 3 s, a test of the unit is made.
The time delays run, the pre-warning and alarm is activated.
An LED chain shows the fault current between 10 and 100 % of the adju-
sted alarm value.
An analogue output 0 ... 10 V indicates also the fault current. 10 V corre-
sponds to 100 % of the adjusted alarm value.
It is of advantage to keep the range small and the Factor high.
Example: Setting 300 mA: Range 0,1 x Factor 3 = 300 mA
Set-up and Adjustment Facilities
Function
M11736
LED "ON"
U connected
H
LED „Pre-Alarm“
LED "Alarm"
LED chain
I=
e.g.
pA IA x setting in %
: I=60mA x 50% = 30mA
Pre-alarm relay trips at 30mA
LED chain shows at that moment 50%
pA
Pushbutton
<3s = reset fault memory
>3s = devise test
I:Pre-Alarm
pA
I:Alarm value = Range x Factor
A
e.g.: I=0,01A x 6 = 60mA
A
I=Alarm relay trips at 60mA
LED chain shows at that
moment 100%
A
t:response delay reacts on Alarm
and Pre-Alarm
v
RN 5883.12/001

304.03.20 en / 201A
Input
Auxiliary voltage UH:AC/DC 24 ... 80 V, AC/DC 80 ... 230 V
Voltage range
at UH= AC/DC 24 ... 80 V: DC 19 ... 110 V, AC 19 ... 90 V,
at UH= AC/DC 80 ... 230 V: DC 64 ... 300 V, AC 64 ... 265 V
Nominal frequency UH:AC 50 / 60 Hz
Nominal consumption
at AC: 5 VA
at DC: 2.5 W
Measuring range: 10 ... 100 mA, 30 ... 300 mA,
100 ... 1000 mA, 300 ... 3000 mA
(3 ... 30 mA on request)
Measuring range
fine adjustment: 1 ... 10
Überlastbarkeit: with overload protection
Alarm: 100 % of the adjusted measuring range
Pre-alarm: 10, 20, 30, 40, 50, 60, 70, 80, 90, 100 %
of the adjusted alarm value
Frequency range: DC and AC to 250 Hz*)
*) depending on the differential current
transformer used. See „Function“ Table 1.
Repeat accuracy: ≤±3 %
Temperature drift: ≤±0.1 % / K
Reaction time: 300 ms
Switching delay
Pre-alarm / alarm: 0 ... 10 s
Output
Contacts: 1 changeover contact for pre-alarm,
1 changeover contact for alarm
Thermal current Ith
up to 30 °C: 5 A
up to 40 °C: 4 A
up to 60 °C: 2 A
Switching capacity
at AC 15:
NO contact: 3 A / AC 230 V IEC/EN 60947-5-1
NC contact: 1 A / AC 230 V IEC/EN 60947-5-1
Electrical life
to AC 15 at 1 A, AC 230 V: 3 x 105switch. cycl. IEC/EN 60947-5-1
Short circuit strength
max. fuse rating: 4 A gG / gL IEC/EN 60947-5-1
Mechanical life: ≥108switching cycles
Analogue Output (option)
Terminal U+ / U-: 0 ... 10 V; 5 mA
variant RN 5883/_ _1
Screened wire; screen one end grounded
at device to PE
General Data
Operating mode: Continuous
Temperature range
Operation: - 40 ... + 60°C
- 20 ... + 60°C (variant /_1_ and /_2_)
Storage: - 40 ... + 70°C
Altitude: < 2000 m
Insulation coordination
according to IEC 60664-1:
RN 5883 cennected with
current transformer ND 5015, ND 5018
Rated impuls voltage /
pollution degree:
Auxiliary voltage / Meas. circuit: 6 kV / 2
Auxiliary voltage / Contacts: 6 kV / 2
Auxiliary voltage / Analoge output: 6 kV / 2
Contacts / Analoge output: 6 kV / 2
Meas. circuit / Analoge output: 6 kV / 2
Contacts 11,12,14 / 21, 22, 24: 4 kV / 2
EMC
Surge voltages: Class 3 (5 kV / 0.5 J) DIN VDE 0435-303
Electrostatic discharge: 8 kV (air) IEC/EN 61000-4-2
HF irradiation
80 MHz ... 2,7 GHz: 20 V / m (class 3) IEC/EN 61000-4-3
HF-wire guided: 10 V (class 3) IEC/EN 61000-4-6
Fast transients: 2 kV (class 3) IEC/EN 61000-4-4
Surge voltages: 1 kV class 3) IEC/EN 61000-4-5
Interference suppression: Limit value class B EN 55011
Degree of protection
Housing: IP 30 IEC/EN 60529
Terminals: IP 20 IEC/EN 60529
Housing: Thermoplastic with V0-behaviour
according UL subject 94
Vibration resistance: Amplitude 0.35 mm
frequency 10 ... 55 Hz IEC/EN 60068-2-6
Climate resistance: 40 / 60 / 03 IEC/EN 60068-1
Terminal designation: EN 50005
Wire connection: DIN 46228-1/-2/-3/-4
Fixed screw terminals
Cross section: 0.5 ... 4 mm² (AWG 20 - 10) solid or
0.5 ... 4 mm² (AWG 20 - 10)
stranded wire without ferrules
0.5 ... 2.5 mm² (AWG 20 - 10)
stranded wire with ferrules
Stripping length: 6.5 mm
Wire fixing: Cross-head screw / M3 box terminals
Fixing torque: 0.5 Nm
Mounting: DIN rail IEC/EN 60715
Weight: approx. 160 g
Dimensions
Width x height x depth: 52.5 x 90 x 71 mm
These devices only monitor residual currents and are not intended to
be used as Ground Fault Circuit Interrupter (GFCI) in accordance with
UL1053 / UL943.
These devices have been investigated to be used with external differen-
tial current transformers manufactured by E. Dold & Söhne KG, Cat. Nos.
ND5015/024/61, ND5015/035/61 or ND5015/070/61.
Supply voltage UN: AC/DC 24-80V single or double phase
50/60 Hz;
AC/DC 80-230V single or double phase
50/60 Hz
Switching capacity relays
Ambient temperature 30°C: 5A, 250Vac G.P.
250 Vac, 2A pilot duty
250 Vac, 1/2hp
Ambient temperature 40°C: 4A, 250Vac G.P.
250 Vac, 2A pilot duty
250 Vac, 1/2hp
Ambient temperature 60°C: 2A, 250Vac G.P.
Analogue output
(only at variant/__1): 0 .. 10V, 5mA
Max. measuring frequency: DC, AC (0 – 250Hz)
Wire connection: AWG 20 - 12
60°C / 75°C copper conductors only
nfo
Technical data that is not stated in the UL-Data, can be found
in the technical data section.
Technical Data Technical Data
UL-Data RN 5883

404.03.20 en / 201A
for DIN rail mounting or screw mounting
Residual Current Monitor ND 5015/024, ND 5015/035
Ambient temperature: - 40 ... + 60°C / 233 K ... 333 K
Inflammability class: V0 according to UL94
Insulation coordination according to IEC 61869-1
Highest rated operating voltage Um: AC 720 V
Rated impulse voltage: 3 kV
Length of connection wires
Type of wire to CT, e.g.
Single wire: up to 1 m
Single wire twisted pair (pair 1: i1 - k1; pair 2: i2 - k2): up to 10 m
Screened wire; screen one end grounded at device to PE: up to 25 m
Wire cross section: 0.2 ... 1.5 mm2
Stripping length: 8 mm
ND 5015:
Wire fixing: Terminals with spring connection and
direct (Push in) technology
Actuation power: 40 N max.
DIN rail mounting: integrated clips for vertical and
horizontal mounting
Screw fixing: M3 or M4
Fixing torque: max. 0.8 Nm
ND 5018:
Wire fixing: Flat terminals with self-lifting clamping piece
DIN rail mounting: using mounting adapter ET 5018
Screw fastening: (only at ND 5018/105, ND 5018/140, ND 5018/210) M 5
M10979_b
B
E
F
k
D
H
L1
L
C
ND 5015/024 øD L L1 B H C E F k
Dimensions/mm 24 82 75 24 54 25 42* 46 4.2
Weight / g approx. 80
ND 5015/035 øD L L1 B H C E F k
Dimensions/mm 35 88 81 24 67 25 42* 46 4.2
Weight / g approx. 90
*)Drill tolerance for screw mounting: ± 0.5 mm
RN 5883.12/61 AC/DC 80 ... 230 V 50 / 60 Hz
Article number: 0066451
• For residual current transformer ND 5015/024 and ND 5018/035
• Alarm und Pre-alarm
• Energized or de-energized on trip
• Without analogue output
• Auxiliary voltage UH: AC/DC 80 ... 230 V
• Width: 52.5 mm
ND 5015/035/61
Article number: 0066841
• Residual current transformer for RN 5883
• Diameter: 35 mm
For residual current transformer ND5015/024 und ND5015/035:
RN 5883.12/001/61: With analogue output 0 ... 10 V
RN 5883.12/800/61: Fixed values, without analogue output
RN 5883.12/802/61: Fixed values, without analogue output;
with bridge on X1/X2:
- Alarm: Energized on trip
- Pre-alarm: De-energized on trip
without bridge:
- Alarm: De-energized on trip
- Pre-alarm: Energized on trip
Für residual current transformer ND5015/070:
RN 5883.12/011/61: with analogue output 0 ... 10 V
For residual current transformer ND5018/105, ND5018/140,
ND5018/210:
RN 5883.12/021: with analogue output 0 ... 10 V
Ordering example for variants
RN 5883 .12 /_ _ _ /61 AC/DC 80 ... 230 V 50 / 60 Hz
Nominal frequency
Auxiliary voltage
UL approval
Variant, if required
Contacts
Type
Standard Type
Variants
Accessories
Technical Data Residual Current Monitor ND 5015, ND 5018
Wire connection: AWG 24 - 16
60°C / 75°C copper conductors only
nfo
Technical data that is not stated in the UL-Data, can be found
in the technical data section.
UL-Daten ND 5015
CCC-Data RN 5883
Insulation coordination
according to IEC 60664-1:
RN 5883 cennected with
current transformer ND 5015, ND 5018
Rated impuls voltage /
pollution degree:
Auxiliary voltage / Meas. circuit: 4 kV / 2
Auxiliary voltage / Contacts: 4 kV / 2
Auxiliary voltage / Analoge output: 4 kV / 2
Contacts / Analoge output: 4 kV / 2
Meas. circuit / Analoge output: 4 kV / 2
Contacts 11,12,14 / 21, 22, 24: 4 kV / 2

504.03.20 en / 201A
Residual Current Monitor ND 5018/105, ND 5018/140, ND 5018/210,
for screw mounting
DB
m
k
E
F
L
H
M7486
D
C
ND 5018/105 øD L B H C D E F k m
Dimensions/mm 105 170 33 146 38 94 46 61 6.5 16
Weight / g 530
ND 5018/140 øD L B H C D E F k m
Dimensions/mm 140 220 33 196 48.5 123 46 61 6.5 16
Weight / g 1250
ND 5018/210 øD L B H C D E F k m
Dimensions/mm 210 299 33 284 69 161 46 61 6.5 16
Weight / g 2100
The residual current transformer ND 5018/105 can also be mounted on
DIN-rail. To do this the metal screw fixings have to be removed and have
to be replaced by 2 mounting clips
(ET5018: art.no. 0058754; set with 2 pcs)
for DIN rail mounting or screw mounting
ND 5015/070 øD L H H1 B C F k E G
Dimensions/mm 70 111 110 115 32 37 55 4,2 50* 74*
Weight / g approx. 220
*)Drill tolerance for screw mounting: ± 0.5 mm
Residual Current Monitor ND 5015/070
Accessories
High forces when mounting may damage the current transformer fixtures.
The fixing clips are designed to support the current transformer. Forces
that are applied by the cable running through the current transformer can
only be tolerated within limitations.
During installation and afterwards please make sure that the wires are
led through the current transformer without applying pressure and remain
stable in that position.
Mounting instructions for screw mounting
B
E
F
k
D
H
H1
L
CC
G
M11582_a

604.03.20 en / 201A
Accessories
Residual Current Monitor ND 5018/105
for DIN rail mounting
Disassembling Residual Current Monitor ND 5015/024 and /035
M11123
Disassembling Residual Current Monitor ND 5015/070
DB
L
H
M9777_b
G
ND 5018/105 øD L B H G
Dimensions/mm 105 170 33 146 55
Weight / g 530
M11583

704.03.20 en / 201A
Connection Example
Installation of Wires
PE
PE
PENNL1
L+
L1
L1
L2
L-
L2
L2
L3 L3
L3
M8362_a
PE
L1
L2
L3
N
i1 i2k1 k2
X1 X2 11 12 14 21 22 24
A1 A2
RN5883
i1
i2
k1
k2
X1-X2 open : operating current
X1-X2 bridged : de-energized
alarm
indicator contact
pre-alarm
11 21
M11294
12 14 2422
monitoring phase

804.03.20 en / 201A
E. DOLD & SÖHNE KG • D-78114 Furtwangen
e-mail: dold-relays
@dold.com • internet: http://www.dold.com
•
POBox 1251•Telephone(+49) 7723 / 654-0 • Telefax (+49) 77 23 / 654-356
This manual suits for next models
1
Table of contents
Other DOLD Relay manuals