domat UC220 User manual

domat UC220 03/2017 Subject to technical changes. 1
UC220
Communicative heating and
cooling controller, 0..10 V output
Summary
UC220 is a communicative room heating controller with two binary inputs and two
0...10 V DC outputs for control of a radiator or electrical heater and a cooling valve
(cooling panels, chilled ceilings). It can work autonomously, or in connection to a
primary controller (MiniPLC or SoftPLC), or building management system (RcWare
Vision or any SCADA).
Application
Systems with radiators, electric heaters, or floor heating, and chilled
ceilings or panels –control and measuring of room temperature
monitoring and communication of room temperatures
Function
The controller reads actual room temperature, setpoint shift by a knob, and set
operation status which is set by short push of the knob. The room temperature is
measured in the range of -20 to +70 °C. Measured and set values are processed in a PI
algorithm, which is brought to sequence block and two 0..10 V DC outputs. All values
are displayed on a large LCD display.
The functionality and control parameters, i.e. P and I constants, and hysteresis, can be
set with ModComTool, the configuration software, which is free to download at
http://domat-int.com/en/downloads/software.
The controller contains real time clock with a weekly scheduler (6 events per day). It
changes between three operation modes: Day, Night, and Off. A short push in the Night
mode switches to Party mode –Comfort extension by 2 hours.
The digital inputs read signals from a window contact and presence sensors. They can
be used optionally.
The communication bus is Modbus RTU over RS485, therefore the controllers are easily
to integrate into any SCADA or BMS system. Protocol description is available in a
separate document.

domat UC220 03/2017 Subject to technical changes. 2
Technical data
Power
16...35 V DC (typical 24 V DC)
Consumption
1400 mVA
Measuring range
-20 ÷ 70 °C
Protection
IP20
Sensor accuracy
+/- 1,5 K (with software correction)
Inputs
Input current
Input voltage
for dry contact
2.4 mA
24 V DC, derived from the power voltage
Outputs
Maximum output current
Short-circuit current
Resolution
2x 0...10 V DC
10 mA (corresponding to 1 kOhm load)
50 mA, tolerant to permanent short-circuit
10 bit D/A converter
Setpoint correction
according to configuration, +/- 10 to +/- 1 K
Communication
RS485 separation
Baud rate
2 wire RS485 - Modbus RTU slave
optically separated up to 1000 V
selectable, 1200...9600...115200 bps
Display
LCD, 60 x 60 mm
Terminals
screw terminals for 0,14 –1,5 mm2wires
Cover
ABS, RAL9010, other colours
Weight
0,13 kg
Dimensions
see below
Terminals
1
2
3
4
5
6
7
8
9
Terminals as seen from above in the bottom
part:
1: DI1 presence input (active by connecting
to G0)
2: DI2 window contact input (active by
connecting to G0)
3: AO1 0...10 V heating output
4: G0 power -, output –reference point
5: AO2 0...10 V cooling output
6: G0 power -, output –reference point
7: G power +
8: K- communication RS485 -
9: K+ communication RS485 +

domat UC220 03/2017 Subject to technical changes. 3
DIP switches
Back of the PCB
BUS END: if ON, the bus is terminated (if last
device on the line)
USR: not used, reserved for future
applications
INIT: sets the controller into default state
and sets bus address to 1, baud rate to 9600.
To init, proceed as follows:
- connect the device over RS485 to a PC with
ModComTool config tool
- set INIT to ON
- apply power (use only the connector
without bottom)
- find the controller in the tool (Scan)
- set INIT to OFF
- in the ModComTool tool, open the
controller window
- click the Init button in the tool
- remove and apply power.
Installation
Units are intended for operating in a normal and chemically non-aggressive
environment. They do not need any servicing or maintenance. Install them in a vertical
position at places where they can be operated easily and measure correct values of
temperature, i.e. in the height of about 150 cm, with no direct sunlight or other heat /
cool source (AHU outlets, refridgerator, electrical appliances). The device consists of
two parts: bottom with screw terminal block and cover containing PCB, display, and the
knob. The bottom part is fixed by 2 or 4 screws to any flat surface or a flush-mounting
box Ø 50 mm. At the back of the bottom there is an aperture for cabling. The bottom
should be installed and cabling connected first, and the upper part inserted after the
construction works have been finished to prevent damage to the unit.
Seal the conduits to avoid influencing the sensor by draught. Use insulating pad when
installing the sensor on cold walls. Avoid sensor exposition to sunlight or other heat
sources.
Opening the
cover
When removing the display part, proceed as follows:
-press gently the side parts of the unit and pull the right of the display part by
several milimeters
-pull the left of the display part
-pull the display part and remove it from the bottom.

domat UC220 03/2017 Subject to technical changes. 4
Do not bend the display part too much, the connector pins could be damaged. The locks
are only at the sides of the display part, not at the top nor bottom.
User settings
Temperature correction:
Turn the knob clockwise to increase setpoint, turn it counter clockwise to decrease
setpoint. The maximum correction range can be modified over the bus e.g. with the
ModComTool configuration tool.
Operation mode change:
Push the knob shortly (<1 s). Each push changes the operation mode to Party –Day –
Night –Off –Auto.
In the Auto mode, the Day / Night / Off modes change according to time schedule).
The Party mode overrides to Comfort for 120 minutes, then follows the actual time
schedule.
The weekly time schedule switches between Day, Night, and Off modes according to the
event list. There may be up to 6 events per day.
Time schedule settings:
Switch to the time schedule settings mode with a long push (>1 s). The controller
switches to settings mode (clock icon).
Turn the knob to select the weekday (1 to 7). Then short push to confirm the selection.
Turn the knob to select the event (large number 1 to 6). Each event displays the mode
activated by this event.
Short push to confirm the event selection. Turn the knob to select the operation mode
(Day, Night, Off, Event inactive) invoked by this event. If the event is not active, the
operation mode is not changed at the set time.
Short push to confirm the operation mode setting. The event time displays. Turn the
knob to set the time of the event and confirm by a short push. Then turn the knob to
select another event or long push and turn the knob to select another weekday.
After all desired events have been edited, long push to leave the time schedule settings.
The controller goes to the basic display mode also after 30 secs of user inactivity.
Change of setpoints and controller time:
Switch to the settings mode with a super long push (>2.5 s). The controller switches to
settings mode (flashing thermometer icon).
Turning the knob selects between following settings:
Controller time and day of week (Clock icon, Day of week)
Setpoint temp. Heating Day mode (Temperature, Heating, Day are flashing)
Setpoint temp. Heating Night mode (Temperature, Heating, Night are flashing)

domat UC220 03/2017 Subject to technical changes. 5
Setpoint temp. Heating Off mode (Temperature, Heating, Empty house are flashing)
Setpoint temp. Cooling Day mode (Temperature, Cooling, Day are flashing)
Setpoint temp. Cooling Night mode (Temperature, Cooling, Night are flashing)
Setpoint temp. Cooling Off mode (Temperature, Cooling, Empty house are flashing)
Select the requested value by a short push. Turn knob to change value. Confirm by a
short push again.
If there is no user activity for 30 secs, the controller goes to the basic display mode.
Default values:
The default values as well as all other settings (PI parameters, address, baud rate...) can
be set by the configuration program, ModComTool.
Dimensions
All dimensions in mm.

domat UC220 03/2017 Subject to technical changes. 6
Connection
Connection of power and communication. Suitable cable types are LAM DATAPAR 2x0.8
(cross-section in mm2), JYTY 2x1 (diameter in mm) etc. If communication and power are
in the same cable, use 4-core LAM DATAPAR 2x2x0.8, JYTY 4x1. Up to 100-120 meters,
parallel lines of 24 V and data bus are no problem. Regarding to EMC it is better if the
pairs are twisted, such as with the LAM DATAPAR or Belden 8205 cable.
A terminal is designed for maximum 3 wires of 0.8 mm2.
Temperature
compensation
After switching the unit on, allow about 90 mins to dissipate the heat inside of the
housing. Then the sensor is measuring correctly. Do not change the sensor correction
variable immediately after powering the device on.
RoHS notice
The device contains a non-rechargeable battery which backups the real-time clock and
part of the memory. After the device is not operable, please return it to the
manufacturer or dispose of it in compliance with local regulations.
1
2
3
4
5
6
78
9
1
2
3
4
5
6
78
9
24 V =
UC120UC220
RS 485
+
-
+
-
G0
G0
G
DI1
G0
G0
G
DI1
AO1 AO1
AO2
DI2
AO2
DI2

domat UC220 03/2017 Subject to technical changes. 7
Changes in
versions
09/2016 —Changed reference to the configuration software and deleted Related
products.
03/2017 —Added picture and description of the installation and link on the datasheet
with other colours.
Table of contents
Other domat Thermostat manuals

domat
domat UI90 Series User manual

domat
domat THERMASGARD RTM Repair manual

domat
domat UI0 Series User manual

domat
domat UC300 User manual

domat
domat UC100 User manual

domat
domat UI0 BL Series User manual

domat
domat UC120 User manual

domat
domat US100 User manual

domat
domat UX0 Series User manual

domat
domat UI0 Series User manual
Popular Thermostat manuals by other brands

Carrier
Carrier debonair 33cssn2-wc owner's manual

Honeywell
Honeywell FocusPRO Wi-Fi TH6000 Series operating manual

resideo
resideo TB7100A1000 MultiPRO manual

Agilent Technologies
Agilent Technologies 1260 Infinity II user manual

Pro 1 IAQ
Pro 1 IAQ true comfort III installation manual

PW maintenance
PW maintenance DT operating instructions