Donaldson Torit PowerCore CPV-1 User manual

Torit® PowerCore®
CPV-1, -2, -3, -4, -6, -8, and -12 After November 2008
Installation and Operation Manual
Installation, Operation, and Service Information
IOM AD3878002 (ENG)
Revision 8
English
Master Language
This manual contains specific precautions related to worker safety. The hazard alert image denotes
safety related instructions and warnings in this manual. DO NOT operate or perform maintenance on this
collector until you have read and understood the instruction and warnings contained within this manual.
CPV-1 CPV-2 through CPV-4
CPV-6 through CPV-12

Donaldson Company, Inc.
The Safety Alert Symbol indicates a hazardous situation which, if not avoided could
result in death or serious injury. Obey all safety messages following this symbol to
avoid possible injury or death.The possible hazards are explained in the associated
text messages.
CAUTION, used with the safety alert symbol, indicates a hazardous situation
which, if not avoided, could result in minor or moderate injury.
NOTICE indicates a potential situation or practice which is not expected to result
in personal injury, but which if not avoided, may result in damage to equipment.
This manual has been supplied to assist with the installation, operation and maintenance for the collector purchased.
Please read the manual before installing, operating, or performing maintenance on the collector as it contains
specific precautions for worker safety. It is the owner’s responsibility to ensure that this manual is available for use by
installers, operators and maintenance personnel that will be working with this collector. This manual is the property of
the owner and should be left with the collector when installation has been completed. DO NOT operate this collector
until you have read and understood the instructions and warnings located in the installation and operation manual.
For additional copies of this manual, contact Donaldson Torit
IMPORTANT NOTES

Magnehelic® and Photohelic® are registered trademarks of Dwyer Instruments, Inc.
Torit PowerCore, CPV-1 to CPV-12
i
Contents
IMPORTANT NOTES ................................................................2
Safety Communication............................................................1
Description................................................................................2
Purpose and Intended Use ....................................................2
Operation...................................................................................3
Inspection on Arrival...............................................................5
Installation Codes and Procedures ......................................5
Installation.................................................................................5
Foundations or Support Framing .......................................6
Collector Location................................................................6
Site Selection .......................................................................6
Hoisting Information ............................................................6
Standard Equipment................................................................6
Typical Installation...................................................................7
Compressed Air Installation...............................................8
Electrical Wiring...................................................................9
Conductive Grounding Installation....................................9
Solid-State Timer Installation...............................................10
Solenoid Connection..........................................................10
Timer and Solenoid Specifications..................................10
Preliminary Start-Up Check .................................................12
Maintenance Information.....................................................13
Operational Checklist ........................................................13
Filter Removal and Installation.........................................13
Filter Removal (CPV-1 Only)..............................................14
Filter Installation (CPV-1 Only) .........................................14
Filter Installation.................................................................15
Compressed Air Components...........................................15
Electrical Connection (CPV-1 Only).................................16
Optional Equipment................................................................16
Fan Blower (Except CPV-1)...............................................16
Magnehelic®Gauge .........................................................17
Photohelic®Gauge ............................................................18
Delta P Control....................................................................21
Delta P Plus Control...........................................................22
Damper Installation (Except CPV-1)................................23
Cold Climate Kit...................................................................24
Troubleshooting......................................................................25
Product Information...............................................................28
Service Notes.........................................................................28
Donaldson Industrial Air Filtration Warranty ....................29

1
Donaldson Company, Inc.
Improper operation of dust collectors and/or dust control systems may contribute to conditions in a work
area or facility which could result in severe personal injury, and product or property damage. All dust
collection equipment should be used only for its intended purpose and should be properly selected and sized
for its intended use.
Process owners have important responsibilities relating to identifying and addressing potential hazards in
their processes. When the potential for handling combustible dust exists within a process the process owner
should include combustion hazards in their risk management activities and should comply with applicable
codes and standards related to combustible dust.
Electrical installation must be performed by a qualified electrician.
This equipment is not designed to support site ducts, piping, or electrical services. All ducts, piping, or
electrical services must be adequately supported to prevent injury and/or property damage.
Site selection must account for wind, seismic zone, and other load conditions.
Equipment may reach peak sound pressure levels above 80 dB (A). Noise levels should be considered when
selecting collector location.
Combustible Dust Hazards
Among other considerations, the current NFPA standards require owners whose processes involve potentially
combustible materials to have a current Dust Hazard Analysis, which can serve as the foundation for their process
hazard mitigation strategy. Mitigation may include but is not limited to:
• Prevention of all ignition sources from entering any dust collection equipment.
• Selection and implementation of fire and explosion mitigation, suppression, and isolation strategies
appropriate for the risks in their process.
• Development and use of work practices to maintain safe operating conditions, and to ensure combustible dust
does not accumulate within their plant or process equipment.
Donaldson designs, manufactures, and sells industrial air filtration products for a wide variety of applications. Some
applications may include processes or materials with inherent fire and explosion hazards. Donaldson is neither an
expert nor a certified consultant in fire, spark, or explosion detection, suppression, or control. Donaldson does not
provide engineering consulting services related to process or dust hazard analyses, or code and standard compliance.
Complying with applicable codes and standards and managing the risks associated with the process or materials
remains the responsibility of the process owner/operator. Donaldson may provide referrals to consultants, suppliers
of equipment or services related to the detection and/or mitigation of sparks, fires and/or explosions, but Donaldson
does not assume responsibility for any such referrals, nor does Donaldson assume any liability for the fitness of a
mitigation strategy or product for a particular installation or application. The process owner’s final selection of dust
collectors and risk mitigation strategies should be based on the outcome of a Dust Hazard / Process Hazard Analysis
performed by the process owner. Although early engagement of a dust collector supplier provides helpful insights on
the availability and features of various products, process owners should consult with a combustible dust expert and/or
a process safety expert before making actual product and mitigation strategy selections.
Donaldson recommends that all industrial air filtration system designs be reviewed and approved by an expert
consultant who is responsible for the integrity of the system design and compliance with applicable codes and
standards. It is the process owner’s responsibility to understand the risks in their process and mitigate those risks in
accordance with all applicable laws, regulations and standards, including those published by the NFPA. Donaldson
also recommends that proper maintenance and housekeeping procedures and work practices be evaluated,
developed, and followed to maintain any industrial air filtration products in safe operating condition.
Many factors beyond the control of Donaldson can affect the use and performance of Donaldson products in a
particular application, including the conditions under which the product is used. Since these factors are uniquely
within the user’s knowledge and control, it is essential the user evaluate the Donaldson products to determine whether
the product is fit for the particular purpose and suitable for the user’s application. All products, product specifications,
and data (airflow, capacity, dimensions, or availability) are subject to change without notice, and may vary by region or
country.
Safety Communication

Torit PowerCore, CPV-1 to CPV-12
2
Description
The Torit PowerCore CPV collector is a continuous duty
dust collector that uses obround style filter packs with
the proprietary axial flow PowerCore filter media. The
system is designed to provide optimum performance for
high efficiency, low operating pressure drop (energy
usage) within a small size collector. The filters can be
pulse-cleaned on- or off-line. Standard sizes range from
1 to 12 obround filter packs.
The Torit PowerCore CPV is not designed as a "stand
alone" collector. Rather, it is designed to be a filtration/
ventilation component of another component, such
as a silo or bin container. The open bottom of the
Torit PowerCore CPV is intended for roof mounting
applications. Some preparation work may be required
before installing the collector. An opening in the silo or
storage bin must have the correct dimensions and be
properly reinforced to support the weight of the Torit
PowerCore CPV. Reference the Rating and Specification
Information.
Purpose and Intended Use
Misuse or modification of
this equipment may result in
personal injury.
Do not misuse or modify.
Discuss the use and application of this equipment with a
Donaldson Torit representative.
In pneumatic conveying systems, Torit PowerCore CPV
can be mounted on the top of silos or storage vessels
to separate the product conveying from displaced air to
prevent product loss and nuisance dust. In mechanical
conveying systems, the dust generated by product
loading, transfer, and discharge can be controlled using
Torit PowerCore CPV on an enclosure. The collected
dust returns directly to the product conveyed making
expensive ductwork systems unnecessary, saving space,
and eliminating dust disposal issues.
Torit PowerCore CPV collectors can be integrated with
process machinery requiring dust control such as fluid
bed reactors, mixers, blenders, mills, and crushers. They
can also be used in bulk materials handling applications
and for bin venting. The CPV model is commonly used in
the grain, chemical, mineral, plastic, wood, composites,
paper, packaging, and textile industries.

3
Donaldson Company, Inc.
Operation
During normal operation, dust-laden air enters the
collector through the cabinet opening at the bottom of
the collector, which is fastened to the silo or storage
container. Airflow is directed upwards through the
collector. The CPV filter packs remove fine particulate
and clean, filtered air passes through the CPV filter pack
to the clean-air plenum and discharges through the
clean-air outlet.
Filter pack cleaning is completed using pulse-jet
technology. Air diaphragm valves provide the pulse
cleaning. An electronic solenoid valve actuates the pulse
cleaning. Filter packs are easily removed without tools
when they need to be changed.

Torit PowerCore, CPV-1 to CPV-12
4
High Pressure Air
Clean Air Plenum
Dust Disposal
Filter Cleaning Operation (1 lter pack collector)Normal Operation (1 lter pack collector)
High Pressure Air
Filter Access Door
Clean Air
Plenum
Dust Disposal
Filter Cleaning Operation (2 to 4 lter pack collectors)Normal Operation (2 to 4 lter pack collectors)
High Pressure Air
Filter Access
Door
Clean Air
Plenum
Dust Disposal
Normal Operation (6 to 12 lter pack collectors) Filter Cleaning Operation (6 to 12 lter pack collectors)
Clean Air
Outlet
Clean Air Outlet
Unpowered
Dirty Air Inlet
Dirty Air Inlet
Clean Air Outlet
Typical Collector Operation

5
Donaldson Company, Inc.
Inspection on Arrival
1. Inspect collector upon delivery.
2. Report any damage to the delivery carrier.
3. Request a written inspection report from the Claims
Inspector to substantiate any damage claim.
4. File claims with the delivery carrier.
5. Compare collector received with description of
product ordered.
6. Report incomplete shipments to the delivery carrier
and your Donaldson Torit representative.
7. Remove crates and shipping straps. Remove loose
components and accessory packages before lifting
collector from truck.
8. Check for hardware that may have loosened during
shipping.
9. Use caution removing temporary covers.
Installation Codes and Procedures
Codes may regulate
recirculating filtered air in your
facility. Consult with the appropriate authorities
having jurisdiction to ensure compliance
with all national and local codes regarding
recirculating filtered air.
Safe and efficient operation of the collector depends on
proper installation.
Authorities with jurisdiction should be consulted
before installing to verify local codes and installation
procedures. In the absence of such codes, install
collector according to the National Electric Code,
NFPA No. 70-latest edition and NFPA 91 (NFPA 654 if
combustible dust is present).
A qualified installation and service agent must complete
installation and service of this equipment.
All shipping materials, including shipping covers, must
be removed from the collector prior to or during collector
installation.
Failure to remove shipping
materials from the collector will
compromise collector performance.
Inspect collector to ensure all hardware is properly
installed and tight prior to operating collector.
Installation
Use proper equipment and
adopt all safety precautions
needed for servicing equipment.
Electrical service or maintenance work must
be performed by a qualified electrician and
comply with all applicable national and local
codes.
Turn power off and lock out all power before
performing service or maintenance work.
Do not install in classified hazardous
atmospheres without an enclosure rated for
the application.
Turn compressed air supply OFF, bleed and
lock out lines before performing service or
maintenance work.
Site selection must account for wind, seismic
zone, and other load conditions when selecting
the location for collectors.
Codes may regulate acceptable locations for
installing dust collectors. Consult with the
appropriate authorities having jurisdiction to
ensure compliance with all national and local
codes regarding dust collector installation.
Collectors must be anchored in a manner
consistent with local code requirements.
Anchors must be sufficient to support dead,
live, seismic, and other anticipated loads.
Consult a qualified engineer for final selection
of anchorage.
Do not set compressed-air
pressure above 100-psig as
component damage can occur.
All compressed air components must be sized
to meet the system requirements of 90-100-psig
supply pressure.
The compressed-air supply must be oil
and moisture free. Contamination in the
compressed air used to clean filters will result
in poor cleaning, cleaning valve failure, or poor
collector performance.
Purge compressed air lines to remove
debris before connecting to the collector’s
compressed air manifold.

Torit PowerCore, CPV-1 to CPV-12
6
Foundations or Support Framing
Prepare the foundation or support framing in the
selected location. Foundation or support framing must
comply with local code requirements and may require
engineering.
Foundation and support framing must be capable of
supporting dead, live, wind, seismic and other applicable
loads. Consult a qualified engineer for final selection of
foundation or support framing.
The collector is suitable for either indoor or outdoor
installations. Reference the Rating and Specification
Information.
Site Selection
This collector can be located on a foundation or
structural framing.
Hoisting Information
Failure to lift the collector
correctly can result in severe
personal injury and/or property damage.
Do not lift collector by the door handle or
air manifold. Follow IOM guidelines and
illustrations.
Use appropriate lifting equipment and adopt
all safety precautions needed for moving and
handling the equipment.
A crane or forklift is recommended for
unloading, assembly, and installation of the
collector.
Location must be clear of all obstructions, such
as utility lines or roof overhang.
Portable collectors may require special installation
accommodations.
Note: Collectors with explosion vents are not
available in portable configurations.
Standard Equipment
Standard installation consists of base collector,
electrical, and compressed air connections.
Collector Location
Donaldson Torit equipment is not
designed to support site installed
ducts, interconnecting piping, or electrical
services. All ducts, piping, or electrical
services must be adequately supported to
prevent severe personal injury and/or property
damage.
When hazardous conditions or materials are
present, consult with local authorities for the
proper location of the collector.
Dust collection equipment may reach peak
sound pressure levels above 80 dB (A). Noise
levels should be considered when selecting
collector location.
Locate the collector to ensure easy access to electrical
and compressed air connections, to simplify solids
collection container handling and routine maintenance,
and to ensure the straightest inlet and outlet ducts.
Provide clearance from heat sources and avoid any
interference with utilities when selecting the location.
Use all lifting points provided.
Use clevis connectors, not hooks, on lifting slings.
Use spreader bars to prevent damage to collector’s
casing.
Check the Specification Control drawing for weight and
dimensions of the collector and components to ensure
adequate crane capacity.
Allow only qualified crane or forklift operators to lift the
equipment.
Refer to applicable OSHA regulations and local codes
when using cranes, forklifts, and other lifting equipment.
Lift collector and accessories separately and assemble
after collector is in place.
Use drift pins to align holes in section flanges during
assembly.

7
Donaldson Company, Inc.
Typical Installation
CPV-1
CPV-6 through CPV-12
Latches and manifold are
not lifting points
Latches and manifold
are not lifting points
CPV-2 through CPV-4
Latches and
manifold are
not lifting
points
angle not to exceed
30° from vertical
Do not lift with
this orientation
30° 0'
Typical Installation
Take center of gravity into consideration when
lifting collector.
Do not install blower before lifting collector (except CPV-1).

Torit PowerCore, CPV-1 to CPV-12
8
1. Remove the plastic pipe plug from the collector’s air
manifold and connect the compressed-air supply
lines. Use thread-sealing tape or pipe sealant on all
compressed-air connections.
2. Install a customer-supplied shut-off valve, bleed-
type regulator with gauge, filter, and automatic
condensate valve in the compressed-air supply line.
3. Set compressed-air supply pressure to a level
suitable for the filters (90-psig). The pulse-cleaning
controls are factory set to clean one or more filters
every 10-seconds during a cleaning cycle.
Compressed Air Installation
Turn compressed air supply OFF,
bleed and lock out lines before
performing service or maintenance work.
A safety exhaust valve should be used to
isolate the compressed air supply. The safety
exhaust valve should completely exhaust
pressure in the collector manifolds when
closed, should be capable of being interlocked
with fire or explosion mitigation equipment
and should include provisions to allow closed-
position locking.
Do not set compressed-air
pressure above 100-psig as
component damage can occur.
All compressed air components must be sized
to meet the system requirements of 90-100-psig
supply pressure.
The compressed-air supply must be oil
and moisture free. Contamination in the
compressed air used to clean filters will result
in poor cleaning, cleaning valve failure, or poor
collector performance.
Purge compressed-air lines to remove
debris before connecting to the collector’s
compressed-air manifold.
air
regulator* bleed-type
air lter*
safety exhaust
valve*
automatic
condensate
valve* compressed-air
supply*
*customer supplied
Compressed Air Installation

9
Donaldson Company, Inc.
All electrical wiring and connections, including electrical
grounding, should be made in accordance with the
National Electric Code (NFPA No. 70-latest edition).
Check local ordinances for additional requirements that
apply.
The appropriate wiring schematic and electrical rating
must be used. See collector’s rating plate for required
voltage.
An electric disconnect switch having adequate amp
capacity shall be installed in accordance with Part IX,
Article 430 of the National Electrical Code (NFPA No.
70-latest edition). Check collector’s rating plate for
voltage and amperage ratings.
Refer to the wiring diagram for the number of wires
required for main power wiring and remote wiring.
Electrical installation, service,
or maintenance work must
be performed by a qualified electrician and
comply with all applicable national and local
codes.
Turn power off and lock out all power before
performing service or maintenance work.
Do not install in classified hazardous
atmospheres without an enclosure rated for
the application.
Electrical Wiring Conductive Grounding Installation
If the collector is equipped with conductive filters and
bonded construction, the collector will need to be
grounded.
1. Follow the instructions provided by the grounding
drawing provided.
2. Ground the collector using the grounding lug at the
rear of the collector.
3. Take resistance readings from the filter media to
ground to ensure conductivity. Records results as
indicated on the drawing.

Torit PowerCore, CPV-1 to CPV-12
10
The solid-state timer is used to control the filter cleaning
system. Available options include 3, 6, 10, 20, or 32-pin
solenoid valve controls.
1. Using the wiring diagram supplied, wire the
starter, solid-state timer and solenoid valves. Use
appropriate wire gauge for rated amp load as
specified by local codes.
2. Plug the program lug into the pin that corresponds
with the number of solenoid valves controlled.
3. With power supply ON, check the operation of the
timer and valves. The valves should open and close
sequentially at factory set 10-second intervals.
4. If a gauge or similar device is used to control the
solid-state timer, the jumper on the pressure switch
portion of the timer should be removed. The solenoid
valves will then pulse only when the differential
pressure reaches the high-pressure setpoint. The
valves will continue to pulse until the low-pressure
setpoint is reached.
The solid-state timer voltage
must match the voltage of the
rating of the timer provided (typically 120VAC).
Do not mount the solid-state timer directly
to the collector as mechanical vibration can
damage the timer.
Electrical installation, service
or maintenance work during
installation must be performed by a qualified
electrician and comply with all applicable
national and local codes.
Turn power off and lock out all power
before performing installation, service, or
maintenance work.
Do not install in classified hazardous
atmospheres without an enclosure rated for
the application.
Solid-State Timer Installation
Solenoid Connection
The collector is equipped with electric solenoid valves
(typically 120V) that controls the pulse-cleaning valves,
which in turn clean the filters.
Solenoid enclosures are mounted near or on the
collector’s compressed-air manifold.
Wire the solenoids to the solid-state timer following the
wiring diagram supplied with the collector. Filter life and
cleaning operation will be affected if not wired correctly.
Timer and Solenoid Specifications
Power to the solid-state timer is supplied to Terminals
L1 and L2, which are intended to operate in parallel
with the fan starter’s low-voltage coil. On fan start-up,
power is supplied to the timer and the preset OFF time is
initiated. At the end of the OFF time, the timer energizes
the corresponding solenoid valve to provide the ON time
cleaning pulse for one diaphragm valve and then steps to
the next until all filters have been cleaned.
To pulse when the fan is OFF, install a toggle switch as
shown on the Solid-State Timer Wiring Diagram. When
the toggle switch is ON, the timer receives power and
energizes the solenoid valves’ pulse-cleaning operation
even though the fan is turned OFF.

11
Donaldson Company, Inc.
Input
105-135V/50 -60Hz/1Ph
Output Solenoids
The load is carried and turned ON and OFF by the 200
watt maximum-load-per-output solid-state switch.
Pulse ON Time
Factory set at 100-milliseconds or 1/10-second.
Do not adjust pulse ON time
unless the proper test equipment
is available. Too much or too little ON time can
cause shortened filter life.
Pulse OFF Time
Factory set at 10-seconds, adjustable from 1 to
180-seconds.
Operating Temperature Range
-20° F to 130° F
Transient Voltage Protection
50 kW transient volts for 20-millisecond duration once
every 20 seconds, 1% duty cycle.
Solenoid Valves
115-V at 19.7 watts each
Compressed-Air
Set compressed-air supply pressure to a level suitable
for the filters (90-psig). The pulse-cleaning controls are
factory set to clean one or more filters every 10-seconds
during a cleaning cycle.
Do not increase supply pressure
above 100-psig as component
damage can occur.
1FU
2FU
3FU
208-230V
60 Hz/3Ph
IL1
IL2
IL3
1M 1OL 1T1
1T2
1T3
230V
115V
H1 H2
H3 H4
X1 X2
stop
start
1M
1M
1TGS
OFF time ON time LAST CHANNEL
LAST CHANNEL SWITCH SETTINGS
4FU, 3A
105 to 135 V
50-60 Hz
COM
L1
L2
L3
L1 L2 2
1
16 8 24 1
1 2 43 5
32
31
30
29
28
27
26
25
24
23
22
00000
00001
00010
00011
00100
00101
00110
00111
01000
01001
01010
21
20
19
18
17
16
15
14
13
12
11
01011
01100
01101
01110
01111
10000
10001
10010
10011
10100
10101
10
9
8
7
6
5
4
3
2
1
10110
10111
11000
11001
11010
11011
11100
11101
111110
111111
O
N
0:OFF 1:ON
Solid-State Timer Typical Wiring Diagram
Disconnect Blower Starter Control Box
fan
motor
solenoid
valves
control
logic
power
supply
timing
logic
pressure
switch
Wiring by factory
Disconnect, fuses, low voltage blower starter, and 1TGS switch are customer-supplied.
Use wiring diagram provided with collector
Wiring by others

Torit PowerCore, CPV-1 to CPV-12
12
Instruct all personnel on safe use and maintenance
procedures.
Electrical work during
installation, service or
maintenance must be performed by a qualified
electrician and comply with all applicable
national and local codes.
Turn power off and lock out all power before
performing service or maintenance work.
Turn compressed air supply OFF, bleed and
lock out lines before performing service or
maintenance work.
Check that the collector is clear and free of all
debris before starting.
Do not install in classified hazardous
atmospheres without an enclosure rated for
the application.
Optional fans over 600 lbs must be
independently supported.
Preliminary Start-Up Check
3. Check that filter retention brackets are properly
tightened to achieve proper filter seal.
1. Check all electrical connections for tightness and
contact.
2. Check for proper rotation on all motors as described
below.
To reverse rotation, single-phase power supply:
Follow manufacturer’s instructions on the motor’s
nameplate.
To reverse rotation, three-phase power supply:
Switch any two leads on the motor junction box.
Do not look into fan outlet to
determine rotation. View the fan
rotation through the back of the motor.
Check that the exhaust plenum is free of tools
or debris before checking blower/fan rotation.
Stand clear of exhaust to avoid personal injury.
Do not interchange a power lead with the
ground wire. Severe personal injury and/or
property damage may result.
4. All access panels should be sealed and secure.
5. Check that fan exhaust damper is set to the fully-
closed position.
6. Check and remove all loose items in or near the inlet
and outlet of the collector.
7. Check that all remote controls and solenoid
enclosures (if applicable) are properly wired and all
service switches are in the OFF position.
8. Check that all optional accessories are installed
properly and secured.
9. Turn power ON at source.
10. Turn the compressed-air supply ON. Adjust pressure
regulator for 90-100 psig.
11. Turn blower fan motor ON.
12. Adjust airflow with the exhaust damper, if equipped.
Excess airflow can shorten filter
life, cause electrical system
failure, and blower motor failure.

13
Donaldson Company, Inc.
Instruct all personnel on safe use and maintenance
procedures.
Use proper equipment and adopt
all safety precautions needed for
servicing equipment.
Use appropriate access equipment and
procedures. Note the standard collector is not
equipped with access platforms unless noted
on the specification drawings.
Electrical service or maintenance work must
be performed by a qualified electrician and
comply with all applicable national and local
codes.
Turn power off and lock out all power before
performing service or maintenance work.
Do not install in classified hazardous
atmospheres without an enclosure rated for
the application.
Turn compressed air supply OFF, bleed and
lock out lines before performing service or
maintenance work.
Do not set compressed-air
pressure above 100-psig as
component damage can occur.
All compressed air components must be sized
to meet the system requirements of 90-100 psig
supply pressure.
The compressed-air supply must be oil
and moisture free. Contamination in the
compressed air used to clean filters will result
in poor cleaning, cleaning valve failure, or poor
collector performance.
Purge compressed air lines to remove
debris before connecting to the collector’s
compressed air manifold.
Maintenance Information
Operational Checklist
1. Monitor the physical condition of the collector and
repair or replace any damaged components.
Routine inspections will minimize downtime and
maintain optimum system performance. This
is particularly important on continuous-duty
applications.
2. Periodically check the compressed air components
and replace compressed air filters.
Drain moisture following the manufacturer’s
instructions. With the compressed air supply ON,
check the cleaning valves, solenoid valves, and
tubing for leaks. Replace as necessary.
3. Monitor pressure drop across filters.
Abnormal changes in pressure drop may indicate a
change in operating conditions and possibly a fault
to be corrected. For example, prolonged lack of
compressed air will cause an excess build-up of dust
on the filters resulting in increased pressure drop.
Cleaning off-line with no airflow usually restores the
filters to normal pressure drop.
4. Monitor exhaust.
5. Monitor dust disposal.
Filter Removal and Installation
Use proper safety and protective
equipment when removing
contaminants and filters.
Dirty filters may be heavier than they appear.
Use care when removing filters to avoid
personal injury and/or property damage.
Turn power off and lock out all power before
performing service or maintenance work.
Turn compressed air supply OFF, bleed and
lock out lines before performing service or
maintenance work.
Do not operate with missing or damaged filters.

Torit PowerCore, CPV-1 to CPV-12
14
Filter Removal (CPV-1 Only)
When inserting the filter pack,
start at the back edge of the
pack first to ensure alignment tabs do not
damage the filter packs.
1. Turn off power to the collector.
2. Loosen wing nuts and slide filter retainer left to
release from hold down.
3. Lift left side of retainer up while moving the right side
towards the back wall.
4. Pull the raised left side of the retainer through upper
left of opening.
5. Remove pack vertically until clear of tubesheet.
Filter Installation (CPV-1 Only)
1. Insert the filter pack, starting with the back edge
first, to ensure alignment tabs do not damage filter
pack.
2. Slide the right side of the retainer through lower right
of opening.
3. Lower the right side of retainer while moving the left
side toward the back wall.
4. Slide filter retainer right and under the hold down lip.
5. Position wing nuts over studs and tighten until stops
are in contact with tubesheet.
Filter Retainer Removal (hinged access panel removed for clarity)
Filter Removal and Installation
(hinged access panel removed for clarity)
1
3
2
Filter Removal and Installation for CPV-1 Collector

15
Donaldson Company, Inc.
Filter Removal (except CPV-1)
1. Turn off power to the collector.
2. Open access door by releasing locking mechanism.
Swing door fully open. Prevent door from closing by
engaging door locking mechanism (except CPV-1).
3. Turn filter pack retention wing nuts counterclockwise
and remove filter pack retainer. Removal of back row
of filter packs first is recommended.
4. Remove filter pack by lifting straight up.
5. Repeat steps 1-4 to remove remaining filter packs.
Filter Installation
1. Clean the surface around the filter opening where
the gasket is seated to ensure a good seal.
2. Insert first filter pack into the tubesheet. Installing
front row of filter packs first is recommended. Install
filter by placing front leading edge of filter into the
opening first.
3. Insert filter pack retainer by engaging both rear
tabs of the retainer into the slots located just behind
the filter pack opening or on opposite side of the
threaded stud. Align the filter pack retention wing
nuts over the posts.
4. Turn filter pack retention wing nuts clockwise until
filter pack gasket is fully seated.
5. Repeat steps 2 through 4 for remaining filter packs.
6. Disengage door locking mechanism (except CPV-1).
Use caution when closing door to avoid personal
injury.
7. Turn access door latch to lock.
8. Reset exhaust damper to required setting if
equipped.
9. Turn electrical power and compressed air supply ON
before starting collector.
Compressed Air Components
1. Periodically check the compressed air components
and replace damaged or worn components as
necessary.
2. Drain moisture following the manufacturer’s
instructions.
3. With the compressed-air supply ON, check the
cleaning valves, solenoid valves, and tubing for
leaks. Repair or replace as necessary.
lter pack retainer
lter pack
Filter Removal and Installation

Torit PowerCore, CPV-1 to CPV-12
16
Electrical Connection (CPV-1 Only)
Electrical work must be
performed by a qualified
electrician and comply with all applicable
national and local codes.
Turn power off and lock out electrical
power sources before performing service or
maintenance work.
Do not install in classified hazardous
atmospheres without an enclosure rated for
the application.
1. Using the wiring diagram supplied, wire the
customer-supplied disconnect switch and fan starter.
Make the connections to the fan motor.
Use appropriate wire gauge for rated amp load as
specified by local codes.
2. Turn the fan motor On then OFF to check for proper
rotation by referencing the rotation arrow located on
the motor's mounting plate.
Do not look into fan outlet to
determine rotation. View the fan
rotation from the back of the motor.
Check that the exhaust plenum is free of tools
or debris before checking blower/fan rotation.
Stand clear of exhaust to avoid personal injury.
To reverse rotation, three-phase power supply: Turn
electrical power OFF at source and switch any two
leads on the output-side of the fan motor starter.
Do not interchange a power lead
with the ground wire. Severe
personal injury or equipment damage may
result.
Fan Blower (Except CPV-1)
Optional Equipment
Failure to lift the fan correctly
can result in severe personal
injury and/or property damage.
Use appropriate lifting equipment and adopt
all safety precautions needed for moving and
handling the fan.
A crane or forklift and qualified operator are
recommended for unloading, assembly, and
installation of the fan.
Location must be clear of all obstructions, such
as utility lines or roof overhang.
To avoid personal injury and/or damage to
equipment, ensure fan blowers are properly
attached to equipment.
The use of a damper or variable
fan drive (VFD) is required to
control airflow through the collector. Lack of a
control damper or VFD will shorten filter life.
The collector can accept direct mounted fan blowers,
Torit Backward Inclined (TBI) or Torit Radial Blade (TRB),
to the top or side of the collector.
For complete information, see the most current version
of the TBI or TRB Fan Installation, Operation and
Maintenance manual.
Fans are dynamically balanced and tested at operating
speeds to check for conformance to vibration limits. All
fans must be adequately supported for smooth operation

17
Donaldson Company, Inc.
Side Mount TBI or TRB Fan Blower
For complete information, see the most current version
of the TBI or TRB Fan Installation, Operation and
Maintenance manuals.
fan blower and
motor assembly
fan blower and
motor assembly
side power adapter
side power adapter
CPV-2, -3, or -4 Side Mount Fan Blower
CPV-6, -8, or -12 Side Mount Fan Blower
Magnehelic®Gauge
The Magnehelic is a differential pressure gauge used to
measure the pressure difference between the clean- and
dirty-air plenums and provides a visual display of filter
change requirements. The high-pressure tap is located in
the dirty-air plenum and the low-pressure tap is located
in the clean-air plenum.
1. Choose a convenient, accessible location on or near
the collector for mounting that provides the best
visual advantage.
If collector is equipped with factory-installed
pressure taps, skip to Step 5.
2. Before drilling, place a piece of non-combustible
cloth over the filter opening in the clean-air plenum
to protect them from drilling chips.
3. Place a piece of wood behind the drill location in the
dirty-air plenum to protect the filters from damage by
the drill bit.
4. Mount the pressure tap hardware on the clean-air
plenum panel and the dirty-air plenum.
5. Plug the pressure ports on the back of the gauge
using two, 1/8-in NPT pipe plugs supplied. Install
two, 1/8-in NPT male adapters supplied with the
gauge into the high- and low-pressure ports on the
side of the gauge.
6. Attach the mounting bracket using three, #6-32 x 1/4-
in screws supplied.
Other manuals for PowerCore CPV-1
1
This manual suits for next models
6
Table of contents
Other Donaldson Torit Industrial Equipment manuals

Donaldson Torit
Donaldson Torit Dalamatic DLMV Series User manual

Donaldson Torit
Donaldson Torit Horizontal Series User manual

Donaldson Torit
Donaldson Torit Dryflo MMA User manual

Donaldson Torit
Donaldson Torit Downflo II User manual

Donaldson Torit
Donaldson Torit LP Series User manual

Donaldson Torit
Donaldson Torit WSO 10 User manual

Donaldson Torit
Donaldson Torit RWB-2000 User manual

Donaldson Torit
Donaldson Torit WSO 20 User manual