Installation and Set Up Wiring the SVI II AP
11
6. Capacitance of the signaling circuit must not exceed 0.26
microfarads or 0.10 microfarads with high series
resistance.
7. Cabling must be shielded to prevent electrical noise that
would interfere with the HART tones, with the shield
grounded.
8. Signal must be properly grounded in only one place.
Note: For details and calculation methods for wiring resistance, and
capacitance and for calculation of cable characteristics please
refer to the HART FSK Physical Layer Specification.
SVI II AP Setups
Typical system setups are shown in Figure 6 on page 13, General
Purpose and Explosion Proof (EEx d) Installation Schematic and Figure
7 on page 13, Intrinsically Safe Installation Schematic. The SVI II AP
positioner can be located in a general-purpose or hazardous area
protected by Explosion Proof (EEx d) methods. Wiring diagrams are
generalized, actual wiring must adhere to Electrical Installation section
of manual and local electrical codes. The use of a Handheld
Communicator or a HART modem is not permitted in the Hazardous
Area protected by Explosion Proof (EEx d) methods. In Figure 7 on
page 13 the SVI II AP positioner is located in a hazardous area that is
protected by Intrinsically Safe wiring practices.
The SVI II AP requires an electrical input from a 4-20 mA current
source. The SVI II AP input signal can carry a HART communication
protocol signal from ValVue 2.4 or greater software and a HART
modem, or from a HART Hand Held Communicator. Since the process
control system, the source of the input signal, is located in a non-
hazardous location, setup requires an intrinsic safety barrier be placed
between the process control system and the SVI II AP. If the SVI II AP
is located in a hazardous area with Intrinsically Safe protection a barrier
is not required for a flameproof installation. Alternatively the system
can be installed as Explosion Proof ⁄flameproof. SVI II AP can
communicate with a remote PC running ValVue software via a modem
connected to the PC's serial or USB port. The PC, which is not
intrinsically safe, must be connected to the circuit on the safe area side
of the intrinsic safety barrier if the valve is located in a hazardous area.
The SVI II AP can be operated, calibrated, configured, and interrogated
either by using local pushbutton and display, or by using a PC running
ValVue 2.4 software, HART Handheld Communicator, or any registered
HART Host that supports DDs. The HART Handheld Communicator is
approved for Intrinsically Safe use in accordance with FM and ATEX
standards. Read and observe all HHC labelling. The SVI II AP is
polarity sensitive so the positive lead must be connected to the positive
(+) terminal and the negative lead to the negative (-) terminal. Reversal
of input will not cause damage but the unit will not function.