DuraVent DURAPLUS CANADA 2 User manual

1
PI DPC2 REV.0 08/2020
DURAPLUS CANADA 2 DPC2
Factory-built 650°C
Chimney 6” & 7” dia.
INSTALLATION
AND
OPERATION
INSTRUCTIONS
These instructions must be followed in their entirety. Failure to do so
may result in hazardous installation. Read these instructions and keep
them for future reference.
Standard: ULC S629-M87
CONTENTS
WARNING…………………………………………2
KEEP YOUR CHIMNEY CLEAN, SIZING CHART………3
GENERAL INSTALLATION NOTES………………….4-5
INTERIOR STRAIGHT INSTALLATION .……….…….6
EXTERIOR INSTALLATION ………………………7-9
REPLACEMENT PARTS .………………………10-11
WARRANTY .……………………….………….…13
WARNING
A MAJOR CAUSE OF CHIMNEY-RELATED FIRES IS FAILURE TO
MAINTAIN REQUIRED CLEARANCES (AIR SPACES) TO COM-
BUSTIBLE MATERIALS. IT IS OF UTMOST IMPORTANCE THAT
THIS CHIMNEY BE INSTALLED ONLY IN
ACCORDANCE WITH THESE INSTRUCTIONS.
2125 Monterey St. • Laval, QC, Canada • H7L 3T6
1-833-DuraVent; www.DuraVentRetail.com

2
WARNING
When wood is burned slowly, it produces tar and
other organic vapors, which when combined with
expelled moisture form creosote. The creosote
vapors condense in the relatively cool chimney ue
of a slow-burning re. As a result, creosote residue
accumulates on the ue lining. When ignited this
creosote makes an extremely hot re. ...A creosote
deposit just 1/8’’ (3 mm) thick is enough to cause
a chimney re.
COAL:
Some coals contain large quantities of sulfur (up to
7%). When coal is burned, sulfur and coal ashes
are deposited in the chimney ue. This deposit
combines with moisture to form a highly corro-
sive acid (sulphuric acid). In order to protect your
chimney, we recommend that you:
1. Burn only low sulfur coals (less than 1% sul-
fur).
2. Have your chimney cleaned within 48 hours
of shutting down your stove at the end of the
heating season. Be certain that all the soot is
removed. Wipe the chimney ue using a strong
solution of baking soda and water. This can
be done by wrapping a rag around a chimney
cleaning brush, dipping it into the baking
soda-water solution then passing it through the
chimney three of four times.
CREOSOTE FORMATION AND NEED FOR REMOVAL
RECOMMENDATIONS
Clearance
The clearances stated in this guide are minimum re-
quirements: if more space is available, use it. Min-
imum clearances mean leaving unobstructed air
space. Do not ll these spaces with any material
whatsoever, especially not insulating material.
Inspection
Contact local building or re ocials about restric-
tions, installation inspections and permits that may
be required in your area.
Replacement Parts
If a component of your chimney system is damaged
it must be replaced by an identical one from Du-
raVent.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
WOOD AND COAL STOVES
We recommend:
1. Choose a stove that bears the label of a test-
ing laboratory (such as ULC, CSA, WH, UL, or
ICBO).
2. Choose the right size stove. Do not buy one
larger than you need.
3. Connect only one appliance to a chimney.
4. Never overre your stove. If any part of the
stove or stove pipe is glowing red, then you are
overring. Immediately close the stove’s damp-
ers until the system cools. The high temperature
caused by overring can permanently damage
the stove and stove pipe and may overheat
nearby combustible walls and furniture.
5. Install the stove and stove pipe as described in
the installation instructions accompanying the
stove. Be certain to maintain the required clear-
ances to combustible construction.
6. Keep your ue gases between 150°C and
260°C. This will maximize eciency while min-
imizing condensation and creosote formation.
Do not ll your stove with wood and allow it to
smolder for 8 to 10 hours. This condition pro-
duces large amounts of creosote in the chimney.
7. Do not burn sea driftwood or treated wood.
These combustibles are highly corrosive to all
types of stainless steel.

3
CHIMNEY OPERATION AND MAINTENANCE
KEEP YOUR CHIMNEY CLEAN SIZING CHART
Wood stoves can quickly create large deposits of
creosote in the chimney. Some wood stoves can
create enough creosote in two weeks to cause a
chimney re. When using a wood stove, we recom-
mend that you:
1. Initially, inspect the chimney system weekly. You
will learn how often it will be necessary to clean
your chimney.
2. The chimney should be inspected at least once
every 2 months during the heating season to de-
termine if a creosote or soot build-up has occurred.
If creosote or soot has accumulated, it should be
removed to reduce the risk of chimney re.
3. Have your chimney cleaned by a qualied chimney
sweep. If you want to clean your chimney yourself:
clean your chimney using plastic, wood, or stainless
steel brushes. Do not use a brush that will scratch
the stainless steel interior of your chimney.
4. Do not expect chemical chimney cleaners to keep
your chimney clean. Their use does not negate the
necessity of periodically inspecting and cleaning
your chimney.
CHIMNEY-SIZE 6” 7”
OUTSIDE-DIAMETER 10” 11”
FRAMING-DIMENSION-REQUIRED
Ceiling Support (Interior Kit) 14-3/8” 14-3/8”
Wall Thimble (Exterior Kit) 14” 15”
MAX. LENGTH HEIGHT SUPPORTED **
Finish Support (Interior Kit) 30’ 28’
Wall Support (Exterior Kit) 24’ 22’
Table 1
HOLE SIZE
DOWN
B
ROOF SLOPE
INCHES
SIDES OF HOLE
MUST
BE VERTICAL
12 IN
X
ACROSS
SLOPE
A
Figure 1
ROOF OPENING CHART
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Table 2 - Refer to Figure 1
KEEP YOUR CHIMNEY CLEAN
CHIMNEY-OPERATION AND MAINTENANCE.
Wood stoves can quickly create large deposits of creosote in
the chimney. Some wood stoves can create enough creosote
in two weeks to cause a chimney fire. When using a wood
stove, we recommend that you:
1. Initially inspect the chimney system weekly. From this
you will learn how often it will be necessary to clean your
chimney.
2. The chimney should be inspected at least once every 2
months during the heating season to determine if a
creosote or soot build-up has occurred: if creosote or
soot has accumulated, it should be removed to reduce
the risk of chimney fire.
3. Have your chimney cleaned by a qualified chimney
sweep. If you want to clean your chimney yourself: clean
your chimney using plastic, wood or stainless steel
brushes. Do not use a brush that will scratch the
stainless steel interior of your chimney.
4. Do not expect chemical chimney cleaners to keep your
chimney clean. Their use does not negate the necessity
of periodically inspecting and cleaning your chimney.
CHIMNEY FIRES
If you are having a chimney fire, follow these steps:
1. Close all heater doors and combustion air controls. For
fireplaces, block the fireplace opening with a non-
combustible material (such as an asbestos or steel
sheet).
2. Alert your family of the possible danger.
3. If you require assistance, alert your fire department.
4. If possible, use a dry chemical fire extinguisher, baking
soda or sand to control the fire. Do not use water as it
may cause a dangerous steam explosion.
5. Watch for smouldering or fire on combustibles next to the
stove, stove pipe and chimney. Check outside to ensure
that sparks and hot embers coming out of the chimney
are not igniting the roof.
6. Do not use the stove again until your chimney and stove
pipe have been inspected by a qualified chimney sweep
or fire department inspector.
The S-2100 + chimney has been designed to withstand
the intense heat of a chimney fire. Nevertheless
chimney fires are dangerous and should be prevented.
*When installed on a concrete floor.
** NOTE: if greater height is required, use additional roof
supports or adjustable wall supports at intervals not
exceeding 20'.
12"
HOLE SIZE
DOWN
B
SIDES OF HOLE
MUST BE VERTICAL
ROOF SLOPE
INCHES
ACROSS
SLOPE
A
X
CHIMNEY SIZE 6" 7"
8"
ROOF SLOPE ROOF HOLE SIZE
(X/12) A B
A
A B
A B
0 14"14"15"15"
16 16
2/12 14"14 1/4"15"15 1/4"
16 16 1/4
4/12 14"14 7/8"15"15 7/8"
16 16 7/8
6/12 14"15 3/4"15"16 3/4"
16 17 7/8
8/12 14"16 7/8"15"18 1/8"
16 19 1/4
10/12 14"18 1/4"15"19 9/16"
16 28 7/8
12/12 14"19 7/8"15"21 1/4"
16 22 5/8
LOADBEARING CHART
BEFORE HIRING A CHIMNEY SWEEP
1. Does the company or individual have adequate
liability insurance in case of damage?
2. How long has the company been in business?
3. Does the company offer current references?
4. Is the company involved in any unresolved disputes?
ROOF OPENING CHART
ROOF HOLE SIZE

4
INSTALLATION NOTES
1. The chimney is intended for use with solid, liquid,
and gaseous fuel burning appliances.
Allowable ue gas temperature:
Maximum continuous 650°C (1200° F)
Brief forced ring 760°C (1400°F)
Tested to 1150°C (2100°F) - 30 minutes
2. The maximum height of chimney supported by the
various DuraVent supports are outlined on page
3.
3. The supports described in this booklet should only
be used with 6” or 7” factory built chimneys.
4. Size the chimney in accordance with the appliance
manufacturer’s instructions.
5. A chimney servicing a replace or an incinerator
shall not serve any other appliance.
6. The chimney shall extend at least 3 ft above its
point of contact with the roof and at least 2 ft higher
than any wall, roof or adjacent building within 10
ft of it.
7. The maximum height of an unguided chimney
above the roof is 5 ft. If the chimney extends more
than 5 ft. above the roof, a Roof Brace (XRSU)
must be used.
8. The clearance between single wall pipe and un-
protected combustible material must not be less
than 18” (see National Building Code) except: The
distance between the vertical stove pipe and the
ceiling may be less than 18” and will be established
by the nish support.
9. Portions of the chimney which may extend through
accessible spaces shall be enclosed in all cases
to avoid personal contact with the chimney and
damage to the chimney. Except for installation in
single and two-story family dwellings, the enclo-
sure must have a re resistance rating equal to or
greater than that of the oor or roof assemblies
through which they pass.
10. Do not ll the 2” space around the chimney with
insulation or any other material. Insulation placed
in this area could cause adjacent combustibles to
overheat.
11. Self tapping screws are not required, but may
be used to reinforce the connection and avoid
accidental unlocking of chimney lengths. Use
only 1/2” self-tapping screws. Do not penetrate
WARNING
The clearance between the chimney and combustible
material must not be less than 2". Do not ll this area
with insulation.
GENERAL INSTALLATION NOTES
1
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
the inner wall of the chimney.
12. If needed, when penetrating the building
envelope the gap between the outer layer of
chimney and any restop or wall thimble can
be sealed using high temperature rated (600°F)
silicone caulking.
13. The safe operation of a factory-built chimney
assembly is based on the use of parts supplied by
the manufacturer. The performance of the assembly
may be aected if the combination of these parts
is not used in actual building construction.
14. All interior portions of the chimney must be ac-
cessible for inspection and cleaning.

5
CEILING
SUPPORT **
2 ft
MIN.
10 ft 3 ft
MIN.
ATTIC
INSULATION
SHIELD
2" MIN.
* 18"
MINIMUM
* CLEARANCE CAN BE REDUCED IF A LISTED CHIMNEY
CONNECTOR IS USED.
** CLEARANCES FOR THE 7’’ CHIMNEY SUPPORT WILL BE
LESS THEN 2’’.
Figure 2
GENERAL INSTALLATION NOTES (CONT’D)
1
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
7.5" MIN
RAIN CAP
COLLAR
To remove cap, unscrew the collar screw to
untighten the collar.
Pull on the cap to remove it from the chimney.
To put the cap back in place, slide it over the
chimney and then tighten the collar using the col-
lar screw.
CAP REMOVAL FOR MAINTENANCE
Figure 3

6
Step 1: Locate the chimney in a convenient place as
near as possible to the appliance outlet.
Step 2: Cut and frame the openings in the ceiling and
roof where the chimney will pass.
NOTE: It is important to follow the framing dimensions
for the oor openings prescribed in this manual.
FRAMING DIMENSION
CHIMNEY
SIZE CEILING SUPPORT ROOF
OPENING
6" 14-3/8’’ x 14-3/8’’ 14’’ x 14’’
7" 14-3/8’’ x 14-3/8’’ 15’’ x 15’’
Step 3: From below push the support into the framed
opening. Attach the support to the framed box
using (12) - 3” spiral nails or #8 x 1 1/2” wood
screws (see Figure 5).
Step 4: Put this rst chimney length in the support.
Turn in clockwise to lock it in place.
NOTE: Make sure arrow on pipe label is pointing
upward.
Step 5: In the Attic, install an Attic Insulation Shield
and Collar from above. (see Figure 6).
Step 6: Stack the next chimney length on the rst
length. Be sure that the male and female
threads are not in line when putting the lengths
together. Turn the chimney clockwise to lock it
in place. You may add a 1/2” stainless steel self
tapping screw to prevent accidental unlocking.
Continue until the required chimney height is
reached.
Step 7: ROOF FLASHING INSTALLATION
Put the roof ashing in place. Seal the joint
Table 3
SILICONE
CAULKING
INTERIOR STRAIGHT INSTALLATION
2
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
between the roof and the ashing with
roong compound. For sloping roofs, place
the ashing under the upper shingles and on
top of the lower shingles. Nail the ashing
to the roof. Place the storm collar around
the chimney and slide down on top of the
ashing. Tighten it with the bolt supplied and
make sure the joint is properly caulked (see
Figure 4).
Step 8: Attach the rain cap to the top of the chimney.
(See Figure 3).
Figure 4
CEILING SUPPORT (SFC) NAILS OR SCREWS
Figure 5
1. BLACK STOVE PIPE
2. FINISHING SUPPORT
3. INSULATED LENGTH
4. ATTIC INSULATION
SHIELD
5. ADJUSTABLE ROOF
FLASHING
6. RAIN CAP
Figure 6

7
EXTERIOR INSTALLATION
3
INSTALLATION NOTES
This chimney will provide optimum performance
when installed within the heated space of a build-
ing. The consequences of installing the chimney
outdoors, up the exterior wall of a building could
result in:
-Back-drafting during cold weather when the con-
nected appliance is not operating.
-Weak, unstable draft.
-Increased creosote accumulation.
-Increased potential for condensation of water vapor
in the chimney ue.
-Decreased eciency of the connected appliance.
If you do install an exterior chimney, we recommend
that you enclose it using an insulated enclosure.
1. Maintain 2" clearance to combustible materials.
Do not ll the 2" space around the chimney with
insulation or any other material.
2. A Wall Band (AWBU) must be used to secure the
chimney to the wall. Maximum distance between
wall bands is 8 feet.
3. The minimum length of chimney extending past
the inside wall is 5”.
4. The maximum length of chimney extending past
the inside wall is 24”.
5. The distance between the stove pipe and a parallel
combustible wall or ceiling must not be less than
18". The distance between the horizontal stove
pipe and the unshielded vertical wall through which
it passes must not be less than 7”. (see Figure 11).
6. If an exterior installation is to be enclosed, allow
for access to base of tee to facilitate required
cleaning.
7. The minimum distance between the bottom of
the Tee and any horizontal combustible (including
the ground) is 2”.
Figure 7
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Wall Support
HOLE SIZE
CHIMNEY SIZE COMBUSTIBLE CONCRETE
6" 14’’ x 14’’ 10-1/4’’
7" 15’’ x 15’’ 11-1/4’’
INSTALLATION INSTRUCTIONS
Step 1. Determine where the chimney will pass
through the wall.
• For concrete walls cut a hole slightly larger than
the chimney.
• For combustible walls cut and frame a hole 4”
larger than the chimney, midway between the wall
studs (see Table 4 below for sizing).
Normally wall studs are placed at 16” centers.
With the hole midway between them, the support
will fasten to these studs and thus ensure a strong
attachment to the wall.
Table 4
Figure 8
10
From inside, put the larger wall-radiation shield over the small
radiation shield. Using a level, make sure that the hole for the
chimney to pass through is horizontal. Screw the radiation shield in
place (see Fig. 20).
Note: The cavity surrounding the radiation shield must be filled with
type R-20 insulation (see Fig. 20).
Attach the clean-out cap to the support's flue
extension using the three (3) metal screws
provided. Make sure that the screws have pierced
through the flue extension. The cap is in the box with
the insulated tee. Or if an insulated tee cap is used,
twist lock the tee cap to the tee (adjustable support
(XSME) only).
The minimum length of insulated chimney required to
pass through the wall will be thickness plus 7". The
insulated chimney must extend at least 5" into the room
beyond the finished wall. Insert this chimney length in
the side entry of the insulated tee. Turn it clockwise to
lock it in place. Seal this joint by wrapping it with the
aluminium tape supplied with the tee.
Mount the insulated tee on the support so that the
chimney length which will go through the wall is
perpendicular to the side of the support that will fasten
to the wall.
This step will require 2 persons:
Insert the chimney length of this tee-support assembly
into the hole in the wall. Using a level, ensure the tee is
vertical, then attach the support to the wall using (8) Nº.
10 x 1 - 1/4" wood screws or 4" spiral nails (see Fig.
21).
NOTE: To provide sufficient strength, the nails must
be driven into the wall studs. For concrete walls, the
support should be attached using (8) 1/4" x 2" lag bolts.
Attach the flue extension to the horizontal chimney
length using the three (3) metal screws provided.
If the chimney passes through the roof, cut a hole large
enough to provide 2" clearance between the chimney
and the roof. For flat roof, and for sloping roofs, see
chart on page 3.
Stack a chimney length on top of the tee. Turn it
clockwise to lock it in place.
Stack the next chimney length on the first length.
Continue until the required chimney heightis reached.
To continue, SEE ROOF FLASHING INSTALLATION,
ON page 5. STEP ....
EXTERIOR INSTALLATION (CONT’D)
WALL
STUD
LARGE
WALL
THIMBLE
LEVEL
WALL
STUDS
FRAMED BOX
(SAME WOOD
SIZE AS JOISTS)
WALL FRAMED
OPENING
IN SU LATE D
CHIMNEY
(X L+)
IN SUL AT E D
TE E (X TI
+
)
5" Min.
3
4
5
6
9
8
7
1" SCREWS
WALL STUD
FLUE
EXTENSION (UP)
4 in. nails or No.10 x 1-1/4 in. screws
4 in. nails or No.10 x 1-1/4 in. screws
Figure 21
WALL
RADIATION
SHIELD
(XRSM+)
WALL SUPPORT
(XSM OR XSMA)
AND INSULATED
TEE CAP (TCS)
OR
ADJUSTABLE
WALL SUPPORT
(XSME) AND
INSULATED
TWIST-
LOCK TEE
CAP (XTCI)
ACCESS
DOOR
Figure 18
1. TEE CAP (TCS
+)
2. WALL RADIATION SHIELD
(XRSM+)
3. INSULATED TEE (XTI+)
4. INSULATED LENGTH (XL+)
5. WALL SUPPORT (XSM)
6. FLUE EXTENSION (UP)
7. WALL BAND (XBM+)
8. FIRESTOP (XBF+)
9. ATTIC RADIATION SHIELD
(XRSA2)
10. STORM COLLAR (XFC+)
ROOF FLASHING (XFA+)
11. RAIN CAP (CC+)
4
LEVEL
INSIDE
OUTSIDE
2" NAILS
SMALL
WALL
THIMBLE
INSULATION
8

8
EXTERIOR INSTALLATION (CONT’D)
Step 2. Wood walls: Place the exterior half of the
Wall Thimble in the opening from the outside.
Fasten in place using (4) 2” nails or 1” screws.
This Wall Thimble is adjustable from 7” to 12”.
(see Figure 9). Make sure the insulation pad
is cut to the desired length according to the
wall thickness. Place the interior half of the
Wall Thimble inside the exterior half of the
Wall Thimble.
Using a level make sure that the hole for the
chimney to pass through is horizontal. Screw
the inner thimble in place with the provided
screws. (see Figure 10).
NOTE: The cavity surrounding the radiation shield
must be lled with any insulation (see Figure
10).
3
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Step 3. The minimum length of insulated chimney
required to pass through the wall will be wall
thickness plus 7". The insulated chimney must
extend at least 5" into the room beyond the
nished wall. Insert this chimney length in
the side branch of the insulated tee. Turn it
clockwise to lock it in place. Seal this joint by
wrapping it with the aluminum tape supplied
with the tee.
Step 4: Fasten a chimney length to the top of the Tee.
Step 5: The Wall Support should be installed on the
rst vertical chimney section above the Tee.
Tighten the Universal Band locking the bolt
just enough to hold the Wall Support in place.
Step 6. This step will require 2 people: (see Figure
11).
Insert the chimney length of this tee-support
assembly into the hole in the wall. Using a
level, ensure the tee is vertical, then attach the
support to the wall using (8) Nº. 10 x 1 - 1/4"
wood screws or 4" spiral nails. Tighten the
collar nut and bolt.
NOTE: To provide sucient strength, the nails
must be driven into the wall studs. For concrete
walls, the support should be attached using
(8) 1/4" x 2" lag bolts.
Step 7: Attach the clean-out cap to the Tee.
Step 8. Attach the ue extension to the horizontal
chimney length.
Step 9. Stack a chimney length on top of the length.
Turn it clockwise to lock it in place. Continue
until the required chimney height is reached.
NOTE: At 8’ intervals, attach the chimney to the wall
using a Wall Band (AWBU).
EXTERIOR INTERIOR
Adjustable 7" to 12"
Wall Thimble
Figure 9
INSIDE OUTSIDE
LEVEL INSULATION
EXTERIOR WALL THIMBLE
2" NAILS
WALL STUD
1" SCREWS
INTERIOR WALL THIMBLE
Figure 10

9
EXTERIOR INSTALLATION (CONT’D)
3
Figure 11
Step 10: If the chimney passes through the roof, cut
a hole large enough to provide 2” clearance
between the chimney and the roof.
Step 11: Put the Roof Flashing in place. Seal the
joint between the roof and the ashing with
roong compound.
For sloping roofs, place the ashing under the
upper shingles and on top of the lower singles.
Nail the ashing to the roof using roong nails.
Place the storm collar around the chimney and
slide down on top of the ashing. Tighten it
with the bolt supplied and make sure the joint
is properly caulked.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Step 12: Attach the Rain Cap to the top of the chim-
ney. (see Figure 3).

10
REPLACEMENT PARTS
4
LENGTHS & FITTINGS
ØDPC2-12 LENGTH Ø" X 12"
ØDPC2-24 LENGTH Ø" X 24"
ØDPC2-36 LENGTH Ø" X 36"
ØDPC2-T TEE WITH TEE CAP (TWIST LOCK)
ØDPC2-TCI INSULATED TEE CAP (TWIST LOCK)
SUPPORTS
ØDPC2-CA FLUE EXTENSION
ØDPC2-SFC CEILING SUPPORT W/COUPLER
DPC2-URES WALL SUPPORT
BRACES & FIRESTOPS
ØDPC2-AARS ADJUSTABLE INSULATED ATTIC INSULATION SHIELD
ØDPC2-WTI INSULATED WALL THIMBLE
DPC2-XRSU UNIVERSAL ROOF BRACE
DPC2-AWBU UNIVERSAL WALL BAND

11
4REPLACEMENT PARTS
VENTED FLASHING (STORM COLLAR INCLUDED)
ØDPC2-F7 ADJUSTABLE ROOF FLASHING 1/12 -7/12
ØDPC2-F12 ADJUSTABLE ROOF FLASHING 8/12 -12/12
ØDPC2-SC STORM COLLAR
OTHERS
ØDPC2-VC RAIN CAP
ØDPC2-DVL ASHT DECORATIVE COLLAR, SINGLE-WALL STOVE PIPE
INSTALLATION KITS
ØDPC2-WSK
WALL SUPPORT KIT
(INCLUDES: 1 OF EACH ØDPC2-TCI, ØDPC2-WTI, ØDPC2-T,
ØDPC2-CA, ØDPC2-DVL, DPC2-AWBU, ØDPC2-URES,
ØDPC2-VC)
ØDPC2-IK INTERIOR KIT
(INCLUDES: 1 OF EACH ØDPC2-SFC, ØDPC2-ARS, ØDPC2-VC)
To order a replacement part, please reach out to your nearest dealer
or to 1-833-DuraVent; www.DuraVentRetail.com

12

13
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
DuraVent Limited Lifetime Warranty
DuraVent, Inc. (“DuraVent”) provides this limited lifetime
warranty for all of its products with the exception of
Ventinox® (lifetime), and PolyPro® (ten years). Subject
to the limitations set forth below, DuraVent warrants
that its products will be free from defects in material or
manufacturing, if properly installed, maintained and used.
DuraVent products are fully warranted if installed only by a
professional installer. This Warranty is transferable from the
original homeowner to the buyer of the home. This warranty
does not cover normal wear and tear, smoke damage or
damage caused by chimney res, acts of God, or any product
that was: (1) purchased other than from an authorized
DuraVent dealer, retailer or distributor; (2) modied or
altered; (3) improperly serviced, inspected or cleaned; or
(4) subject to negligence or any use not in accordance with
the installation instructions included with the product
as determined by DuraVent. Installation instructions are
available online at www.duravent.com under Support/
Literature and through our Customer Service Department
800-835-4429 or customerservice@duravent.com. This
limited lifetime warranty applies only to parts manufactured
by DuraVent.
DuraVent provides the following warranties for its products:
One Hundred Percent (100%) MSRP 15 years from the date of
purchase, and Fifty Percent (50%) thereafter, except for the
following limitations on: all Termination Caps and DuraBlack®
are warranted at One Hundred Percent (100%) for ve years.
All warranty obligations of DuraVent shall be limited to repair
or replacement of the defective product pursuant to the
terms and conditions applicable to each product line. These
remedies shall constitute DuraVent’s sole obligation and sole
remedy under this warranty. This warranty provides no cash
surrender value. The terms and conditions of this warranty
may not be modied, altered or waived by any action,
inaction or representation, whether oral or in writing, except
upon the express, written authority of an executive ocer of
DuraVent.
Corn, bio-fuels, driftwood or other wood containing salt,
preservative-treated lumber, plastic and household trash or
garbage, or wood pellets containing such materials must not
be burned in the appliance or replace. In case of a chimney
re, the chimney must be inspected and approved by a
certied Chimney Sweep before reuse. After each annual
inspection, maintenance, and cleaning, the certied Chimney
Sweep must ll out and date the appropriate section of the
warranty card provided with the chimney liner.
LIMITATIONS ON INTERNET SALES: Notwithstanding
any other terms or conditions of this Limited Lifetime
Warranty, DuraVent provides no warranty for the following
specic products if such products are not installed by
a qualied professional installer: DuraTech®, DuraTech®
DTC, DuraPlus HTC®, DuraTech® Premium, DuraChimney®
II, DuraPlus Canada 2, PelletVent Pro®, DirectVent Pro®,
www.duravent.com | 800-835-4429
FasNSeal®, FasNSeal® W2, FasNSeal® Flex, and PolyPro®, and
DuraVent’s relining products including DuraLiner®, DuraFlex®
(SW, Pro, 316, 304), and Ventinox®. For purposes of this
warranty, a trained professional installer is dened as one
of the following: licensed contractors with prior chimney
installation experience, CSIA Certied Chimney Sweeps, NFI
Certied Specialists, or WETT Certied Professionals.
DuraVent must be notied and given the opportunity to
inspect defective product prior to replacement under the
terms of this limited lifetime warranty. All warranty claims
must be submitted with proof of purchase. Labor and
installation costs are not covered under this warranty. To
obtain warranty service contact: DuraVent Warranty Service,
877 Cotting Ct., Vacaville CA 95688, or call 800-835-4429.
WHERE LAWFUL, DURAVENT DISCLAIMS ALL OTHER
WARRANTIES, INCLUDING BUT NOT LIMITED TO IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE. IN NO EVENT WILL DURAVENT BE
LIABLE FOR INCIDENTAL, CONSEQUENTIAL, PUNITIVE OR
SPECIAL DAMAGES OR DIRECT OR INDIRECT LOSS OF ANY
KIND, INCLUDING BUT NOT LIMITED TO PROPERTY DAMAGE
AND PERSONAL INJURY. DURAVENT’S ENTIRE LIABILITY
IS LIMITED TO THE PURCHASE PRICE OF THIS PRODUCT.
SOME STATES DO NOT ALLOW LIMITATIONS ON IMPLIED
WARRANTIES, OR THE EXCLUSION OR LIMITATION OF
INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE
LIMITATIONS AND EXCLUSIONS MAY NOT APPLY TO YOU.
THIS LIMITED WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS,
AND YOU MAY ALSO HAVE OTHER RIGHTS THAT VARY FROM
STATE TO STATE.
For the most up-to-date installation instructions, see
www. duravent.com
REV 05.03.18
Manufactured in Vacaville CA and Albany NY
L209_ 810007492_DV Limited LifetimeWarranty_08-2020

14
Printed in Canada © 2020
WARRANTY
This product has a limited lifetime warranty. Please
read the warranty to be familiar with its coverage.
Retain this manual. File it with your other documents
for future reference.
PRODUCT REFERENCE INFORMATION
Please contact DuraVent for the phone number of
your nearest DuraVent dealer who will answer your
questions or address your concerns.
Normally, all parts should be ordered through your
DuraVent distributor or dealer. Parts will be shipped
at prevailing prices at time of order.
When ordering repair parts, always give the following
information:
1. The model number of the vent system.
2. The part number.
3. The description of the part.
4. The quantity required.
5. The installation date of the chimney system.
If you encounter any problems or have any questions
concerning the installation or application of this sys-
tem, please contact your dealer.
DuraVent
2125 Monterey St. • Laval, QC, Canada • H7L 3T6
1-833-DuraVent
Visit us at www.DuraVentRetail.com
DuraVent reserves the right to make changes at any time, without notice,
in design, materials, specications, prices.
Consult your local distributor for chimney system code information.
2125 Monterey St. • Laval, QC, Canada • H7L 3T6
1-833-DuraVent; www.DuraVentRetail.com
PI DPC2 REV.0 08/2020
This manual suits for next models
1
Table of contents
Other DuraVent Ventilation Hood manuals

DuraVent
DuraVent DuraTech User manual

DuraVent
DuraVent FasNSeal W2 User manual

DuraVent
DuraVent SELKIRK Ultimate StovePipe USP User manual

DuraVent
DuraVent DuraChimney II User manual

DuraVent
DuraVent DuraTech Series User manual

DuraVent
DuraVent DURASTACK PRO DAS1 Series User manual

DuraVent
DuraVent Type B User manual

DuraVent
DuraVent DAS1 User manual