manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. E2S
  6. •
  7. Fire Alarm
  8. •
  9. E2S D2xC2LD3 User manual

E2S D2xC2LD3 User manual

European Safety Systems Ltd.
Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D211-00-671-IS
Issue 3
20-08-22
Sheet 1 of 8
INSTRUCTION MANUAL
D2xC2LD3 Alarm Horn and LED
For use in Hazardous Locations
1) Product Table
2) Warnings
 DO NOT OPEN WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
 DO NOT OPEN WHEN ENERGISED
 POTENTIAL ELECTROSTATIC CHARGING
HAZARD - CLEAN ONLY WITH A DAMP
CLOTH
Avertissement:
 NE PAS OUVRIR UN PRESENCE
D’ATMOSPHERE EXPLOSIVE
 NE PAS OUVRIR ENERGIE
 DANGER POTENTIEL CHARGE
ÉLECTROSTATIQUE - NETTOYER
UNIQUEMENT AVEC UN CHIFFON HUMIDE
3) Rating & Marking Information
3.1. Fire Alarm Ratings
The D2xC2LD3DC024 is certified for use as a public mode
audible and visual alarm device in accordance with UL464
Tenth Edition / CAN/ULC-S525 Fourth Edition and UL1638
Fifth Edition / CAN/ULC-S526 Fourth Edition.
The D2xC2LD3DC024 is approved for use as an Audible and
Visual Appliance for use in Private Mode Fire Alarm System in
accordance with UL464 Tenth Edition / CAN/ULC-S525
Fourth Edition and UL1638 Fifth Edition / CAN/ULC-S526
Fourth Edition.
See fire instructions D211-00-671-IS-SC-UL
3.1. ATEX / IECEx / UKEx certification
Standards
EN IEC 60079-0:2018 / IEC60079-0:2017 (Ed 7):
Explosive Atmospheres - Equipment. General Requirements
EN IEC 60079-7:2015 +A1:2018 / IEC 60079-7:2018 (Ed. 5.1):
Explosive Atmospheres - Equipment Protection by Increased
Safety "e"
EN 60079-31:2014 / IEC 60079-31:2013 (Ed 2):
Explosive Atmospheres - Equipment Dust Ignition Protection by
Enclosure "t"
Ratings
D2xC2LD3: Ex ec IIC T4 Gc Ta -40°C to +50°C
Ex tc IIIC T75°C Dc Ta -40°C to +50°C
Certificate No. DEMKO 14 ATEX 4786493904X
IECEx ULD 14.0004X
UL21UKEX2131X
ATEX Mark, Equipment
Group and Category:
II 3G
II 3D
CE Marking
UKCA Marking
D2XC2LD3
Model Nominal Voltage Nominal Beacon
Current
Nominal Sounder
Current
D2xC2LD3DC024 20-28Vdc 248mA 250mA
For detailed max current ratings of the device please see Section 14.
Table 1: Electrical Ratings
European Safety Systems Ltd.
Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D211-00-671-IS
Issue 3
20-08-22
Sheet 2 of 8
3.2. NEC & CEC Ratings
NEC & CEC Class / Division Ratings for US / Canada
Standards
UL1971 Ed. 3 2018
UL1638 Ed. 5 2017 / CAN/ULC-S526 Ed. 4
UL464 Ed. 10 2017 / CAN/ULC-S525 Ed. 4
CSA C22.2 No. 205-17
UL 121201-2021 Edition 9
CAN/CSA C22.2 No. 213-17 Edition 3
Ratings
D2xC2LD3:
Class I Div 2 ABCD T4 Ta -40°C to +50°C
Class II Div 2 FG T6 Ta -40°C to +50°C
Class III Div 1&2 Ta -40°C to +50°C
The certification approval has validated continuous use up to
38°C and are for transient use up to 50°C ambient.
Installation must be carried out in compliance with the National
Electric Code / Canadian Electric Code
NEC Class / Zone ratings US
Standards
UL 60079-0 (Ed. 7):
Explosive Atmospheres - part 0: Equipment - General
Requirements
UL 60079-7 (Ed. 5):
Explosive Atmospheres - Equipment Protection by Increased
Safety "e"
UL 60079-31 (Ed. 2)
Explosive Atmospheres - Equipment Dust Ignition Protection by
Enclosure "t"
Ratings
D2xC2LD3:
Class I Zone 2 AEx ec IIC Gc T4 Ta -40°C to
+50°C
AEx tc IIIC T75°C Dc Ta -40°C to +50°C
Installation must be carried out in compliance with the National
Electric Code.
CEC Class / Zone ratings Canada
Standards
CAN/CSA C22.2 No. 60079-0 (Ed. 4) 02/2019
Explosive Atmospheres - Part 0: Equipment - General
Requirements
CAN/CSA C22.2 No. 60079-7 (Ed. 2)
Explosive Atmospheres - Equipment Protection by Increased
Safety "e"
CAN/CSA C22.2 No. 60079-31 (Ed. 2)
Explosive Atmospheres - Equipment Dust Ignition Protection by
Enclosure "t"
Rating
D2xC2LD3:
Ex ec IIC Gc X T4 Ta -40°C to +50°C
Ex tc IIIC T75°C Dc X Ta -40°C to +50°C
Installation must be carried out in compliance with the Canadian
Electric Code
4) Zones, Gas / Dust Groups and Temperature
Classification
When connected to an approved system the D2XC2LD3 LED
beacon may be installed in:
Area
Classification
Zone 2
Explosive gas air mixture not likely to occur in
normal operation, and if it does, it will only
exist for a short time.
Zone 22
Explosive dust air mixture not likely to occur in
normal operation, and if it does, it will only
exist for a short time.
Gas Groupings
Group IIA Propane
Group IIB Ethylene
Group IIC Hydrogen and Acetylene
Temperature Classification for Gas Applications
T1 450ºC
T2 300ºC
T3 200ºC
T4 135°C
Dust Groupings
(ATEX / IECEx
/ UKEX
only)
Group IIIA Combustible Flyings
Group IIIB Non-conductive Dust
Group IIIC Conductive Dust
Maximum Surface Temperature for Dust Applications
(ATEX / IECEx
/ UKEX
only)
D2xC2LD3: 75°C
Equipment Category
3G / 3D
Equipment Level Protection
Gc, Dc
Ambient
Temperature Range
-40°C to +50°C
IP Rating
IP6X to EN/IEC60079
-
0
IP66 to EN60529
To maintain the ingress protection rating, the two off cable entries
must be fitted with suitably rated, certified cable entry and/or
blanking devices during installation.
Type Rating
Per UL50E / NEMA250: 4 / 4X / 3R / 13
Installation must be carried out in compliance with the
latest issue of the following standards:
EN60079-14 / IEC60079-14: Explosive atmospheres - Electrical
installations design, selection and erection
EN60079-10-1 / IEC60079-10-1: Explosive atmospheres -
Classification of areas. Explosive gas atmospheres
EN60079-10-2 / IEC60079-10-2: Explosive atmospheres –
Classification of areas. Explosive dust atmospheres
European Safety Systems Ltd.
Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D211-00-671-IS
Issue 3
20-08-22
Sheet 3 of 8
Beacon
Cover
M4 Screws
(4-off)
147,0mm [5,73in.]
116,0mm [4,52in.]
213,3mm [8,32in.]
165,6mm [6,46in.]
9,7mm [0,38in.]
6,7mm [0,26in.]
Ø6,9mm [Ø0,27in.]
310,3mm [12,10in.]
125,0mm [4,88in.]
168,0mm [6,55in.]
Sounder
Cover
M4
Screws
(4
-
off)
5) Special Conditions for Safe Use
Special Condition for safe Use as stated on the Type
Examination Certificate DEMKO 14 ATEX 4786493904X /
CoC/IECEx ULD 14.0004X / UL21UKEX2131X:
When used for a Group III application, the surface of the
enclosure may store electrostatic charge and become a
source of ignition in applications with a low relative humidity
<~30% relative humidity where the surface is relatively free of
surface contamination such as dirt, dust, or oil.
Guidance on protection against the risk of ignition due to
electrostatic discharge can be found in EN TR50404 and IEC
TR60079-32.
End user shall adhere to the manufacturer’s installation and
instruction when performing housekeeping to avoid the
potential for hazardous electrostatic charges during cleaning,
by using a damp cloth.
To maintain the ingress protection rating and mode of
protection, the cable entries must be fitted with suitably rated,
certified cable entry and/or blanking devices during
installation.
The equipment shall only be used in an area of at least
pollution degree 2, as defined in IEC 60664-1.
6) Product Mounting and Access
6.1. Location and Mounting
The location of the combined alarm horn and beacon should
be made with due regard to the area over which the warning
signal must be visible and audible. It should only be fixed to
services that can carry the weight of the unit.
DxC2 Alarm Horn and Strobe to a flat surface via the two 9.7
x 6.7mm, 147mm pitch fixing holes in the mounting feet of the
sounder section and the two 7mm fixing holes in the feet of
the base.
The equipment is not to be mounted with the horn facing
upwards.
Fig. 1 Fixing locations.
6.2. Access to the Enclosure
Warning – High voltage may be
present, risk of electric shock.
DO NOT open when energised,
disconnect power before opening.
Warning – Hot surfaces. External
surfaces and internal components
may be hot after operation, take
care when handling the equipment.
To access the enclosures, loosen the four M4 posi pan head
screws of the beacon and loosen the four M4 posi pan head
screws of the sounder and withdraw the covers.
Fig. 2 Accessing the Enclosures.
To replace covers, check that the ‘O’ ring seals are in place.
Carefully push the covers in place. Insert M4 screws with fibre
washers and tighten to 3Nm torque.
7) Selection of Cable, Cable Glands, Blanking
Elements & Adapters
When selecting the cable size, consideration must be given to
the input current that each unit draws (see Table 1), the number
of units on the line and the length of the cable runs. The cable
size selected must have the necessary capacity to provide the
input current to all of the sounders connected to the line.
When selecting the cable size consideration must be given to
the voltage drop over the length of the cable run to ensure the
min. input voltage at the point of use (voltage range, see section
15)
The voltage drop depends on:
- The total current draw of the devices installed on this
cable run
- The wire size and total length of the cable run,
determining the total resistance of this cable run
- The minimum output voltage supplied by the power
supply
The voltage drop and input voltage at the point of use can be
calculated as follows:
Total Wire resistance =
Wire resistance / 1000ft x length of cable run x 2
(length of cable run needs to be multiplied by two to account for
two wires going to and from the unit)
Total current draw =
Current draw per unit x number of units
Voltage Drop = Total current draw x Total wire resistance
Minimum output of power supply =
Min. voltage at point of use + voltage drop
The entries are available as one of the following options:
2-off M20 x 1.5 thread & 1-off ¾” NPT thread;
European Safety Systems Ltd.
Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D211-00-671-IS
Issue 3
20-08-22
Sheet 4 of 8
-
-
+ +
External
Earth
Internal
Earth
2-off ½” NPT thread & 1-off ¾” NPT thread
If a high IP (Ingress Protection) rating is required then a
suitable sealing washer must be fitted under the cable glands
or blanking plugs.
For use in explosive dust atmospheres, a minimum ingress
protection rating of IP6X must be maintained.
For use in explosive gas atmospheres, a minimum ingress
protection rating of IP54 must be maintained.
NPT plugs should be greased before insertion.
8) Cable Connections
Electrical connections are to be made into the terminal blocks
on the PCBAs located in the enclosures. See section 6 of this
manual for access to the enclosures.
The Sounder and Beacon are supplied connected by default.
In order to power the beacon and sounder separately, the link
wires between the units must be disconnected.
Wires having a cross sectional area between 0.5 mm² to
2.5mm² can be connected to each terminal way. If an input
and output wire is required the 2-off +/- terminals of the
beacon or 3-off +/- terminals of the sounder can be used. If
fitting 2-off wires to one terminal way the sum of the 2-off
wires must be a maximum cross sectional area of 2.5mm².
Strip wires to 8mm. Wires may also be fitted using ferrules.
Terminal screws need to be tightened down with a tightening
torque of 0.56 Nm / 5 Lb-in. When connecting wires to the
terminals great care should be taken to dress the wires so that
when the cover is inserted into the chamber the wires do not
exert excess pressure on the terminal blocks. This is
particularly important when using cables with large cross
sectional areas such as 2.5mm².
9) Wiring
The beacon is powered via factory installed wires connected
to the alarm horn. The wires connecting the alarm horn and
strobe can be removed if the user wishes to power the strobe
separately. For further wiring schematics refer to document
D211-06-651
Fig. 4 Terminals
10) Earthing
The beacon bas has both internal and external earth points,
(please see fig 5). The sounder PCBA also has earth terminals,
(see fig 4).
Internal earthing connections should be made to the internal
earth point on the beacon, (please see fig 5). The earth
conductor should be at least equal in size and rating to the
incoming power conductors. The internal earth bonding wires
connect the covers to the internal earth points in the bases.
External earth connections should be made to the M5 earth
stud, using a ring crimp terminal to secure the earth conductor
to the earth stud. The external earth conductor should be at
least 4mm2 in size. The external earth crimp ring should be
located between the two M5 plain washers provided and
securely locked down with the M5 spring washer and M5 nut.
Fig. 5 Earth locations
11) End Of Line Monitoring
On DxC2 DC units, dc reverse line monitoring can be used if
required. All DC units have a blocking diode fitted in their supply
input lines. An end of line monitoring resistor can be connected
across the +ve and –ve terminals. If an end of line resistor is
used it must have the following values:-
Min. Resistance Min. Power
3.9KΩ 0.5W
1KΩ 2W
The resistor must be connected directly across the +ve and
-ve terminals of the PCBA, as shown in the following diagrams.
Whilst keeping its leads as short as possible, a spacing of at
least 1/16 inch (1.58mm) must be provided through air and over
surfaces between uninsulated live parts.
Fig. 6a End of Line Resistor Forming
European Safety Systems Ltd.
Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D211-00-671-IS
Issue 3
20-08-22
Sheet 5 of 8
Fig. 6b End of Line Resistor Placement - Beacon
Fig. 7a End of Line Resistor Forming
Fig. 7b End of Line Resistor Placement – Sounder
12) Setting
12.1. Volume Control
The alarm horn output level of the DxC2 unit can be set by
adjusting the volume control potentiometer (see Fig 8). For
maximum output, set the potentiometer fully clockwise.
Fig. 8 Location of field controls
12.2. Tone Selection
The DxC2 alarm horns have 64 different tones. The tones are
selected by operation of the tone setting DIP switches (see
Fig. 9 & 10) on the PCB. The alarm horns can also be
switched to sound the second, third and fourth stage alarm
tones. The tone table (Table 1) shows the switch positions for
the 64 tone and which tones are available for the second, third
and fourth stages.
12.3. Flash Rate Setting
The D2xC2LD3 beacons can produce different flash patterns as
shown in Table 1. The flash patterns are selected by operation
of the flash setting DIP switch on the PCB, Fig 10.
Fig. 9:
DIP Switch
Location
1=ON; 0=OFF
Table 1: Switch Positions for Flash Patterns
Fig. 10 Dip Switch
Example shown: 01 = Flashing 1.33Hz
13) Maintenance, Overhaul & Repair
Maintenance, repair and overhaul of the equipment should only
be carried out by suitably qualified personnel in accordance with
the current relevant standards:
IEC/EN60079-19 Explosive atmospheres - Equipment repair,
overhaul and reclamation
IEC/EN60079-17 Explosive atmospheres - Electrical
installations inspection and maintenance
To avoid a possible ELECTROSTACTIC CHARGE the unit must
only be cleaned with a damp cloth.
Units must not be opened while an explosive atmosphere is
present.
If opening the unit during maintenance operations a clean
environment must be maintained and any dust layer removed
prior to opening the unit.
Switch
Setting Mode
00 1Hz (60FPM)
01 1.33Hz (80FPM)
10 1.5Hz (90FPM)
11 2Hz (120FPM)
Volume
Control
Tone Setting
Switches 1-6
(See tone
selection table)
End Of Line Resistor
Warning – high-intensity light source. Avoid
looking directly at the light source for
extended periods of time.
- +
European Safety Systems Ltd.
Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D211-00-671-IS
Issue 3
20-08-22
Sheet 6 of 8
14) Electrical Ratings
14.1 Operating current Consumption
Table 6 – Electrical Ratings
Model Nom.
Voltage
Voltage
Range
Flash Rate Setting Nom. operating
current
#
Max. operating
current
##
Beacon Sounder Beacon Sounder
D2xC2LD3DC024 24Vdc Regulated
(16-33Vdc)*
Flashing 1Hz 153mA
250mA
465mA
250mA
Flashing 1.33Hz 189mA 488mA
Flashing 1.5Hz 203mA 456mA
Flashing 2Hz 248mA 528mA
* For Public Mode or private mode Fire Alarm or General Signaling use
# nominal rms current at nominal voltage
## max. rms current at worst-case voltage in voltage range.
European Safety Systems Ltd.
Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D211-00-671-IS
Issue 3
20-08-22
Sheet 7 of 8
1600Hz
1400Hz 1s
0.5s
15) Tone Table
Tone Selection – To select the required first stage tone set the tone switches 1 to 6 (see Fig 2) to the tone setting shown in the table below. The table also shows
which 2
nd
, 3
rd
and 4
th
stage tones are available for use with the selected first stage tone if m
ore than one tone output stage is required.
Stage 1
Tone No Tone Description Tone Visual Switch Settings
1 2 3 4 5 6
Stage 2
Tone
(S2)
Stage 3
Tone
(S3)
Stage 4
Tone
(S2 + S3)
1
1000Hz PFEER Toxic Gas
0 0 0 0 0 0 3 2 44
2 1200/500Hz @ 1Hz DIN /
PFEER P.T.A.P.
1 0 0 0 0 0 1 3 44
3 1000Hz @ 0.5Hz(1s on, 1s
off) PFEER Gen. Alarm
0 1 0 0 0 0 1 2 44
4 1.4KHz-1.6KHz 1s, 1.6KHz-
1.4KHz 0.5s NF C 48
-
265
1 1 0 0 0 0 44 24 1
5 544Hz(100mS)/440Hz
(400mS) NF S 32
-
001
0 0 1 0 0 0 52 19 1
6 1500/500Hz - (0.5s on , 0.5s
off) x3 + 1s gap AS4428
1 0 1 0 0 0 7 44 1
7 500-1500Hz Sweeping 2 sec
on 1 sec off AS4428
0 1 1 0 0 0 6 44 1
8
500/1200Hz @ 0.26Hz(3.3s
on, 0.5s off) Netherlands -
NEN 2575
1 1 1 0 0 0 44 24 35
9 1000Hz (1s on, 1s off)x7 + (7s
on, 1s off) IMO Code 1a
0 0 0 1 0 0 18 34 1
10 1000Hz (1s on, 1s off)x7 + (7s
on, 1s off) IMO Code 1a
1 0 0 1 0 0 21 34 1
11
420Hz(0.5s on, 0.5s off)x3 +
1s gap ISO 8201 Temporal
Pattern
0 1 0 1 0 0 44 1 8
12
1000Hz(0.5s on, 0.5s off)x3 +
1s gap ISO 8201 Temporal
Pattern
1 1 0 1 0 0 44 1 8
13
422/775Hz - (0.85 on, 0.5
off) x3 + 1s gap NFPA -
Temporal Coded
0 0 1 1 0 0 44 1 8
14 1000/2000Hz @ 1Hz
Singapore 1 0 1 1 0 0 23 3 35
15
300Hz Continuous
0 1 1 1 0 0 44 24 35
16
440Hz Continuous
1 1 1 1 0 0 44 24 35
17
470Hz Continuous
0 0 0 0 1 0 44 24 35
18 500Hz Continuous IMO code
2 (Low)
1 0 0 0 1 0 44 24 35
19
554Hz Continuous
0 1 0 0 1 0 64 24 35
20 660Hz Continuous 1 1 0 0 1 0 44 24 35
21
800Hz IMO code 2 (High)
0 0 1 0 1 0 44 24 35
22
1200Hz Continuous
1 0 1 0 1 0 44 24 35
23
2000Hz Continuous
0 1 1 0 1 0 15 3 35
24
2400Hz Continuous
1 1 1 0 1 0 48 20 35
25 440 @0.83Hz (50
cycles/minute) Intermittent
0 0 0 1 1 0
1 44 8
26 470 @0.9Hz - 1.1s
Intermittent 1 0 0 1 1 0 1 44 8
27 470Hz @5Hz - (5
cycles/second) Intermittent
0 1 0 1 1 0 1 44 8
28 544Hz @ 1.14Hz - 0.875s
Intermittent
1 1 0 1 1 0 44 24 8
29 655Hz @ 0.875Hz
Intermittent
0 0 1 1 1 0 1 44 8
30 660Hz @0.28Hz - 1.8sec on,
1.8sec off Intermittent
1 0 1 1 1 0 44 24 8
31 660Hz @3.34Hz - 150mS on,
150mS off
Intermittent
0 1 1 1 1 0 30 24 8
1000Hz
1000Hz 1s
1s
544Hz
440Hz
0.1s
0.4s
1500Hz
500Hz
0.5s
0.5s 1.5s
0.5s
0.5s
0.5s
1500Hz
500Hz 2s 1s
1200Hz
500Hz 3.3s 0.5s
1s 1s 1s 7s
7s
1s 1s 1s 1s 1s 1s 1s
1000Hz 1s 1s 1s 1s
0.5s
0.5s
0.5s
1.5s
420Hz 0.5s
0.5s
1000Hz 0.5s
0.5s
0.5s
0.5s
0.5s
1.5s
775Hz
422Hz 0.85s 0.5s 0.85s 0.5s 0.85s 1.5s
2000Hz
1000Hz 1s
300Hz
440Hz
470Hz
500Hz
554Hz
660Hz
800Hz
1200Hz
2000Hz
2400Hz
440Hz 0.6s
0.6s
470Hz 0.55s
0.55s
470Hz 0.1s
0.1s
470Hz 0.43s
0.44s
655Hz 0.57s
0.57s
660Hz 1.8s
1.8s
660Hz 0.15s
0.15s
500Hz
1s
1200Hz
European Safety Systems Ltd.
Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D211-00-671-IS
Issue 3
20-08-22
Sheet 8 of 8
32
745Hz @ 1Hz Intermittent
1 1 1 1 1 0 44 24 8
33 800Hz - 0.25sec on, 1 sec off
Intermittent
0 0 0 0 0 1 53 24 8
34 800Hz @ 2Hz IMO code 3.a
(High) Intermittent
1 0 0 0 0 1 56 24 8
35
1000Hz @ 1Hz Intermittent
0 1 0 0 0 1 44 24 8
36
2400Hz @ 1Hz Intermittent
1 1 0 0 0 1 21 24 8
37
2900Hz @ 5Hz Intermittent
0 0 1 0 0 1 53 24 8
38
363/518Hz @ 1Hz Alternating
1 0 1 0 0 1 1 8 19
39
450/500Hz @ 2Hz
Alternating
0 1 1 0 0 1 1 8 19
40
554/440Hz @ 1Hz Alternating
1 1 1 0 0 1 44 24 19
41 554/440Hz @ 0.625Hz
Alternating
0 0 0 1 0 1 1 8 19
42 561/760Hz @0.83Hz (50
cycles/minute) Alternating
1 0 0 1 0 1 1 8 19
43 780/600Hz @ 0.96Hz
Alternating
0 1 0 1 0 1 1 8 19
44 800/1000Hz @ 2Hz
Alternating
1 1 0 1 0 1 5 24 19
45
970/800Hz @ 2Hz Alternating
0 0 1 1 0 1 1 8 19
46 800/1000Hz @ 0.875Hz
Alternating
1 0 1 1 0 1 53 24 19
47 2400/2900Hz @ 2Hz
Alternating
0 1 1 1 0 1 57 24 19
48 500/1200Hz @ 0.3Hz
Sweeping
1 1 1 1 0 1 44 24 12
49 560/1055Hz @ 0.18Hz
Sweeping
0 0 0 0 1 1 44 24 12
50 560/1055Hz @ 3.3Hz
Sweeping
1 0 0 0 1 1 44 24 12
51 600/1250Hz @ 0.125Hz
Sweeping
0 1 0 0 1 1 44 24 12
52 660/1200Hz @ 1Hz
Sweeping
1 1 0 0 1 1 64 24 12
53
800/1000Hz @ 1Hz Sweeping
0 0 1 0 1 1 56 24 12
54
800/1000Hz @ 7Hz Sweeping
1 0 1 0 1 1 57 24 12
55 800/1000Hz @ 50Hz
Sweeping
0 1 1 0 1 1 54 24 12
56 2400/2900Hz @ 7Hz
Sweeping
1 1 1 0 1 1 57 24 12
57 2400/2900Hz @ 1Hz
Sweeping
0 0 0 1 1 1 47 24 12
58 2400/2900Hz @ 50Hz
Sweeping
1 0 0 1 1 1 54 24 12
59 2500/3000Hz @ 2Hz
Sweeping
0 1 0 1 1 1 44 24 12
60 2500/3000Hz @ 7.7Hz
Sweeping
1 1 0 1 1 1 44 24 12
61
800Hz
Motor Siren
0 0 1 1 1 1 44 24 12
62
1200Hz Motor Siren
1 0 1 1 1 1 44 24 12
63
2400Hz Motor Siren
0 1 1 1 1 1 44 24 12
64
Simulated Bell
1 1 1 1 1 1 44 21 12
745Hz 0.5s
0.5s
800Hz 0.25s
1s
800Hz 0.25s
0.25s
1000Hz 0.5s
0.5s
2400Hz 0.5s
0.5s
2900Hz 0.1s
0.1s
1250Hz
600Hz 8s
1450Hz 0.25s
0.69ms
1200Hz
500Hz 3.34s
1055Hz
560Hz 5.47s
1055Hz
560Hz 0.3s
1200Hz
660Hz 1s
1000Hz
800Hz 1s
1000Hz
800Hz 0.14s
1000Hz
800Hz 0.02s
2900Hz
2400Hz 0.14s
2900Hz
2400Hz 1s
2900Hz
2400Hz 0.02s
3000Hz
2500Hz 0.5s
3000Hz
2500Hz 0.13s
800Hz
1.6s
1200Hz
2s
2400Hz
1.7s
363Hz
518Hz
0.5s
0.5s
500Hz
0.25s
0.25s
450Hz
554Hz
0.5s
0.5s
440Hz
554Hz
0.8s
0.8s
440Hz
760Hz
0.6s
0.6s
561Hz
780Hz 0.52s
0.52s
600Hz
1000Hz
0.25s
0.25s
800Hz
970Hz 0.25s
0.25s
800Hz
2900Hz
0.25s
0.25s
2400Hz
1000Hz
0.57s
0.57s
800Hz
__________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880
Document No. D211-00-611-IS-SC-UL Issue: A 26-07-2022 Sheet 1 of 5
FIRE INSTRUCTION MANUAL
D2xC2LD2 Alarm Horn and LED
For use in Hazardous Locations
1) Warnings
 DO NOT PAINT
Avertissement:
 NE PAS PEINTURER
2) Rating & Marking Information
2.1 Public Mode Fire Alarm Ratings
The D2xC2LD2DC024 is certified for use a as public mode audible and visual alarm device in accordance with UL464 & UL1971 /
UL1638.
For use in public-mode fire alarm systems the equipment must be installed without the wire guard or plastic lens cover on the beacon.
The beacon must be set to one of the certified flash patterns of 1Hz, 1.33Hz or 2Hz (for DIP switch settings see section 10).
For light output ratings of the beacon see section 12.
The sounder section produces a sound pressure level above 75dB(A) at 10 feet:
For Fire Alarm applications, the Sounder Volume must be at the highest setting, (see volume control section).
For fire alarm use, the temporal pattern tone No. 12 as per the tone table provided in these instructions must be selected.
This tone produces a minimum sound pressure level of:
CAN/ULC-S525: 100.4dB(A)* at 10 feet.
(*anechoic room)
UL464: 92.2dB(A)† at 10 feet.
(†reverberation room)
Testing of synchronization requirements of UL1971 & UL1638 / CAN/ULC-S526 were conducted by UL using a total of 6 units connected
to the same wire run. Auto-synchronization does not require the use of any external sync modules or protocols. Providing the correct
cable has been selected (see section 6) an unlimited number of units will remain synchronized when powered from the same source.
2.2 Private Mode Fire Alarm Ratings
The D2xC2LD2DC024 is approved for use as Audible and Visual Appliance for use in Fire Alarm Systems – Private Mode.
For private mode fire alarm use the beacons must only be fitted with clear or red plastic lens covers and must be set to one of the
certified flash patterns of 1Hz, 1.33Hz or 2Hz.
For light output ratings see section .
3) Light output for Fire alarm use
In order to meet the requirements for UL 1971, (D2xC2LD2DC024 when used with 1Hz, 1.33Hz or 2Hz Flash rates and without plastic
lens cover and wire guard only), the installation must be carried out to the correct NFPA standards and guidelines.
__________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880
Document No. D211-00-611-IS-SC-UL Issue: A 26-07-2022 Sheet 2 of 5
3.1 Horizontal Light Output Dispersion for wall mounting – public mode
0° 15°
15° 30°
45°
60°
75°
90°
90°
30°
45°
60°
75°
Fig. 1 – Horizontal dispersion angles for wall mounting
Table 1 - Horizontal Light Output Dispersion for Wall Mounting
Viewing Angle % Of Rating Intensity (cd) at
1Hz flash rate
Intensity (cd) at
1.
33
Hz flash rate
Intensity (cd) at
2Hz flash rate
0
⁰
100 38.38 35.87 25.97
5-25
⁰
90 34.54 32.28 23.37
30-45
⁰
75 28.79 26.90 19.48
50
⁰
55 21.11 14.28 14.28
55
⁰
45 17.27 11.69 11.69
60
⁰
40 15.35 10.39 10.39
65
⁰
35 13.43 9.09 9.09
70
⁰
35 13.43 9.09 9.09
75
⁰
30 11.51 7.79 7.79
80
⁰
30 11.51 7.79 7.79
85
⁰
25 9.60 6.49 6.49
90
⁰
25 9.60 6.49 6.49
Compound 45
⁰
to Right 24 9.21 8.61 6.23
Compound 45
⁰
to Left 24 9.21 8.61 6.23
__________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880
Document No. D211-00-611-IS-SC-UL Issue: A 26-07-2022 Sheet 3 of 5
3.2 Vertical Light Output Dispersion for wall mounting – public mode
75°
60°
45°
30°
15°
0°
90°
Fig. 2 – Vertical dispersion angles for wall mounting
Table 2 - Vertical Light Output Dispersion for Wall Mounting
Viewing
Angle
% Of Rating Intensity (cd) at 1Hz
flash rate
Intensity (cd) at
1.
33
Hz flash rate
Intensity (cd) at
2Hz flash rate
0° 100 38.38 35.87 25.97
5-30° 90 34.54 32.28 23.37
35° 65 24.95 23.32 16.88
40° 46 17.65 16.50 11.95
45° 34 13.05 12.20 8.83
50° 27 10.36 9.68 7.01
55° 22 8.44 7.89 5.71
60° 18 6.91 6.46 4.67
65° 16 6.14 5.74 4.16
70° 15 5.76 5.38 3.90
75° 13 4.99 4.66 3.38
80-90° 12 4.61 4.30 3.12
__________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880
Document No. D211-00-611-IS-SC-UL Issue: A 26-07-2022 Sheet 4 of 5
3.3 Vertical Light Output Dispersion for ceiling mounting – public mode
0°
15°
30°
45°
60°
75°
90°
15°
30°
45°
60°
75°
90°
Fig. 3 – Vertical dispersion angles for ceiling mounting
All light output ratings min. values as per UL 1971 / UL1638 / CAN/ULC-S526 at worst-case (min.) input voltage.
3.4 On-axis light output rating – private mode
Table 3 – Vertical Light Output Dispersion for Ceiling Mounting
Viewing Angle % Of Rating Intensity (cd) at
1Hz flash rate
Intensity (cd) at
1.
33
Hz flash rate
Intensity (cd) at
2Hz flash rate
0
⁰
100 38.38 35.87 25.97
5-25
⁰
90 34.54 32.28 23.37
30-45
⁰
75 28.79 26.90 19.48
50
⁰
55 21.11 19.73 14.28
55
⁰
45 17.27 16.14 11.69
60
⁰
40 15.35 14.35 10.39
65
⁰
35 13.43 12.55 9.09
70
⁰
35 13.43 12.55 9.09
75
⁰
30 11.51 10.76 7.79
80
⁰
30 11.51 10.76 7.79
85
⁰
25 9.60 8.97 6.49
90
⁰
25 9.60 8.97 6.49
Table 5 – Vertical Light Output Dispersion for Ceiling Mounting
Model Lens Cover Colour Intensity (cd) at 1Hz flash rate
D2xC2LD2DC024 clear 73.4
red 67.27
__________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880
Document No. D211-00-611-IS-SC-UL Issue: A 26-07-2022 Sheet 5 of 5
4) Electrical Ratings
4.1 Surge current for Fire Alarm system use
Table 4 – Surge Currents
Model Nom. Voltage Voltage Range Flash Rate Setting Init, Peak Surge
Current (A)
Init. RMS Surge
Current (mA)
D2xC2LD2DC024 24Vdc Regulated 24
(16-33Vdc)*
1Hz (60fpm) 2.73 240
1.33Hz (80 fpm) 2.75 214
2Hz (120fpm) 2.33 204
5) Sound Directional Characteristics for Canadian Fire CAN/ULC-S525
Horizontal Axis
Angle OSPL Angle OSPL
Reference (90°) 101.2 dB(A) Reference (90°) 101.2 dB(A)
115° -3 dB(A) 68° -3 dB(A)
129° -6 dB(A) 55° -6 dB(A)
180° 92.4 dB(A) 0° 92.4
Vertical Axis
Angle OSPL Angle OSPL
Reference (90°) 101.5 dB(A) Reference (90°) 101.5 dB(A)
123° -3 dB(A) 65° -3 dB(A)
137° -6 dB(A) 50° -6 dB(A)
180° 91 dB(A) 0° 88.5 dB(A)
ALL DIMENSIONS IN MM
IF IN DOUBT, ASK -
DO NOT SCALE
2S
warning signals
NTS
D2xC2LD3 PUBLIC MODE FIRE
COMBINED BEACON AND SOUNDER WIRING DIAGRAM
D211-06-671
1 1
OF
R.N.POTTS
D.HOWGILL
B. ISARD
17-05-2022
MOD No. REASON - INITIAL - DATEISSUE
1INTRODUCTION
DH 17-05-2022
D2x
-
-
+ve OUT
-ve OUT
+
+
-
-
-
+
+
+
E
E
+ve IN
+ve OUT
-ve IN
-ve OUT
EARTH IN
EARTH OUT
DC D2XC2LD3 UNITS
Line Monitoring
Stage 1: Apply power to Sounder +ve & -ve
Stage 2: Apply power to Sounder +ve & -ve. Connect Stage 2 to -ve
Stage 3: Apply power to Sounder +ve & -ve. Connect Stage 3 to -ve
Stage 4: Apply power to Sounder +ve & -ve. Connect Stage 2 and Stage 3 to -ve
OPTIONAL LINE MONITORING RESISTOR, CUSTOMER SUPPLIED,
REQUIRED MINIMUM VALUES:
R1
24VDC : 1KΩ MIN, 2W MIN OR 3K9Ω MIN, 0.5W MIN
48VDC : 3.9KΩ MIN, 2W MIN OR 15KΩ MIN, 0.5W MIN
S3
S2
STAGE 3
STAGE 2
R1 R1
WIRING LINKING BEACON & SOUNDER
FACTORY FITTED
TO OPERATE SOUNDER AND BEACON
INDEPENDENTLY, REMOVE FACTORY
FITTED WIRES LINKING THE UNITS
17-05-2022
17-05-2022
E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: [email protected] www.e2s.com DC-061_Issue_J (D2x).docx - Page 1 of 2 - QAF_252_Issue_5
EU Declaration of Conformity
Manufacturer: European Safety Systems Ltd.
Impress House, Mansell Road, Acton
London, W3 7QH
United Kingdom
Authorised Representative: E2S Warnsignaltechnik UG
Charlottenstrasse 45-51
72764 Reutlingen
Germany
Equipment Type: D2xS1, D2xC1X05, D2xC1X10
D2xB1X05, D2xB1X10, D2xB1LD2, D2xB1XH1, D2xB1XH2, D2xB1LD3
D2xC2X05, D2xC2X10, D2xC2LD2, D2xC2XH1, D2xC2XH2, D2xC2LD3
D2xJ1
Directive 2014/34/EU: Equipment and Protective Systems for use in Potentially Explosive Atmospheres (ATEX)
Notified Body for EU
type Examination
(Module B)
:
UL International Demko A/S
Notified Body No.: 0539
Borupvang 5A, 2750 Ballerup, Denmark
EU
-
type Examination Certificate
(Module B)
:
DEMKO 14 ATEX
4786493904X
Notified Body for Quality Assurance Notification
/ Conformity to EU
-
type
based on
quality assurance of the production process (Module D):
Sira Certification Service
Notified Body No.: 2813
CSA Group Netherlands B.V, Utrechtseweg 310, 6812 AR, Arnhem, Netherlands
Quality Assurance Notification
(Module D)
:
SIRA 05 ATEX M342
Provisions fulfilled by the equipment:
II 3G Ex
ec
IIC
T6/
T4
/T3
/T2/T1 Gc
II 3D Ex tc IIIC Ex tc IIIC T55/75/80/85/90/95/105/110°C Dc
IP66 Ingress / Dust Protection to EN60079-0 / EN60079-31
Standards applied:
EN IEC 60079
-
0:2018
EN IEC 60079-7:2015 +A1:2018
EN 60079-31:2014
Directive 2014/30/EU: Electromagnetic Compatibility Directive (EMC)
Standards applied:
EN 61000
-
6
-
1:2007
EN 61000-6-2:2005
EN 61000-6-3:2007 / A1:2011 / AC: 2012
EN 61000-6-4:2007 / A1: 2011
Directive 2011/65/EU: Restriction of the use of certain hazardous substances in electrical and electronic equipment (RoHS)
The product and all the components contained within it are in accordance with the restriction of the use of hazardous substances in electrical and electronic
equipment, including amendment by Directive 2015/863/EU.
Regulation (EC) 1907/2006: Registration, Evaluation, Authorisation and Restriction of Chemicals (REACH)
The product and all the components contained within it are free from substances of very high concern.
Other Standards and Regulations
EN 60529:1992+A2:2013 - Degrees of protection provided by enclosures (IP code) – enclosure rated IP66
E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: [email protected] www.e2s.com DC-061_Issue_J (D2x).docx - Page 2 of 2 - QAF_252_Issue_5
Martin Streetz Document No.: DC-061_Issue_J
Quality Assurance Manager Date and Place of Issue: London, 22/08/2022
EU Declaration of Conformity
On behalf of European Safety Systems Ltd., I declare that, on the date the equipment accompanied by this declaration is placed on the market, the equipment
conforms with all technical and regulatory requirements of the above listed directives, regulations and standards.
This Declaration is issued under the sole responsibility of the manufacturer.
E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: [email protected] www.e2s.com DC-102_Issue_A - Page 1 of 2 - QAF_252_Issue_5
UKCA Declaration of Conformity
Manufacturer: European Safety Systems Ltd.
Impress House, Mansell Road, Acton
London, W3 7QH
United Kingdom
Equipment Type: D2xS1, D2xC1X05, D2xC1X10
D2xB1X05, D2xB1X10, D2xB1LD2, D2xB1XH1, D2xB1XH2, D2xB1LD3
D2xC2X05, D2xC2X10, D2xC2LD2, D2xC2XH1, D2xC2XH2, D2xC2LD3
D2xJ1
Directive UKSI 2016:1107 (as amended by UKSI 2019:696) – Schedule 3A, Part 1 : Product or Protective System Intended for use in Potentially Explosive Atmospheres
(UKCA)
Notified Body for
UK
type Examination
(Module B)
:
UL International (UK) Ltd
Notified Body No.: 0843
Unit 1‐3 Horizon Kingsland Business Park, Wade Road,
Basingstoke, Hampshire RG24 8AH UK
UK
‐
type Examination Certificate
(Module B)
:
UL21UKEX2131X
Notified Body for Quality Assurance Notification
/ Conformity to EU
‐
type
based on
quality assurance of the production process (Module D):
Sira Certification Service
Notified Body No.: 0518
Rake Lane, Eccleston, Chester CH4 9JN, UK
Quality Assurance Notification
(Module D)
:
CSAE 22UKQAN0046
Provisions fulfilled by the equipment:
II 3G Ex
ec
IIC
T6/
T4
/T3
/T2/T1 Gc
II 3D Ex tc IIIC Ex tc IIIC T55/75/80/85/90/95/105/110°C Dc
IP66 Ingress / Dust Protection to EN60079‐0 / EN60079‐31
Standards applied:
EN IEC 60079
‐
0:2018
EN IEC 60079‐7:2015 +A1:2018
EN 60079‐31:2014
Directive 2014/30/EU: Electromagnetic Compatibility Directive (EMC)
Standards applied:
EN 61000
‐
6
‐
1:2007
EN 61000‐6‐2:2005
EN 61000‐6‐3:2007 / A1:2011 / AC: 2012
EN 61000‐6‐4:2007 / A1: 2011
Directive 2011/65/EU: Restriction of the use of certain hazardous substances in electrical and electronic equipment (RoHS)
The product and all the components contained within it are in accordance with the restriction of the use of hazardous substances in electrical and electronic
equipment, including amendment by Directive 2015/863/EU.
Regulation (EC) 1907/2006: Registration, Evaluation, Authorisation and Restriction of Chemicals (REACH)
The product and all the components contained within it are free from substances of very high concern.
Other Standards and Regulations
EN 60529:1992+A2:2013 ‐ Degrees of protection provided by enclosures (IP code) – enclosure rated IP66
E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: [email protected] www.e2s.com DC-102_Issue_A - Page 2 of 2 - QAF_252_Issue_5
Martin Streetz Document No.: DC‐102_Issue_A
Quality Assurance Manager Date and Place of Issue: London, 22/08/2022
UKCA Declaration of Conformity
On behalf of European Safety Systems Ltd., I declare that, on the date the equipment accompanied by this declaration is placed on the market, the equipment
conforms with all technical and regulatory requirements of the above listed directives, regulations and standards.
This Declaration is issued under the sole responsibility of the manufacturer.

Other manuals for D2xC2LD3

1

This manual suits for next models

1

Other E2S Fire Alarm manuals

E2S IS-CP4B-PB User manual

E2S

E2S IS-CP4B-PB User manual

E2S BExCP3C-BG User manual

E2S

E2S BExCP3C-BG User manual

E2S STExJ2 User manual

E2S

E2S STExJ2 User manual

E2S GNExCP7-BG-S User manual

E2S

E2S GNExCP7-BG-S User manual

E2S BExTS110D User manual

E2S

E2S BExTS110D User manual

E2S BExCP3D-PB User manual

E2S

E2S BExCP3D-PB User manual

E2S D1xB2XH1 User manual

E2S

E2S D1xB2XH1 User manual

E2S BExTBG05D User manual

E2S

E2S BExTBG05D User manual

E2S BExCP3B-PB User manual

E2S

E2S BExCP3B-PB User manual

E2S BExCP3B-BG User manual

E2S

E2S BExCP3B-BG User manual

E2S GNExCP6B-PB User manual

E2S

E2S GNExCP6B-PB User manual

E2S BExCP3A-PB User manual

E2S

E2S BExCP3A-PB User manual

E2S D2xB1LD3DC024 User manual

E2S

E2S D2xB1LD3DC024 User manual

E2S AlertAlight AL100H User manual

E2S

E2S AlertAlight AL100H User manual

E2S GNExCP7-PB-S User manual

E2S

E2S GNExCP7-PB-S User manual

E2S D2xB1LD3 User manual

E2S

E2S D2xB1LD3 User manual

Popular Fire Alarm manuals by other brands

Fike FCP-300 Installation & operation manual

Fike

Fike FCP-300 Installation & operation manual

Simplex Foundation 2606-9111 Series installation guide

Simplex

Simplex Foundation 2606-9111 Series installation guide

Aritech 2X-F1 Operation manual

Aritech

Aritech 2X-F1 Operation manual

Autronica BS-200 How to operate

Autronica

Autronica BS-200 How to operate

Vigilant MICROVAC owner's manual

Vigilant

Vigilant MICROVAC owner's manual

Hochiki America Corporation FireNET Plus Installation and operation manual

Hochiki America Corporation

Hochiki America Corporation FireNET Plus Installation and operation manual

Mircom QX-mini Installation and operation manual

Mircom

Mircom QX-mini Installation and operation manual

INIM Electronics PREVIDIA MAX Manual for system configuration, commissioning and maintenance

INIM Electronics

INIM Electronics PREVIDIA MAX Manual for system configuration, commissioning and maintenance

Brooks RFP V2 Series Operation & installation manual

Brooks

Brooks RFP V2 Series Operation & installation manual

Incite Fire Sigma-XT Installation and operation manual

Incite Fire

Incite Fire Sigma-XT Installation and operation manual

Gent System 800 Installer manual

Gent

Gent System 800 Installer manual

Siemens FDM365-RP Installation

Siemens

Siemens FDM365-RP Installation

Fire-Lite Alarms MS-4412B manual

Fire-Lite Alarms

Fire-Lite Alarms MS-4412B manual

Bosch FAP-420 Series quick guide

Bosch

Bosch FAP-420 Series quick guide

DSPPA DSP9102 user manual

DSPPA

DSPPA DSP9102 user manual

Gamewell IDENTIFLEX 632 Installation & operation manual

Gamewell

Gamewell IDENTIFLEX 632 Installation & operation manual

Ampac ACP05 installation guide

Ampac

Ampac ACP05 installation guide

Brooks FIRETRACKER FT128 Quick operation guide

Brooks

Brooks FIRETRACKER FT128 Quick operation guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.