E2S GNExCP7-BG-S User manual

INSTRUCTION MANUAL
GNExCP7-BG-S, GNExCP7-BG-D
Call Point
Class I & II Div 2 ; UL38
NEC / CEC / ATEX / IECEx / UKEx Zone 1, 2, 21, 22
_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e-2-s.com Fax: +44 (0)208 740 4200
Document No. D202-00-001-IS Issue 1 25-04-2022 Sheet 1 of 7
GNExCP7-BG
1) Product Table
Unit Type Code Input Voltage
Input Current
GNExCP7-BG-S
GNExCP7-BG-D
250Vac Max 5.0A Max
48Vdc Max 1.0A Max
24Vdc Max 3.33A Max Class Div/Zone
5.0 Max ATEX/IECEx
/
UKEx
Table 1: Elect
r
ical Ratings
2) Warnings
WARNINGS:
USE COVER BOLTS CLASS A4-70
DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT
POTENTIAL ELECTROSTATIC CHARGING HAZARD – SEE INSTRUCTIONS
FOR INDOOR OR OUTDOOR USE
TO REDUCE THE RISK OF IGNITION OF HAZARDOUS ATMOSPHERES, CONDUIT RUNS
MUST HAVE A SEALING FITTING CONNECTED WITHIN 2 INCHES OF ENCLOSURE
AVERTISSEMENT:
UTILISER COUVRIR BOULONS CLASSE A4-70
NE PAS OUVRIR UN PRESENCE D'ATMOSPHERE EXPLOSIVE
DANGER POTENTIEL CHARGE ÉLECTROSTATIQUE - VOIR LES INSTRUCTIONS
POUR USAGE INTÉRIEUR OU EXTÉRIEUR
POUR RÉDUIRE LE RISQUE D'INFLAMMATION DES ATMOSPHÈRES DANGEREUSES, LES CONDUITES DE CONDUIT
DOIVENT AVOIR UN RACCORD D'ÉTANCHÉITÉ RACCORDÉ À MOINS DE 2 POUCES DE ENCLOS

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e-2-s.com Fax: +44 (0)208 740 4200
Document No. D204-00-001-IS Issue 1 25-04-2022 Sheet 2 of 7
3) Marking & Rating Information
The GNExCP7-BG Call Points comply with the following standards
for hazardous locations:
3.1 Class/Division Ratings for US & Canada
All models are approved for use as Fire Alarm System use:
UL 38 8th Edition 10/4/2013 Manual Signaling Boxes for Fire
Alarm Systems
ULC-S528 3rd Edition 2014-10 Manual Stations For Fire
Alarm Systems, Including Accessories
For Indoor and Outdoor Use
Pour usage Interier INTÉRIEUR
Ambient Temperature Range:
-55°C to +70°C
Standards
UL 60079-0:2017 (Ed 6): Explosive Atmospheres - Part 0: Equipment -
General requirements
UL 60079-1:2015 (Ed7): Explosive Atmospheres - Part 1: Equipment
protection by flameproof enclosures “d”
UL 60079-31:2012 (Ed 2): Explosive Atmospheres - Part 31: Equipment
dust ignition protection by enclosure "t"
CSA C22.2 NO. 60079-0:2015 (Ed 3) Explosive Atmospheres – Part 0:
Equipment – General requirements
CSA C22.2 NO. 60079-1:2016 (Ed 3): Explosive Atmospheres – Part 1:
Equipment protection by flameproof enclosures “d”
CSA C22.2 NO. 60079-31:2015 (Ed 2): Explosive Atmospheres – Part 31:
Equipment dust ignition protection by enclosure “t”
Class Division Ratings for US (NEC) & Canada (CEC)
Model No: Rating
GNExCP7-BG-S
Class I Div 2 Group ABCD T6 Ta -55°C to
+70°C
Class II Div 2 Group FG T4 Ta -55°C to
+70°C
Class III Div 1 & 2 Ta -55°C to +70°C
GNExCP7-BG-D
Class I Div 2 Group ABCD T5 Ta -55°C to
+70°C
Class I Div 2 Group ABCD T6 Ta -55°C to
+65°C
Class II Div 2 Group FG T4 Ta -55°C to
+70°C
Class III Div 1 & 2 Ta -55°C to +70°C
Class Zone Ratings for US (NEC)
Model No: Rating
GNExCP7-BG-S
Class I Zone 1 AEx db IIC T6 Gb Ta -55°C
to +70°C
Zone 21 AEx tb IIIC T110°C Db Ta -55°C to
+70°C
GNExCP7-BG-D Class I Zone 1 AEx db IIC T5 Gb Ta -55°C
to +70°C
Class I Zone 1 AEx db IIC T6 Gb Ta -55°C
to +65°C
Zone 21 AEx tb IIIC T135°C Db Ta -55°C to
+70°C
Class Zone Ratings for Canada (CEC)
Model No: Rating
GNExCP7-BG-S
Ex db IIC T6 Gb X Ta -55°C to +70°C
Ex tb IIIC T110°C Db Ta -55°C to +70°C
GNExCP7-BG-D Ex db IIC T5 Gb Ta -55°C to +70°C
Ex db IIC T6 Gb Ta -55°C to +65°C
Ex tb IIIC T135°C Db Ta -55°C to +70°C
Installation must be carried out in compliance with the National Electric
Code / Canadian Electric Code
3.2 ATEX / IECEx & UKEx Ratings
Standards
EN60079-0:2018/IEC60079-0:2017 (ed.7): Explosive Atmospheres -
Equipment General Requirements.
EN60079-1:2014/IEC60079-1:2014 (ed.7): Explosive Atmospheres -
Equipment Protection by Flameproof Enclosures “d”.
EN60079-31:2014/IEC60079-31:2013 (ed.2): Explosive Atmospheres -
Equipment Dust Ignition Protection by enclosure “t”.
Model No: Rating
GNExCP7-BG-S
Ex db IIC T6 Gb Ta –55°C to +70°C
Ex tb IIIC T80°C Db Ta
–
55°C to +70°C
GNExCP7-BG-D
Ex db IIC T5 Gb Ta –55°C to +70°C
Ex db IIC T6 Gb Ta –55°C to +65°C
Ex tb IIIC T85°C Db Ta
–
55°C to +70°C
See Product table for electrical ratings of each unit model
Certificate No. DEMKO 19 ATEX 2101X
IECEx ULD 19.0097X
UKEx UL UL21UKEX2134X
Epsilon x
Equipment Group
and Category:
II 2G
II 2D
CE Marking and
Notified Body No.
2813
UKCA Marking and
Notified Body No.
0518
4) Zones, Gas Group, Category and
Temperature Classification
The units can be installed in locations with the following conditions:
Area Classification Gas
Zone 1 Explosive gas air mixture likely to occur in normal
operation.
Zone 2 Explosive gas air mixture not likely to occur in normal
operation, and if it does, it will only exist for a short time.
Gas Groupings
Group IIA Propane
Group IIB Ethylene
Group IIC Hydrogen and Acetylene
Temperature Classification for Gas Applications
T1 450oC
T2 300oC

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e-2-s.com Fax: +44 (0)208 740 4200
Document No. D202-00-001-IS Issue 1 25-04-2022 Sheet 3 of 7
T3 200oC
T4 135oC
T5 100ºC
T6 85ºC (GNExCP7-BG-D up to 65°C ambient)
Area Classification Dust
Zone 21 Explosive dust air mixture likely to occur in normal
operation.
Zone 22 Explosive dust air mixture not likely to occur in normal
operation, and if it does, it will only exist for a short time.
Dust Groupings
Group IIIA Combustible Dusts
Group IIIB Non-Conductive Dusts
Group IIIC Conductive Dusts
E
q
ui
p
ment Cate
g
or
y
2G, 2D
E
q
ui
p
ment Protection Level
Gb, Gc, Db, Dc
Maximum Surface Tem
p
erature for Dust A
pp
lications
80°C (GNExCP7-BG-S) ATEX/IECEx/UKEx
85°C (GNExCP7-BG-D) ATEX/IECEx/UKEx
110°C (GNExCP7-BG-S) Class Zone
135°C
(
GNExCP7-BG-D
)
Class Zone
Ambient Temperature Range
-55°C to +70°C (-67°F to +158°F)
IP Rating
IP66 to EN60529
4 / 4X / 3R / 13 to UL50E / NEMA250
Installation must be carried out in compliance with the latest
issue of the following standards:
EN60079-14 / IEC60079-14: Explosive atmospheres - Electrical
installations design, selection and erection
EN60079-10-1 / IEC60079-10-1: Explosive atmospheres -
Classification of areas. Explosive gas atmospheres
EN60079-10-2 / IEC60079-10-2: Explosive atmospheres -
Classification of areas. Explosive dust atmospheres
5) Specific Conditions for Safe Use
The stainless steel lift flap is not earthed and may generate
an ignition-capable level of electrostatic charges. It has a max
capacitance of 6.33pF according to CSA C22.2 NO. 60079-0
/ UL 60079-0:2017, clause 7.5 or EN/IEC60079-0, clause 7.5.
Equipment is permitted to be wall mounted only in vertical
position. The enclosure base is permitted in two mounting
positions, with the double entry lowermost or uppermost.
Fig 1 Wall mounting
Flame Path Positions
Flame Path on Base shown
hatched
Flame path through shaft bore
Flame Path on Cover Shown
Hatched
No repair to the Flamepaths is permitted
7) Location and Mounting
The location of the call point should enable ease of access
for operation and testing. The unit should be mounted using
the 4 off fixing holes which will accept up to M5 sized fixings.
They should only be fixed to services that can carry the
weight of the unit.
To gain access to the mounting holes in the base the front
cover must be removed. See Section 8.
Fig. 1 View of base unit showing fixing centres (in mm).
8) Access to the Flameproof Enclosure
To access the Ex d chamber, remove the four off M6 x 60
hexagon socket head screws and withdraw the flameproof
cover taking extreme care not to damage the flameproof
faces in the process. M6 cover screws are Class A4-70
stainless steel and only screws of this category can be used
for the enclosure.
Warning – Hot surfaces. External surfaces
and internal components may be hot after
operation, take care when handling the
equipment.
Warning – High voltage may be present,
risk of electric shock. DO NOT open
when energised, disconnect power
before opening.

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e-2-s.com Fax: +44 (0)208 740 4200
Document No. D202-00-001-IS Issue 1 25-04-2022 Sheet 4 of 7
On completion of the installation, the flameproof joints should
be inspected to ensure that they are clean and that they have
not been damaged during installation.
Once the screws are removed the cover will hang down out
of the way to gain access to the terminals, the internal earth
terminal and mounting hole recesses.
Call Point Cover Call Point Base
M6 x 60 Cap head Cover Bolts - 4 off Positions
Fig. 2 Accessing the Explosion proof Enclosure.
Check that the earth bonding wire between the two castings
is secure and the ‘O’ ring seal is in place.
When replacing the flameproof cover casting ensure that it is
square with the flameproof chamber casting before inserting.
Carefully place the cover on the base. Only after the cover is
fully in place should the four M6 x 60 Stainless Steel A4-70
cover bolts and their spring washer be tightened down
(tighten torque 3.5Nm). Never use the cover bolts to force the
cover into position.
9) Earthing
The units are provided with internal and external earth
terminals which are mounted in the base of the unit.
Internal earthing connections should be made to the Internal
Earth terminal in the base of the housing using a ring crimp
terminal to secure the earth conductor under the earth clamp.
The earth conductor should be at least equal in size and
rating to the incoming power conductors.
Fig 3 Earth terminals
10) Power Supply Selection
Electrical Ratings
See table 1
250Vac max. / 5.0A max (3.33A max NEC/CEC)
48Vdc max. / 1.0A max
24Vdc max / 3.0A max
11) Selection of Cable. Cable Glands, Blanking
Elements & Adapters
ATEx/IECEx & UKEx Installations:
The equipment must only be installed by suitably qualified
personnel in accordance with the latest issues of the relevant
standards:
EN60079-14 / IEC60079-14: Explosive atmospheres -
Electrical installations design, selection and erection
EN60079-10-1 / IEC60079-10-1: Explosive atmospheres -
Classification of areas. Explosive gas atmospheres
The installation of the units must also be in accordance with
any local codes that may apply and should only be carried
out by a competent electrical engineer who has the
necessary training.
The equipment must not be installed with any obstruction to
the flanged flameproof joint any closer than permitted as per
EN/IEC60079-14, table 13.
For high ambient temperatures the cable entry temperature
may exceed +70ºC or the cable branching point temperature
may exceed 80ºC and therefore suitable heat resisting cables
and cable glands must be used, with a rated service
temperature of at least the values stated below:
For Single Switch models GNExCP7-BGS:
Max. ambient
temperature ºC
50 55 60 65 70
req. Cable / Cable
Gland rating: ºC
76 81 86 91 96
For Dual Switch models GNExCP7-BGD:
Max. ambient
temperature ºC
40 45 50 55 60 65 70
req. Cable /
Cable Gland
rating: ºC
80 85 90 95 100 105 110
The cable gland entries have an M20 x 1.5 entry thread. Only
suitably rated ATEX / IECEx or UKEx certified cable glands
which must be suitable for the type of cable being used and
also meet the requirements of the current Ex ‘d’ flameproof
installation standards EN 60079-14 / IEC60079-14.
When only one cable entry is used the other entries must be
closed with suitably rated ATEX / IECEx or UKEx certified
blanking plugs that meet the requirements of the current Ex
‘db’ and Ex ‘tb’ flameproof installation standards EN 60079-
14 / IEC60079-14 (tightening torque 10Nm).
The stainless steel lift flap is not earthed and may generate
an ignition-capable level of electrostatic charges. It has a max
Wiring terminal
Internal Earthing
External Earthing

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e-2-s.com Fax: +44 (0)208 740 4200
Document No. D202-00-001-IS Issue 1 25-04-2022 Sheet 5 of 7
capacitance of 6.33pF according to EN/IEC60079-0, clause
7.5.
Caution do not change factory applied finishes
NEC / CEC Installations:
The equipment must only be installed by suitably qualified
personnel in accordance with the latest issues of the relevant
standards:
The installation of the units must also be in accordance with
any local codes that may apply and should only be carried
out by a competent electrical engineer who has the
necessary training.
The equipment must not be installed with any obstruction to
the flanged flameproof joint any closer than permitted as per
the NEC/CEC.
For high ambient temperatures the cable entry temperature
may exceed +60ºC or the cable branching point temperature
may exceed 60ºC and therefore suitable heat resisting cables
and cable glands must be used, with a rated service
temperature of at least the values stated below:
For Single Switch model GNExCP7-BG-S:
Max.
ambient
temperature
ºC
35 40 45 50 55 60 65 70
req. Cable /
Cable
Gland
rating: ºC
61 66 71 76 81 86 91 96
For Dual Switch model GNExCP7-BG-D:
Max.
ambient
temperature
ºC
20 25 30 35 40 45 50 55 60 65 70
req. Cable /
Cable
Gland
rating: ºC
60 65 70 75 80 85 90 95 100 105 110
For use in Class I Division II locations, in order to maintain
the db type protection, flameproof conduit seals and/or cable
glands must be used.
The cable gland entries have an M20 x 1.5 entry thread. Only
suitably rated and certified cable glands which must be
suitable for the type of cable being used and also meet the
requirements of the current Ex ‘db’ and Ex ‘tb’ flameproof and
NEC/CEC installation standards (tightening torque 10Nm).
When only one cable entry is used the other entries must be
closed with suitably rated and certified blanking plugs that
meet the requirements of the current Ex ‘db’ and Ex ‘tb’
flameproof and NEC/CEC installation standards (tightening
torque 10Nm).
All Installations:
To access the Ex d chamber, remove the four off M6 x 60
stainless steel A4-70 Cap Head cover bolts.
If the installation is made using conduit, openings must have
a sealing fitting connected as close as practical to the wall of
the enclosure, but in no case more than the size of the
conduit or 2” of enclosure, whichever is the lesser.
Electrical connections are to be made into the PCB / terminal
blocks / DIN rail provided.
Internal earthing connections should be made to the Internal
Earth terminal on the PCBA. The earth conductor should be
at least equal in size and rating to the incoming power
conductors.
On completion of the installation the flameproof joint surfaces
should be inspected to ensure that they are clean and that
they have not been damaged during installation. Flamepaths
are not intended to be repaired.
When fitting the flameproof cover ensure the cover is sitting
flat and correctly positioned on the base. Insert the M6 x 60
stainless steel A4-70 Cap Head cover bolts and fully tighten
down (tightening torque 3.5Nm), ensuring no gap is visible
between the cover and base of the enclosure.
If a high IP (Ingress Protection) rating is required then a
suitable sealing washer must be fitted under the cable glands
or blanking plugs.
The enclosure is non-conducting and may generate an
ignition-capable level of electrostatic charges under certain
extreme conditions. The user should ensure that the
equipment is not installed in a location where it may be
subjected to external conditions that might cause a build-up
of electrostatic charges on non-conducting surfaces.
The M12 Cap fitted to the top side of the unit is not a user
serviceable part and must not be removed during installation
and maintenance.
The GNExCP7 Call Point range can be supplied with the
following types of adapters:
M20 to ½” NPT
M20 to ¾” NPT
M20 to M25
It is important to note that stopping plugs cannot be fitted
onto adapters, only directly onto the M20 entries.
Any other adapters used must be suitably rated and ATEX /
IECEx / UKEx or NEC/CEC certified adapters.
12) Cable & Wiring Connections
Wiring methods shall be in accordance with CSA C22.1,
Canadian Electrical Code, Part I, Safety Standard for
Electrical Installations, Section 32; and CAN/ULC-S524,
Standard for Installation of Fire Alarm Systems.
The units come with two options for the terminal block.
A DIN rail version which has 8-way connection and allows for
limited wiring of EOL devices, or a 6 Way terminal block.
The PCB Terminal Version has a 6-way connector but is
designed to allow for full configuration with Series and EOL
devices in a number of wiring configurations.
For full wiring details see wiring diagrams D202-06-211
For EOL and Series device limitations and configurations see
Section 15. Fitting can be requested by E2S at the order

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e-2-s.com Fax: +44 (0)208 740 4200
Document No. D202-00-001-IS Issue 1 25-04-2022 Sheet 6 of 7
stage or added to the correct terminal blocks afterward. All
devices must comply with the requirements stipulated in
section 15.
Electrical Connections are to be made into the terminal
blocks using solid or stranded wire.
Wires having a cross sectional area between 0.5 mm² to
2.5mm² (AWG 20 – 14) can be connected to each terminal
way.
If an input and output wire is required the 2-off Live/Neutral or
+/- terminals can be used. If fitting 2-off wires to one terminal
way the sum of the 2-off wires must be a maximum cross
sectional area of 2.5mm².
Strip wires to 8mm. Wires may also be fitted using ferrules.
Terminal screws need to be tightened down with a tightening
torque of 0.45 Nm / 5 Lb-in.
When connecting wires to the terminals great care should be
taken to dress the wires so that when the cover is inserted
into the chamber the wires do not exert excess pressure on
the terminal blocks. This is particularly important when using
cables with large cross sectional areas such as 2.5mm².
13) Testing unit operation
The break glass unit can be tested without the need to
break/replace the frangible glass element.
A test key (Plastic Key Supplied with unit) is used to
mechanically drop the glass down activating the switch.
The test key is inserted in the test cam and rotated clockwise
by an angle of 90º the glass element will visibly drop down in
the viewable window.
The call point switch will now change over its contacts to
operate the alarm.
Once testing is complete the unit needs to be reset, the test
key is rotated back anticlockwise 90º to its original vertical
position. The glass element should now raise up so it is level
again (horizontal) in the viewable window.
1. 2. 3.
Insert test Hold in Rotate back
Key rotate position anticlockwise
clockwise during to reset
60º test
14) Replacement of glass element
If the break glass unit has been operated the broken glass
element can be quickly replaced.
The break glass cover plate is removed by unscrewing the 4
off M4 cap head screws attaching it.
Once the cover is removed the broken glass will be free to be
removed, clean out any other fragments of glass carefully.
To fit the new glass element rotate the test cam clockwise by
an angle of 90º (use test key supplied) this will than allow the
glass to fit back into the pocket it sits in, resting on the pivot
point and test cam, ensure the plunger shaft is resting on the
top of the glass, it might need to be pushed up slightly to
achieve this.

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e-2-s.com Fax: +44 (0)208 740 4200
Document No. D202-00-001-IS Issue 1 25-04-2022 Sheet 7 of 7
Pivot point Test Cam Plunger Rotate test cam back
Shaft Upright set point
Whilst lightly holding the glass in place rotate the test cam
back anticlockwise 90º to its original vertical position. The
glass element should now raise up so it is level again
(horizontal) in the viewable window.
Replace the cover plate and tighten the 4 off M4 cap head
screws.
Ensure the glass element is free to move under the cover
plate. This can be done by running through the units test
operation. See section 13 of this instruction manual.
15) End-of-Line and Series Devices
All models can be fitted with series resistors, end-of-line
monitoring resistors, monitoring diodes and zener diodes if
supplied with direct current up to 48Vdc and limited to a
maximum total power consumption no greater than 6.224W.
Min. resistor values and current limitations must be observed
depending on supply voltage and type of components fitted. If
a combination of resistors / diodes / zener diodes is used,
values for all components must be observed and lowest
current limit for either component becomes overall limit.
Current limitation for units fitted with end-of-line resistors,
diodes or zener diodes must be ensured by using a current
limited power supply or fitting a current limiting resistor at the
control panel (not provided).
The following table 2 shows limitations for all possible
variations:
EOL (End of line) device;
resistor – ExxxR
diode – ED1
zener – ExxxZ
Series (In line) device;
resistor – SxxxR
diode – SD1
zener – SxxxZ
LED
Microswitch 1 = M/S 1
Microswitch 2 = M/S 2
Table 2 : EOL and Series Devices limits
The unit can be wired with a maximum of 4 module devices –
see wiring diagram D202-06-211
Note:- The maximum voltage stated must not be exceeded,
as the internal resistor modules are rated as compliant with
Ex d according to the units voltage
16) Maintenance, Overhaul, Repair and
Cleaning
Maintenance, repair and overhaul of the equipment should
only be carried out by suitably qualified personnel in
accordance with the current relevant standards:
For ATEX / IECEx / UKEx
For US & CEC Class / Div / Zone
UL 60079-19 Explosive atmospheres - Equipment repair,
overhaul and reclamation
UL 60079-17 Explosive atmospheres - Electrical
installations inspection and maintenance
Electrostatic charging hazard – clean only with a damp cloth.
Units must not be opened while an explosive atmosphere is
present.
Caution do not change factory applied finishes
Supply voltage 24Vdc Supply voltage 48Vdc
Type of
component
fitted
value Max.
current
(mA)
value Max.
current
End-of-Line
Resistor
*See note
min. 470R/
2W or min.
2k2 / 0.5W
3000 min. 2k2 /
2W or min.
8k2 / 0.5W
1000
End-of-Line
Diode
Type 1N5401
2W 59.13 2W 25.26
Series
Resistor
*See note
min. 470R/
2W or min.
2k2 / 0.5W
3000 min. 2k2 /
2W or min.
8k2 / 0.5W
1000
Series Diode
Type 1N5401
2W 59.13 2W 25.26
Series Zener
Diode Type
1N5333B
3.3V 230 3.3V 230
4.7V 162 4.7V 162
5.1V 149 5.1V 149
5.6V 136 5.6V 136
6.2V 122 6.2V 122
6.8V 112 6.8V 112
10V 76 10V 76
12V 63 12V 63
EN60079-19
IEC60079-19
Explosive atmospheres - Equipment repair,
overhaul and reclamation
EN 60079-17
IEC60079-17
Explosive atmospheres - Electrical
installations inspection and maintenance

ALL DIMENSIONS IN MM
IF IN DOUBT, ASK -
DO NOT SCALE
A3
2S
warning signals
NTS
GNExCP7 CALL POINT
WIRING / CIRCUIT OPERATION DIAGRAM
D202-06-211
14
OF
5
GNExCP7
Addition of BG version ; options clarified
RNP 15-04-2022
R.N.POTTS
R.S.RAIT 05-03-2020
B.ISARD
123456
M/S 1
78
KEY:
COM - Common
N/C - Normally Closed
(Contacts closed in unoperated state)
N/O - Normally Open
(Contacts open in unoperated state)
123456
M/S 1
78
COM N/O
WIRE LINK
1A - Circuit as shown in Unoperated condition
Terminals (4/5) & (7/8) open
Terminals (4/5) & (6) closed
DIODE
ZENER DIODE
POSITIVE (+) COMMON
(IF DIODES SUPPLIED & CONFIGURED BY E2S)
12345678
EOL
SER
M/S 1
Standard Unit withsuggested Series / EOL
Devices - Alternative Configuration
2A - Circuit as shown in Unoperated condition
Terminals (4/5) & (7/8) open
Terminals (4/5) & (6) closed
Standard Unit as supplied by E2S
Without Series / EOL Devices
N/C COM N/O
N/C
EOL
SER
123456
M/S 1
78
COM N/O
WIRE LINK
1B - Circuit as shown in Operated condition
Terminals (4/5) & (7/8) closed
Terminals (4/5) & (6) open
N/C
12345678
12345678
COM N/O
N/C
COM
+
N/O
-
N/C
-
COM
+
N/O
-
N/C
-
Standard Unit showing possitions
of optional Series / EOL Devices
123456
M/S 1
78
2B - Circuit as shown in Operated condition
Terminals (4/5) & (7/8) closed
Terminals (4/5) & (6) open
COM N/O
N/C
EOL
SER
NOTE: These can be fitted either
by customer or pre-installed by
E2S at point of order.
When fitting diodes or zener diodes, polarity
across devices must be observed
(Resistor polarity is unimportant)
SERIES
EOL
Wiring option shown with EOL &
series devices acting in parallel
3A - Circuit as shown in Unoperated condition
Terminals (4/5) & (7/8) open
Terminals (4/5) & (6) closed
DIODE
ZENER DIODE
POSITIVE (+) COMMON
(IF DIODES SUPPLIED & CONFIGURED BY E2S)
12345678
12345678
COM
+
N/O
-
N/C
-
COM
+
N/O
-
N/C
-
When fitting diodes or zener diodes, polarity
across devices must be observed
(Resistor polarity is unimportant)
SERIES
EOL
Wiring option shown with EOL &
series devices acting in series
45 78
45 78
12345678
EOL
SER
M/S 1
COM N/O
N/C
3B - Circuit as shown in Operated condition
Terminals (4/5) & (7/8) closed
Terminals (4/5) & (6) open
E2S PART NO.
GNExCP7-BG
GNExCP7-PB
GNExCP7-PM
GNExCP7-PT
DESCRIPTION
GNExCP7 Ex d GRP CALL POINT BREAK GLASS
GNExCP7 Ex d GRP CALL POINT PUSH BUTTON
GNExCP7 Ex d GRP CALL POINT MOMENTARY PUSH BUTTON
GNExCP7 Ex d GRP CALL POINT PUSH BUTTON TOOL RESET
DATA REFERENCE
1.24.150
1.24.180
1.24.170
1.24.160
GNExCP7 [ ] [S] [D] SWITCH TYPE: [S] - Single Microswitch TERMINAL TYPE [D] - DIN RAIL
FOR PERMITTED MIN/MAX
VALUES OF EOL & SERIES
DEVICES, PLEASE REFER TO
INSTRUCTIONS
05-03-2020
05-03-2020
ACN0102

ALL DIMENSIONS IN MM
IF IN DOUBT, ASK -
DO NOT SCALE
A3
2S
warning signals
NTS 24
OF
R.N.POTTS
123456
M/S 1 M/S 2
78
N/O
COM EOL
4A - Circuit as shown in Unoperated condition
Terminals (1) & (4) M/S 1 and (5) & (8) M/S 2 open
Terminals (1) & (3) M/S 1 and (5) & (7) M/S 2 closed
GNExCP7 [ ] [D] [D] SWITCH TYPE: [D] - Double Microswitch TERMINAL TYPE [D] - DIN RAIL
When fitting diodes or zener diodes,
polarity across devices must be observed
(Resistor polarity is unimportant)
Standard Unit showing positions of
optional EOL Devices
NOTE: These can be fitted either
by customer or pre-installed by
E2S at point of order.
N/C
N/O
COM EOL
N/C
123456
M/S 1 M/S 2
78
N/O
COM EOL
4B - Circuit as shown in Operated condition
Terminals (1) & (4) M/S 1 and (5) & (8) M/S 2 closed
Terminals (1) & (3) M/S 1 and (5) & (7) M/S 2 open
N/C
N/O
COM EOL
N/C
GNExCP7 CALL POINT
WIRING / CIRCUIT OPERATION DIAGRAM
D202-06-211
FOR PERMITTED MIN/MAX
VALUES OF EOL & SERIES
DEVICES, PLEASE REFER TO
INSTRUCTIONS
GNExCP7
R.S.RAIT 05-03-2020
B.ISARD 05-03-2020
05-03-2020
DIODE
ZENER DIODE
POSITIVE (+) COMMON
(IF DIODES SUPPLIED & CONFIGURED BY E2S)
12345678
12345678
COM
+
N/O
-
N/C
-
COM
+
N/O
-
N/C
-
COM
+
N/O
-
N/C
-
COM
+
N/O
-
N/C
-
Standard Unit showing positions of
optional Series and EOL Devices
123456
M/S 1 M/S 2
78
N/O
COM
4A - Circuit as shown in Unoperated condition
Terminals (1) & (4) M/S 1 and (5) & (8) M/S 2 open
Terminals (1) & (3) M/S 1 and (5) & (7) M/S 2 closed
N/C
N/O
COM
N/C
123456
M/S 1 M/S 2
78
N/O
COM EOL
4B - Circuit as shown in Operated condition
Terminals (1) & (4) M/S 1 and (5) & (8) M/S 2 closed
Terminals (1) & (3) M/S 1 and (5) & (7) M/S 2 open
N/C
N/O
COM EOL
N/C
SER
EOL EOL
SER
SER
EOL EOL
SER
Standard Unit showing positions of
optional Series Devices
123456
M/S 1 M/S 2
78
N/O
COM
4A - Circuit as shown in Unoperated condition
Terminals (1) & (4) M/S 1 and (5) & (8) M/S 2 open
Terminals (1) & (3) M/S 1 and (5) & (7) M/S 2 closed
N/C
N/O
COM
N/C
123456
M/S 1 M/S 2
78
4B - Circuit as shown in Operated condition
Terminals (1) & (4) M/S 1 and (5) & (8) M/S 2 closed
Terminals (1) & (3) M/S 1 and (5) & (7) M/S 2 open
SER SER
SER SER
DIODE
ZENER DIODE
POSITIVE (+) COMMON
(IF DIODES SUPPLIED & CONFIGURED BY E2S)
12345678
12345678
COM
+
N/O
-
N/C
-
When fitting diodes or zener diodes,
polarity across devices must be observed
(Resistor polarity is unimportant)
COM
+
N/O
-
N/C
-
COM
+
N/O
-
N/C
-
COM
+
N/O
-
N/C
-
N/O
COM
N/C
N/O
COM
N/C
5
See Sht 1
RNP 15-04-2022
ACN0102

ALL DIMENSIONS IN MM
IF IN DOUBT, ASK -
DO NOT SCALE
A3
2S
warning signals
NTS 34
OF
R.N.POTTS
GNExCP7 [ ] [D] [D] ...[W1] SWITCH TYPE: [D] - Double Microswitch TERMINAL TYPE [D] - DIN RAIL VERSION [W1] - Special Wiring
GNExCP7 CALL POINT
WIRING / CIRCUIT OPERATION DIAGRAM
D202-06-211
GNExCP7
R.S.RAIT 05-03-2020
B.ISARD 05-03-2020
05-03-2020
Special Wiring
Option A - Series & EOL on M/S 1
Other wiring configurations are available pre-configured
Contact E2S sales for special wiring requests
4A - Circuit as shown in Unoperated condition
Terminals (1) & (4) M/S 1 and M/S 2 open
Terminals (1) & (3) M/S 1 and M/S 2 closed
4B - Circuit as shown in Operated condition
Terminals (1) & (4) M/S 1 and M/S 2 closed
Terminals (1) & (3) M/S 1 and M/S 2 open
123456
M/S 1 M/S 2
78
N/O
COM
4A - Circuit as shown in Unoperated condition
Terminals (1) & (4) M/S 1 and (5) & (8) M/S 2 open
Terminals (1) & (3) M/S 1 and (5) & (7) M/S 2 closed
N/C
N/O
COM
N/C
123456
M/S 1 M/S 2
78
N/O
COM EOL
4B - Circuit as shown in Operated condition
Terminals (1) & (4) M/S 1 and (5) & (8) M/S 2 closed
Terminals (1) & (3) M/S 1 and (5) & (7) M/S 2 open
N/C
N/O
COM
N/C
SER
EOL
SER
EOL
4A - Circuit as shown in Unoperated condition
Terminals (1) & (4) M/S 1 and M/S 2 open
Terminals (1) & (3) M/S 1 and M/S 2 closed
4B - Circuit as shown in Operated condition
Terminals (1) & (4) M/S 1 and M/S 2 closed
Terminals (1) & (3) M/S 1 and M/S 2 open
Special Wiring
Option B - M/S 1 and M/S 2 connected
Special Wiring
Option C - Series & EOL with M/S 1 and M/S 2 connected
123456
M/S 1 M/S 2
78
N/O
COM
N/C
123456
M/S 1 M/S 2
78
N/O
COM
N/C
SER
EOL
123456
M/S 1 M/S 2
78
N/O
COM
N/C
123456
M/S 1 M/S 2
78
N/O
COM
N/C
SER
EOL
5
See Sht 1
RNP 15-04-2022
ACN0102

ALL DIMENSIONS IN MM
IF IN DOUBT, ASK -
DO NOT SCALE
A3
2S
warning signals
NTS 44
OF
123
NO SERIES DEVICE
DEFAULT PIN 1 & 2
LINKED
123
SR1 OR SR2
SERIES RESISTOR
FIT IN 1 & 3
123
SD1 OR SD2
SERIES DIODE
FIT IN 1 & 3
123
SZ1 OR SZ2
SERIES ZENER
DIODE FIT IN 1 & 3
123
NO EOL DEVICE
DEFAULT NOT
LINKED
123
ER1
EOL RESISTOR
FIT IN 1 & 3
123
ED1
EOL DIODE
FIT IN 1 & 3
123
EZ1
EOL ZENER
DIODE FIT IN 1 & 3
123
ER1
EOL RESISTOR
FIT IN 2 & 3
WIRING OPTION 2
123456
- -
M/S 1 M/S 2
123 123
123 123
5A - Circuit as shown in Unoperated condition
Terminals +(1) & -(3) M/S 1 and +(4) & -(6) M/S 2 open
Terminals +(1) & (2) M/S 1 and +(4) & (5) M/S 2 closed
M/S 1
+
M/S 2
+
123456
- -
M/S 1 M/S 2
123 123
123 123
M/S 1
+
M/S 2
+
5B - Circuit as shown in Operated condition
Terminals +(1) & (2) M/S 1 and +(4) & (5) M/S 2 open
Terminals +(1) & -(3) M/S 1 and +(4) & -(6) M/S 2 closed
R.N.POTTS
Optional Single or Double Microswitch
Circuit shown with Double Microswitch, Unit un-operated : GNExCP7 PCB Version
Devices selected only as example:
On M/S 1: Series resistor and EOL Zener diode
On M/S 2: EOL resistor with no series device
GNExCP7 [ ] [S] [P] SWITCH TYPE: [S] - Single Microswitch TERMINAL TYPE [P] - PCB
GNExCP7 [ ] [D] [P] SWITCH TYPE: [D] - Double Microswitch TERMINAL TYPE [P] - PCB
GNExCP7 CALL POINT
WIRING / CIRCUIT OPERATION DIAGRAM
D202-06-211
FOR PERMITTED MIN/MAX
VALUES OF EOL & SERIES
DEVICES, PLEASE REFER TO
INSTRUCTIONS
GNExCP7
R.S.RAIT 05-03-2020
B.ISARD 05-03-2020
05-03-2020
EOL DEVICE 1 SERIES DEVICE 1
EOL DEVICE 2 SERIES DEVICE 2
EOL DEVICE 1 SERIES DEVICE 1
EOL DEVICE 2 SERIES DEVICE 2
5
See Sht 1
RNP 15-04-2022
ACN0102

E2STelephone:+44(0)2087438880Fax:+44(0)2087404200Email:[email protected]www.e2s.comDC‐078_Issue_E‐Page1of1‐QAF_252_Issue_5
MartinStreetzDocumentNo.:DC‐078_Issue_E
QualityAssuranceManagerDateandPlaceofIssue:London,23/12/2020
EUDeclarationofConformity
Manufacturer: EuropeanSafetySystemsLtd.
ImpressHouse,MansellRoad,Acton
London,W37QH
UnitedKingdom
AuthorisedRepresentative:E2SWarnsignaltechnikUG
Charlottenstrasse45‐51
72764Reutlingen
Germany
EquipmentType:GNExCP7‐BG,GNExCP7‐PB,GNExCP7‐PM,GNExCP7‐PT
Directive2014/34/EU:EquipmentandProtectiveSystemsforuseinPotentiallyExplosiveAtmospheres(ATEX)
NotifiedBodyforEUtypeExamination(ModuleB):ULInternationalDemkoA/S
NotifiedBodyNo.:0539
Borupvang5A,2750Ballerup,Denmark
EU‐typeExaminationCertificate(ModuleB):DEMKO19ATEX2101X
NotifiedBodyforQualityAssuranceNotification/ConformitytoEU‐type
basedon
qualityassuranceoftheproductionprocess(ModuleD):
SiraCertificationService
NotifiedBodyNo.:2813
CSAGroupNetherlandsB.V,Utrechtseweg310,6812AR,Arnhem,Netherlands
QualityAssuranceNotification(ModuleD):SIRA05ATEXM342
Provisionsfulfilledbytheequipment:II2GExdIICT6…T5Gb
II2DExtbIIICT90°C….T80°CDb
Standardsapplied:EN60079‐0:2018
EN60079‐1:2014
EN60079‐31:2014
IP6XDustProtectiontoEN60079‐0/EN60079‐31
Directive2014/30/EU:ElectromagneticCompatibilityDirective(EMC)
Standardsapplied:EN61000‐6‐1:2007
EN61000‐6‐2:2005
EN61000‐6‐3:2007/A1:2011/AC:2012
EN61000‐6‐4:2007/A1:2011
Directive2011/65/EU:Restrictionoftheuseofcertainhazardoussubstancesinelectricalandelectronicequipment(RoHS)
Theproductandallthecomponentscontainedwithinitareinaccordancewiththerestrictionoftheuseofhazardoussubstancesinelectricalandelectronic
equipment,includingamendmentbyDirective2015/863/EU.
Regulation(EC)1907/2006:Registration,Evaluation,AuthorisationandRestrictionofChemicals(REACH)
Theproductandallthecomponentscontainedwithinitarefreefromsubstancesofveryhighconcern.
OtherStandardsandRegulations
EN60529:1991+A1:2000+A2:2013.‐Degreesofprotectionprovidedbyenclosures(IPcode)–enclosureratedIP66/67
OnbehalfofEuropeanSafetySystemsLtd.,Ideclarethat,onthedatetheequipmentaccompaniedbythisdeclarationisplacedonthemarket,theequipment
conformswithalltechnicalandregulatoryrequirementsoftheabovelisteddirectives,regulationsandstandards.
ThisDeclarationisissuedunderthesoleresponsibilityofthemanufacturer.

E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: sal[email protected] www.e2s.com DC-099_Issue_A - Page 1 of 1 - QAF_252_Issue_5
Martin Streetz Document No.: DC-099_Issue_A
Quality Assurance Manager Date and Place of Issue: London, 24/02/2022
UKCA Declaration of Conformity
Manufacturer: European Safety Systems Ltd.
Impress House, Mansell Road, Acton
London, W3 7QH
United Kingdom
Equipment Type: GNExCP7-BG, GNExCP7-PB, GNExCP7-PM, GNExCP7-PT
Directive UKSI 2016:1107 (as amended by UKSI 2019:696) – Schedule 3A, Part 1 : Product or Protective System Intended for use in Potentially Explosive Atmospheres
(UKCA)
Notified Body for
UK
type Examination
(Module B)
:
UL International (UK) Ltd
Notified Body No.: 0843
Unit 1-3 Horizon Kingsland Business Park, Wade Road,
Basingstoke, Hampshire RG24 8AH UK
UK
-
type Examination Certificate
(Module B)
:
UL21UKEX2134X
Notified Body for Quality Assurance Notification
/ Conformity to EU
-
type
based on quality assurance of the production process (Module D):
Sira Certification Service
Notified Body No.: 0518
Rake Lane, Eccleston, Chester CH4 9JN, UK
Quality Assurance Notification
(Module D)
:
CSAE 22UKQAN0046
Provisions fulfilled by the equipment:
II 2G Ex d IIC T
6…T
5
Gb
II 2D Ex tb IIIC T90°C… T80°C Db
Standards applied:
EN 60079
-
0:
2018
EN 60079-1:2014
EN 60079-31:2014
IP6X Dust Protection to EN60079-0 / EN60079-31
Directive 2014/30/EU: Electromagnetic Compatibility Directive (EMC)
Standards applied:
EN 61000
-
6
-
1:2007
EN 61000-6-2:2005
EN 61000-6-3:2007 / A1:2011 / AC: 2012
EN 61000-6-4:2007 / A1: 2011
Directive 2011/65/EU: Restriction of the use of certain hazardous substances in electrical and electronic equipment (RoHS)
The product and all the components contained within it are in accordance with the restriction of the use of hazardous substances in electrical and electronic
equipment, including amendment by Directive 2015/863/EU.
Regulation (EC) 1907/2006: Registration, Evaluation, Authorisation and Restriction of Chemicals (REACH)
The product and all the components contained within it are free from substances of very high concern.
Other Standards and Regulations
EN 60529:1991 + A1:2000 + A2:2013. - Degrees of protection provided by enclosures (IP code) – enclosure rated IP66/67
On behalf of European Safety Systems Ltd., I declare that, on the date the equipment accompanied by this declaration is placed on the market, the equipment
conforms with all technical and regulatory requirements of the above listed directives, regulations and standards.
This Declaration is issued under the sole responsibility of the manufacturer.
Other manuals for GNExCP7-BG-S
1
This manual suits for next models
3
Table of contents
Other E2S Fire Alarm manuals
Popular Fire Alarm manuals by other brands

Ampac
Ampac ACP-02 installation guide

Notifier
Notifier ACS Series installation manual

Siemens
Siemens Synova FC330A operating manual

Polon-Alfa
Polon-Alfa POLON 4000 Series Installation and maintenance manual

Edwards
Edwards 2400 Series Product/Technical Bulletin

Taktis
Taktis Incite Fire S3 operating instructions