EAE LC100 User manual

PRODUCT MANUAL LC100
EAE KNX LINE COUPLER LC100 R0
©EAE Technology www.eaetechnology.com Page 1 / 17
EAE KNX LINE COUPLER
Product Order Nr: 48074

PRODUCT MANUAL LC100
EAE KNX LINE COUPLER LC100 R0
©EAE Technology www.eaetechnology.com Page 2 / 17
Table of Contents
1. General Description ........................................................................................................................3
1.1. Communication Objects ...........................................................................................................4
1.2. LC1000 as Programming Interface ............................................................................................4
1.3. Feature Summary.....................................................................................................................4
2. Device Technology ..........................................................................................................................5
2.1. Commissioning.........................................................................................................................5
2.2. Device Peripherals....................................................................................................................6
2.3. Function Button .......................................................................................................................7
2.4. Physical Addressing Mode........................................................................................................8
2.5. KNX Topology...........................................................................................................................9
2.6. LC100 as TP Coupler ...............................................................................................................10
2.5. LC100 as TP Repeater .............................................................................................................11
3. Default Factory Settings ................................................................................................................12
4. Technical Data ..............................................................................................................................13
5. Technical Drawing.........................................................................................................................14
7. ETS Parameters.............................................................................................................................15
7.1. General ..................................................................................................................................15
7.2. Main Line ...............................................................................................................................16
7.3. Subline...................................................................................................................................17

PRODUCT MANUAL LC100
EAE KNX LINE COUPLER LC100 R0
©EAE Technology www.eaetechnology.com Page 3 / 17
1. General Description
The KNX TP Media Coupler LC100 provides a bi-directional data connection between two KNX TP lines
or areas and works as a KNX line/area coupler in the KNX network. KNX TP main line and KNX TP subline
are coupled having a galvanic isolation in between. Extended frames and long telegrams with up to
240 bytes APDU length are supported.
Using the TP Coupler application, LC100 can be used as KNX TP line coupler to connect different TP
lines, but also as a KNX TP area coupler to connect different TP areas or installation systems via a TP
Backbone. Telegram filtering is accomplished according to the installation place in the hierarchy
(Physical[ly addressed] Telegrams) and according to the built in filter tables for group communication
(Group [oriented] Telegrams). For detailed diagnosis, all operational modes/states are shown by a duo-
LED display. Programming on main line from the subline can be suppressed. Number of repetitions on
both KNX TP lines can be reduced.
Using the TP Repeater application, LC100 is able to extend a KNX TP line providing unfiltered data
transfer and galvanic isolation between segments. Up to four line segments can form a single KNX TP
line by connecting three LC100 line repeaters. Each line segment requires its own KNX power supply
unit.
To ease commissioning and troubleshooting, special routing/repetition/confirmation ETS settings and
a configurable Manual Function for short-time telegram filter switch-off are available. E.g. “transmit
all group telegrams” can be activated by a single button press. After the set time period, LC100
switches back to normal operation automatically. Another feature to increase the data throughput is
the ability to send IACKs on own telegrams.

PRODUCT MANUAL LC100
EAE KNX LINE COUPLER LC100 R0
©EAE Technology www.eaetechnology.com Page 4 / 17
1.1. Communication Objects
LC100 has no KNX communication objects.
1.2. LC1000 as Programming Interface
LC100 can be used together with the ETS as a programming interface. The device provides an additional
physical address for this purpose which can be used for a line coupling or repeating.
1.3. Feature Summary
- LC100 supports extended frames and long telegrams up to 240 bytes APDU length. (With all MEC
couplers and UIM interfaces long messages e.g. for energy metering applications and visualization
purposes can be processed.)
- IACK sending on sent out messages is ETS configurable.
- When there is no IACK response on the subline, LC100 is able to repeat messages up to three times.
Repetitions can be configured for both Physical Telegrams and Group Telegrams via ETS (to ease
troubleshooting). E.g. after an IACK response no repetition is following and the negative IACK/BUSY
failure mechanism is maintained.
- For an ETS configurable time period, it is possible to switch off telegram filtering by only pressing a
button on the device front panel. Without additional ETS download filtering is suspended. This is
necessary for running fast diagnostics on site.
- Suspending telegram filtering eases commissioning and debugging. When filtering is suspended,
temporary access to other lines becomes possible.
- Automatic function for switching back to run-time telegram filtering after configurable suspension
period (see Manual Mode). This avoids forgetting the reactivation of filtering.
- In networks with high busload the internal amount of communication buffers are capable of
smoothing peeks in the communication load course.
- LC100’s ETS database entries are available for ETS4 and later.

PRODUCT MANUAL LC100
EAE KNX LINE COUPLER LC100 R0
©EAE Technology www.eaetechnology.com Page 5 / 17
KNX TP Main Line
KNX TP Sub Line
2. Device Technology
2.1. Commissioning
Please note for commissioning with default settings:
•All telegrams are blocked because the filter table is not defined
•The Manual Function switch-off time is 120 min
•Physical address is 15.15.0
Please read carefully before first use:
•After connection to the KNX bus system, the device works with its default settings
•Warning: Do not connect to 230 V. The device is supplied by the KNX bus and does not require
any additional external power supply
•The device may only be installed and put into operation by qualified electrician or authorized
personnel
•For planning and construction of electric installations the appropriate specifications,
guidelines and regulations in force of the respective country have to be complied
•For mounting use an appropriate equipment according to IEC60715
•Installation on a 35 mm DIN rail (TH35)
•Connect the KNX bus line as for common KNX bus connections with a KNX bus cable, to be
stripped and plugged into a KNX TP connector
•Do not damage electrical insulations during connecting
•Installation only in dry locations
•Accessibility of the device for operation and visual inspection must be provided
•For changing the configuration use the ETS
•The housing must not be opened
•Protect the device from moisture, dirt and damage
•The device needs no maintenance
•If necessary, the device can be cleaned with a dry cloth
•In the case of damage (at storage, transport) no repairs may be carried out by unauthorized
personnel

PRODUCT MANUAL LC100
EAE KNX LINE COUPLER LC100 R0
©EAE Technology www.eaetechnology.com Page 6 / 17
2.2. Device Peripherals
1- Indicator LEDs
2- Function Button
3- Programming LED
4- Programming Button
5- KNX –Main Line
6- KNX –Sub Line
Indicator
Green
Blinked
Green
Orange
Red
Blinked Red
Off
Connect –
Main
KNX Main
line OK
-
Manual
Function
Active
-
-
No KNX Main
Line connection
Connect –Sub
KNX Sub
line OK
-
-
-
-
No KNX Sub Line
connection
Tx/Rx –Main
-
Traffic on
KNX Main
line
-
Transmissio
n Error on
KNX Main
line
No traffic on
KNX Main line
Tx/Rx –Sub
-
Traffic on
KNX Sub line
-
Transmissio
n Error on
KNX Sub
line
No traffic on
KNX Sub line
Group Address
Filter
-
Route all
Block
all
-
No route
Physical
Address
Filter
-
Route all
Block
all
-
No route
Programming
LED
-
-
-
Prg.
mode
-
Programming
mode de-active

PRODUCT MANUAL LC100
EAE KNX LINE COUPLER LC100 R0
©EAE Technology www.eaetechnology.com Page 7 / 17
2.3. Function Button
Long press (3 sec)
- Switch to manual override.
- Default function is set with LAN line and (KNX) line parameter.
- Manual override functionality is configured in “General parameters”.
NOTE: The latest downloaded settings (parameters) and filter table are still available after switching
back from “Manual operation” to “Normal operation”.
Very long press (15s)
LEDs: LEDs are on red
- Press and release button after 15 sec and press again for 3 sec: resets all the parameter to factory
default (incl. physical address).

PRODUCT MANUAL LC100
EAE KNX LINE COUPLER LC100 R0
©EAE Technology www.eaetechnology.com Page 8 / 17
2.4. Physical Addressing Mode
LED addressing mode
Off: normal operating mode
On: addressing mode
After receiving the physical address, the LC100 automatically returns from addressing mode to the
normal operating mode.
Button addressing mode
Button for switching between normal operating mode and addressing mode for assigning the physical
address.

PRODUCT MANUAL LC100
EAE KNX LINE COUPLER LC100 R0
©EAE Technology www.eaetechnology.com Page 9 / 17
2.5. KNX Topology
Via a line/area coupler up to 15 lines can be connected to a main line called an area. It is possible to
have up to 64 bus devices on one line. With use of line repeaters, a line can theoretically be extended
to 255 bus devices. This means up to four line segments form a single KNX TP line. But it is common
practice on exceeding 64 bus devices to insert a new line instead of extending the originating one.
The free tree structure of the KNX topology prevents problems caused by circling telegrams and heavy
bus load. To maintain this condition, interconnection between lines or line segments is strictly
forbidden.
LC100
LC100
LC100
LC100
LC100
LC100

PRODUCT MANUAL LC100
EAE KNX LINE COUPLER LC100 R0
©EAE Technology www.eaetechnology.com Page 10 / 17
2.6. LC100 as TP Coupler
When LC100 receives telegrams (for example during commissioning) that use Physical Addresses as
destination addresses, it compares the Physical Addresses of the receiver with its own physical address
and decides on that whether it has to route the telegrams or not.
When LC100 receives telegrams that use group addresses as destination addresses, it reacts in
accordance with the parameter settings. During normal operation (with Group Telegram routing set
to filter), LC100 only routes telegrams whose group addresses are entered in its filter table.
If a telegram is routed by LC100 without receiving the corresponding acknowledgement, i.e. due to a
missing receiver or to a transmission error, the telegram will be repeated up to three times (depending
on the ETS setting). With the parameters „Repetitions if errors...“, this function can be configured
separately for each line and both kinds of telegrams. It is recommended to use the default parameter
setting.
If not already configured as “Line Coupler”, the ETS application program “TP Coupler” has to be
downloaded to the device. Under the Information tab the configuration setting can be changed by the
drop-down menu “Change Application Program”. After changing the configuration setting the filter
table entries can be added manually. Updating the application program version can also be done here.

PRODUCT MANUAL LC100
EAE KNX LINE COUPLER LC100 R0
©EAE Technology www.eaetechnology.com Page 11 / 17
2.5. LC100 as TP Repeater
Any received telegram is routed to all lines irrespective of in which line it is processed. Line repeaters
make no use of a filter table. It is therefore not important whether the telegram is generated within a
line or whether it is sent from an upper line to a lower line via a coupler.
If a telegram is routed by LC100 without receiving the corresponding acknowledgement, i.e. due to a
missing receiver or to a transmission error, the telegram will be repeated up to three times (depending
on the ETS setting). With the parameters „Repetitions if errors...“, this function can be configured
separately for each line and both kinds of telegrams. It is recommended to use the default parameter
setting.
If not already configured as Line/Area/BB Repeater, the ETS application program “TP repeater” has to
be downloaded to the device. Under the Information tab the configuration setting can be changed by
the drop-down menu “Change Application Program”. After changing the configuration setting the filter
table entries can be added manually. Updating the application program version can also be done here.

PRODUCT MANUAL LC100
EAE KNX LINE COUPLER LC100 R0
©EAE Technology www.eaetechnology.com Page 12 / 17
3. Default Factory Settings
Marking/Design
LC100
Physical address
15.15.0
Main Line
Group telegrams 0-13
Filter (filter table is empty)
Group telegrams 14-31
route all
Physical telegrams
filter
Physical: Repetition if errors on main line
up to 3 repetitions
Group: Repetition if errors on main line
up to 3 repetitions
Telegram confirmations on main line
if routed
Send confirmation on own telegrams
no
Subline
Group telegrams 0-13
Filter (filter table is empty)
Group telegrams 14-31
route all
Physical telegrams
filter
Physical: Repetition if errors on subline
up to 3 repetitions
Group: Repetition if errors on subline
up to 3 repetitions
Telegram confirmations on subline
if routed
Send confirmation on own telegrams
no
Configuration from subline
allow

PRODUCT MANUAL LC100
EAE KNX LINE COUPLER LC100 R0
©EAE Technology www.eaetechnology.com Page 13 / 17
4. Technical Data
Protection Class
IP 20
EN 60 529
Safety class
III
EN 61 140
Power supply
- Voltage
21V… 30V DC, SELV
- Current consumption
< 10 mA
Type of contact
- potential-free, bistable
Installation
- 35mm mounting rail
EN 60 715
Operating elements
- LED (red) and button
- Function Button
For physical address
For special modes
Temperature range
- Ambient
-5° C + 45° C
- Storage
-25° C + 55° C
- Transport
-25° C + 70° C
Humidity
- max. air humidity
95 % no moisture
condensation
Dimensions
90x36x71 mm
Weight
62g
Box
Plastic, polycarbonate, color grey
CE
In accordance with the EMC guideline and low
voltage
NOTE: Device default physical address is 15.15.0. In order to configure switch actuator, ETS application
file “.knxprod” is needed. It’s possible to download the file on EAE website. ETS is required for
programming the device. Parameter settings can be changed by ETS. Learn more by reading ETS help
file.

PRODUCT MANUAL LC100
EAE KNX LINE COUPLER LC100 R0
©EAE Technology www.eaetechnology.com Page 14 / 17
5. Technical Drawing

PRODUCT MANUAL LC100
EAE KNX LINE COUPLER LC100 R0
©EAE Technology www.eaetechnology.com Page 15 / 17
7. ETS Parameters
7.1. General
Picture 1: General
ETS-Text
Range
[Default value]
Comment
Manual Function
disabled
pass all telegrams
pass all Physical telegrams
pass all Group telegrams
[pass all telegrams]
Configuration setting for telegram routing
when the Manual Function is active.
Switch-off time for
Manual Function
10 min, 1 hour, 4 hours,
8 hours
[1 hour]
After expiry of this time period the
Manual Function is switched off
automatically.
Table 1: Parameter General

PRODUCT MANUAL LC100
EAE KNX LINE COUPLER LC100 R0
©EAE Technology www.eaetechnology.com Page 16 / 17
7.2. Main Line
For Group Telegrams and Physical Telegrams the setting “transmit all” is intended only for testing
purposes. Please do not use for normal operation.
NOTE: If the parameter “Send confirmation on own telegrams” is set to “yes”, the LC100 systematically
sends an ACK on any own routed telegram. Since the repeater does not use a filter table, it is useful to
have an ACK sent along with routed telegrams.
Picture 2: Main Line Tab Parameters
ETS-Text
Range
[Default value]
Comment
Telegram routing
Group and Physical: route
configure
[Group and Physical: route]
route:
all telegrams are routed
configure:
The following parameters must
be set manually.
Physical telegrams
transmit all
block
[transmit all]
•Physical telegrams are all routed.
•Physical telegrams are all blocked.
Physical telegrams:
Repetition
if errors on main line
no
up to 3 repetitions
only one repetition
[only one repetition]
After main line transmission error (e.g. due to
missing receiver) Physical telegrams
•are not repeated.
•are repeated max. 3 times.
•are repeated once.
Group telegrams:
Repetition
if errors on main line
no
up to 3 repetitions
only one repetition
[only one repetition]
After main line transmission error (e.g. due to
missing receiver) Group telegrams
•are not repeated.
•are repeated max. 3 times.
•are repeated once.
Telegram confirmation
on main line
If routed
always
[always]
•Routed telegrams to the subline are
confirmed by an ACK on the main line.
•Each telegram on the mainline is confirmed
by an ACK.
Send confirmation on
own telegrams
yes
no
[yes]
•Telegrams sent out to the mainline are
confirmed by added ACK.
•No ACK confirmation.
Table 2: Main Line Tab Parameter Settings

PRODUCT MANUAL LC100
EAE KNX LINE COUPLER LC100 R0
©EAE Technology www.eaetechnology.com Page 17 / 17
7.3. Subline
For Group Telegrams and Physical Telegrams the setting “transmit all” is intended only for testing
purposes. Please do not use for normal operation.
Picture 3: Subline Tab Parameters
ETS-Text
Range
[Default value]
Comment
Telegram routing
Group and Physical: route
configure
[Group and Physical: route]
route:
all telegrams are routed
configure:
The following parameters must
be set manually.
Physical telegrams
transmit all
block
[transmit all]
•Physical telegrams are all routed.
•Physical telegrams are all blocked.
Physical telegrams:
Repetition
if errors on main line
no
up to 3 repetitions
only one repetition
[only one repetition]
After main line transmission error (e.g. due to
missing receiver) Physical telegrams
•are not repeated.
•are repeated max. 3 times.
•are repeated once.
Group telegrams:
Repetition
if errors on main line
no
up to 3 repetitions
only one repetition
[only one repetition]
After main line transmission error (e.g. due to
missing receiver) Group telegrams
•are not repeated.
•are repeated max. 3 times.
•are repeated once.
Telegram confirmation
on main line
If routed
always
[always]
•Routed telegrams to the subline are
confirmed by an ACK on the main line.
•Each telegram on the mainline is confirmed
by an ACK.
Send confirmation on
own telegrams
yes
no
[yes]
•Telegrams sent out to the mainline are
confirmed by added ACK.
•No ACK confirmation.
Table 3: Subline Tab Parameter Settings
This manual suits for next models
1
Table of contents
Other EAE Controllers manuals
Popular Controllers manuals by other brands

Etatron
Etatron eSelect-CD1 Operating instructions and maintenance

iNels
iNels SA3-012M instructions

Shimaden
Shimaden FP23 Series Detailed instruction manual

Norac
Norac UC4+ Apache 1010 2005+ installation manual

Siemens
Siemens GDB 9E Series Mounting instructions

Agilent Technologies
Agilent Technologies ETC 60 user guide