
4
RVAC Fluid-insulated Vacuum Switchgear
InstallatIon, operatIon, and MaIntenance InstructIons MN285005EN March 2018
Installation procedure
WARNING
This equipment is not intended to protect human
life. Follow all locally approved procedures and safety
practices when installing or operating this equipment.
Failure to comply can result in death, severe personal
injury, and equipment damage. G102.1
1. Check the fluid level. Make sure the fluid in the
switchgear tank is at the proper level by checking the
fluid level indicator on the front plate. Two-sided units
have fluid level indicators on both source-side and
tap-side front plates. Make sure both are at the proper
level.
2. Test the fluid dielectric strength and moisture content.
If the switchgear has been stored for some time or
is being relocated, perform these tests on the fluid in
accordance with ASTM-approved testing procedures.
WARNING
This equipment relies on dielectric fluid to provide
electrical insulation between components.The dielectric
strength and moisture content of the fluid must be
checked on a regular basis, as part of the routine
maintenance inspection, to ensure that it is at or
above minimum dielectric requirements and below the
maximum moisture content. Use of this equipment
with dielectric fluid that does not meet requirements
can result in internal flashovers that will damage the
equipment and can result in death or serious injury. G107.3
NOTICE
The use of Envirotemp™ FR3™ dielectric fluid is limited to
a minimum operating temperature of 32 °F (0 °C). Failure
to comply can result in equipment misoperation. T374.0
a. On new equipment, the fluid must have a minimum
dielectric strength of 26 kV.
b. If the dielectric strength of the fluid is less than
26 kV, process or replace the fluid to restore its
dielectric strength to an acceptable minimum level.
c. Refer to the Fluid testing section of this manual for
service recommendations based on the moisture
content of the fluid.
d. For additional information on fluid specifications and
tests, refer to Reference Data TD280022EN and to
the Fluid testing section of this manual.
3. Check the nameplate ratings. Make sure the ratings on
the switchgear nameplate are correct for the planned
installation.
NOTICE
Equipment damage. Never place jacks, tackle or
other attachments under the unit for the purpose of
lifting. Failure to comply will result in damage to the
equipment. T240.0
NOTICE
Follow all locally approved safety practices when lifting
and mounting the equipment. Use the lifting lugs provided.
Lift the unit smoothly and do not allow the unit to shift.
Improper lifting can result in equipment damage. G106.2
4. Mount the switchgear on the concrete pad.
a. The switchgear must be installed on a level concrete
pad or structure that has been designed to support
the size and weight of the unit.
b. The switchgear must be hoisted only by the
recessed lifting provisions provided at the four
corners of the tank. Suitable lifting straps must be
used to prevent damage to the switchgear housing.
c. The switchgear must be anchored to the concrete
pad. Anchor the pad using the mounting cleats
provided or using other suitable mounting hardware.
WARNING
Hazardous voltage. Solidly ground all equipment. Failure
to comply can result in death, severe personal injury,
and equipment damage. T223.2
5. Ground the switchgear. Switchgear must be adequately
grounded. Install a permanent, low resistance
ground connection to the switchgear tank. Grounding
provisions are provided near the bottom of the tank.
CAUTION
Equipment misoperation. Always use compatible
fuses. Follow all locally approved operating practices
whenever changing fuses. Wet-well fuse assemblies
must be re-fused and operated in accordance with the
instructions provided by the fuse manufacturer. Failure
to install the proper fuse can result in switchgear
misoperation, equipment damage, and personal injury.
G260.0
6. Assemble and install fuses. If the switchgear is
equipped with fuses, be sure that the fuses are rated
correctly for the installation and that they are properly
installed. Further verify that the fuses are compatible
with the wetwell fuse holder(s) supplied with the
switchgear. Refer to Figure 5 to ascertain fuse/wetwell
fuse holder compatibility.
ote:N Fuses should be applied on solidly grounded wye
systems only. Consult factory for fuse application
on delta systems.
7. Make the high-voltage line connections.
a. Prior to making connections, make sure that the
source-side and tap-side cable elbows are correctly
identified and that the switchgear unit is oriented
correctly for the installation. The source leads must
connect to the source bushings of the unit, and the
tap leads must connect to tap bushings of the unit.