INTRODUCTION
Dehumidifiers remove moisture from the air that is circulating through the unit.
The resulting reduction of relative humidity helps prevent rust, rot, mould, mildew and
condensation within the room, or other enclosed spaces where the dehumidifier is used.
A dehumidifier consists of a motor-compressor unit, a refrigerant condenser, an air circulating
fan, a refrigerated surface, a means of collecting and disposing the condensed moisture and a
cabinet to house these components.
The fan draws air through the refrigerated surface and cools it below its dew point, removing
moisture which is collected and led away. The cool air then passes the hot condenser, where it is
reheated. With the addition of other radiated heat the air is discharged into the room at a higher
temperature but lower relative humidity than when the air entered the unit. Continuous
circulation of the room air through the dehumidifier unit gradually reduces the relative humidity
in the room.
The CD100 dehumidifier is a rugged reliable drying unit designed to operate effectively over a
broad range of temperature and humidity conditions. A powerful and reliable active hot gas
defrost system, controlled by an electronic timer, guarantees positive de-icing and thereby
optimising operation at low temperatures.
The unit incorporates a welded steel chassis and is finished in vinyl coated steel covers for
resilience to damage caused by rough handling.

CD100 OWNERS MANUAL
Drawing No. :- TPC112
Issue :- 1
Date :- 20/06/03
SPECIFICATIONS
MODEL: CD100
HEIGHT: 400mm
WIDTH: 900mm
DEPTH: 500mm
WEIGHT: 50 Kg
AIRFLOW: 510 M3/hr
POWER SUPPLY: UK-220V/240V, 1 ph, 50Hz/60Hz
USA-110V/120V, 1 ph, 50Hz/60Hz
POWER 1.2kW (max)
FINISH: Vinyl coated steel
REFRIGERANT TYPE/QTY: R407c (540g)
MOBILITY: Choice of aids – wheels or skid handles

CD100 OWNERS MANUAL
Drawing No. :- TPC112
Issue :- 1
Date :- 20/06/03
INSTALATION
POSITIONING:
Position the dehumidifier unit in the center of the room to be conditioned if at all possible.
However if a damp patch is particularly apparent the outlet grille should be pointed towards it.
NOTE: Both inlet grille and outlet grille of the dehumidifier unit must have clear space around
them and not be obstructed in anyway.
WIRING:
Connect the power mains cable to a 13 Amp power supply. As follows:-
Brown Live
Blue Neutral
Green/Yellow Earth (ground)
DRAINAGE:
Connect a 15mm inside diameter hose to the water outlet pipe. Secure the hose using a worm
drive clip. The hose should at no point be raised higher than the outlet pipe. Failure to observe
this requirement will result in flooding of the dehumidifier unit.
The CD100 may also be fitted with a water pump (optional), which is capable of discharging the
condensate water 30ft away from the unit. The water can, therefore, be discharged into a drain
some distance away.

CD100 OWNERS MANUAL
Drawing No. :- TPC112
Issue :- 1
Date :- 20/06/03
OPERATION
The operation of the dehumidifier is to remove moisture from the air by having it condense on
the cold tubes of the evaporator coil. The air then passes over the hot condenser coil and returns
to the conditioned space slightly warmer and dryer than when it entered the dehumidifier unit.
To concentrate drying all doors and windows should be kept closed.
Test for Correct Operation
WARNING: DO NOT RUN THE MACHINE WITHOUT THE COVERS IN
PLACE FOR ANY LONGER THAN NECESSARY. DO NOT
REMOVE/REPLACE THE COVERS WITH THE POWER ON.
Remove the cover by releasing the retaining bolts and follow the test procedure laid out below:-
1. Set the adjustable humidistat to maximum.
2. Switch the machine to the on position, this will result in the compressor starting to run and
the fan blade starting to rotate.
3. When the compressor has been running for 20 minutes the coils located above the drain tray
will be evenly coated in frost. (If the ambient temperature is above 25ºC the coils will be
covered in water.
4. After the machine has been running for approximately 50 minutes the unit will automatically
enter into defrost. The defrost cycle lasts for approximately 3 minutes, this will result in the
frost on the coils melting and dripping into the drainage tray.
5. After the defrost has finished the machine will return to normal operation.
6. Ensure the condensate drains away from the machine.
Setting the Adjustable Humidistat
The position of the humidistat depends on the application the CD100 is being used for and the
conditions within the area to be dried. The worse the conditions within the area then the higher
the humidistat should be set (i.e. the machine will run for a longer period of time to ensure all the
moisture is reduced sufficiently). As a rough guide the humidistat wants to be set at
approximately 50% for factories and warehouses, and for basements or de-flooding then the
humidistat should be set to approximately 100%.

CD100 OWNERS MANUAL
Drawing No. :- TPC112
Issue :- 1
Date :- 20/06/03
Optional Discharge Pump
This is an optional extra as requested at purchase. The pump works automatically and
periodically pumps away collected moisture to a drain or container. The pump is capable of
discharging water to a vertical height of 30ft.
Indicator Panel
The CD100 is fitted with an indicator lamp to show when power is available and the unit is
switched on, if this does not appear to be functioning correctly then refer to the repairs section.
Warnings.
•Due to the high pressures within the refrigeration circuit, under no circumstances must direct
heat be applied to the evaporator coil in an attempt to remove the build up of ice.
•No attempt should be made to cut open any part of the refrigeration circuit due to high
pressures and gas involved.
•If the unit is switched off at the mains power supply for any reason, the unit must be allowed
to stand at rest for at least three minutes before restarting. Failure to do so may cause the unit
to blow the fuses owing to the compressor due to there being a refrigerant imbalance.

CD100 OWNERS MANUAL
Drawing No. :- TPC112
Issue :- 1
Date :- 20/06/03
ROUTINE MAINTENANCE
WARNING: ENSURE THAT THE POWER CORD TO THE MACHINE
HAS BEEN DISCONNECTED BEFORE CARRYING OUT
ROUTINE MAINTENANCE ON ITEMS 1, 2, 4, 5, AND 6.
To ensure continued full efficiency of the dehumidifier, maintenance procedures should be
performed as follows:
Removal of the cover is achieved by means of four screws at the sides of the unit at base level.
With the cover removed all maintenance can be carried out.
1. Clean the surface of the evaporator and condenser coils by blowing the dirt out from
behind the fins with compressed air. Hold the nozzle of the air hose away from the
coil (approx 6”) to avoid damaging the fins. Alternatively, vacuum clean the coils.
WARNING: DO NOT STEAM CLEAN REFRIGERATION COILS.
2. Check that the fan is firmly secured to the motor shaft and that the fan rotates freely.
THE FAN IS SEALED FOR LIFE AND DOES NOT NEED LUBRICATING.
3. To check the refrigerant charge, run the unit for 20 minutes (with humidistat set to
maximum) and briefly remove the cover. The evaporator coil should be evenly frost
coated across its surface. At temperatures above 25°C, the coil may be covered with
droplets of water rather than frost. Partial frosting accompanied by frosting of the
thin capillary tubes, indicates loss of refrigerant gas or low charge.
4. Check all wiring connections.
IF ANY OF THE PRECEDING PROBLEMS OCCUR,CONTACT THE EBAC SERVICE CENTER PRIOR TO
CONTINUED OPERATION OF THE UNIT TO PREVENT PERMANENT DAMAGE.

CD100 OWNERS MANUAL
Drawing No. :- TPC112
Issue :- 1
Date :- 20/06/03
REPAIRS
1. Should an electrical component fail, consult the Factory Service Center to obtain the
correct replacement part.
2. If refrigerant gas is lost from the machine, it will be necessary to use a refrigeration
technician to correct the fault. Contact the Factory Service Center prior to initiating
this action.
Any competent refrigeration technician will be able to service the equipment. The
following procedure must be used:
a. The source of the leak must be determined and corrected.
b. The machine should be thoroughly evacuated before recharging.
c. The unit must be recharged with refrigerant measured accurately by weight.
d. For evacuation and recharging of the machine, use the crimped and brazed
charging stub attached to the side of the refrigerant compressor.
The charging stub should be crimped and rebrazed after servicing. NEVER allow
permanent service valves to be fitted to any part of the circuit. Service valves
may leak causing further loss of refrigerant gas.
3. The refrigerant compressor fitted to the dehumidifier is a durable unit that should
give many years of service. Compressor failure can result from the machine losing its
refrigerant gas. The compressor can be replaced by a competent refrigeration
technician.
Failure of the compressor can be confirmed by the following procedure:
a. Establish that power is present at the compressor terminals using a voltmeter.
b. With the power disconnected, check the continuity of the internal winding by
using meter across the compressor terminals. An open circuit indicates that the
compressor should be replaced.
c. Check that the compressor is not grounded by establishing that a circuit does not
exist between the compressor terminals and the shell of the compressor.

CD100 OWNERS MANUAL
Drawing No. :- TPC112
Issue :- 1
Date :- 20/06/03
TROUBLESHOOTING
SYMPTOM CAUSE REMEDY
Little or no airflow
1. Loose fan on shaft
2. Fan motor burnt out
3. Dirty refrigeration coils
4. Loose electrical wiring
5. Fuse blown
1. Tighten fan
2. Replace the fan motor
3. See Routine Maintenance Section
4. Check the wiring diagram to find
fault and repair
5. Replace the fuse or reset the circuit
breaker
Little or no water extraction
1. Insufficient air flow
2. Compressor fault
3. Loss of refrigerant gas
1. Check all of the above
2. Contact the Factory Service Center
3. Contact the Factory Service Center
Little or no defrost when
required
1. Faulty Timer
2. Faulty bypass timer
1. Contact the Factory Service Center
2. Contact the Factory Service Center
Unit vibrates excessively 1. Loose compressor mounts
2. Damaged fan
1. Tighten nuts on compressor mounts
2. Replace with a new fan
Water flooding inside
machine
1. Faulty water pump
2. Sticking float switch
3. Drain tray blocked
1. Replace water pump
2. Remove obstruction
3. Remove obstruction