manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. DanVex
  6. •
  7. Dehumidifier
  8. •
  9. DanVex DEH-290h User manual

DanVex DEH-290h User manual

DanVex DEH-290h
Dehumidifier
Operation manual
R
www.danvex.fi
1
R
www.danvex.fi
Operation instructions
Please read these instructions carefully before installing / operating this unit!
Our warranty becomes null and void in case of the unit improper operation, installation or
maintenance or in case of the supplied unit modification without prior consent from our part.
Design is subject to changes!
2
Air dehumidification
The processes that take place during dehumidification are based on physical laws. We will try
to illustrate them here in a simplified form to give you a general idea of dehumidification
principles.
Attention!!! These units cannot be used for air cooling!!!
Use of DanVex dehumidifier
◊ Despite of windows and doors insulation quality, damp and moisture can penetrate even
through thick concrete walls.
◊ It can take 1-2 months for the water used for construction (concrete works, whitewashing,
plasterworks etc.) to dry out.
◊ The moisture that has penetrated masonry following high water or flooding is released very
slowly.
◊ One example of moisture-related issues is damping of materials in storage.
The moisture escaping from building elements or materials by evaporation is absorbed by the
ambient air. Thus, this increases the air humidity and ultimately results in corrosion, mould,
rot, peeling of paint coatings and other unwanted damages.
R
www.danvex.fi
The below diagram shows an example of metal corrosion rate at different air humidity levels.
3
As you can see the rate of corrosion is insignificant at the relative humidity below 50%, and it
can be disregarded at the relative humidity below 40%. But at the relative humidity above
60% the rate of corrosion increases considerably. This moisture damage example applies
also to many other materials, such as powders, packaging, wood, electric equipment or elec-
tronic devices.
There are two different ways of buildings drying out:
1. By heating with further air exchange:
The ambient air is heated to absorb the moisture and then it is discharged to the atmosphere.
However the total energy output is lost during the moist air discharging to the atmosphere.
2. By the air dehumidification:
The moist air in an enclosed room is continuously dehumidified by the condensation principle.
In terms of energy consumption the air dehumidification has one essential advantage:
The energy expenditure requirements are limited by the air volume in the existing room only.
The mechanical heat released during the dehumidification process slightly increases the air
temperature in the room.
When properly used the dehumidifier consumes about 25% of the energy that would be
needed for the „heating and ventilation".
020 40 60 80 100
30
60
90
120
0
Air relative humidity, %
Corrosion time
R
www.danvex.fi 4
The relative air humidity
The ambient air is a gas mixture that always contains a certain amount of water in the form of
water vapor.
This water percentage is expressed in g per kg of dry air (absolute water content).
3
1 m of dry air weighs about 1,2 kg at 20° C.
Depending on the temperature each kg of the air is only able to absorb a certain amount of
water vapor. When this absorptive capacity is reached the air becomes "saturated" and the
relative humidity becomes 100%.
The relative humidity is understood to be the ratio between the water vapor percent currently contained
in the air and the maximum water vapor percent at the same temperature.
The ability of air to absorb water vapor increases with temperature increasing. This means that the
maximum (= absolute) water content increases with temperature increasing.
Water vapor condensation
The maximum water vapor volume that can be absorbed increases when the air is heated,
but the water vapor content remains however the same and this results in relative humidity
reduction.
In contrast, when the air is cooled, the maximum water vapor volume that can be absorbed
continuously reduces, the water vapor volume contained in the air remains however the same
and the relative humidity increases.
If the air temperature falling continues the capacity to absorb the water vapor volume is
reduced until it is equal to the water vapor content. This temperature is called the dew-point
temperature.
When the air is cooled below the dew-point temperature, the water vapor content becomes
higher than the maximum possible water vapor content.
Water vapor displacement starts.
The vapor condenses to water. Thus the moisture is removed from the air.
-5
+10
+15
+20
+25
+30
1,3
3,8
5,1
6,9
9,2
12,9
1,9
5,6
7,7
10,4
13,8
18,2
2,6
7,5
10,2
13,8
18,4
24,3
3,3
9,4
12,8
17,3
23,0
30,3
40% 60% 80% 100%
3
Water vapor content in g/m in the air at the
humidity of
Temp. °C
R
www.danvex.fi
A misted window glass in winter or a misted bottle with a cold drink are common
examples of condensing.
The higher the relative air humidity the higher is the dew-point temperature,
and thus it is easier to fall below the dew-point temperature.
Drying materials
Building materials/structures can absorb considerable amounts of water, e.g. bricks can
absorb 90-190 l/m3, heavy concrete can absorb 140-190 l/m3, sand-lime bricks can absorb
180-270 l/m3. Wet materials such as masonry are dried as follows:
The moisture contained in the material moves from within the material
to its surface
Evaporation takes place on the surface = water vapor is absorbed by
the ambient air
The air enriched with water vapor continuously circulates through the
dehumidifier. It is dehumidified and leaves the unit being slightly heated
to absorb the moisture again
In this way, the moisture content in the material is continuously reduced
and the material dries
The produced condensate is collected in the unit and discharged
The air flow is cooled on the way through /via the evaporator-condenser
till its temperature is below the dew point. Water vapor condenses, it is
collected in a condensate trap and discharged.
5
Heat of condensation
The energy transferred from the condenser to the air consists of:
The heat earlier transferred from the evaporator
Real electrical power.
The heat of condensation released through the condensation of water vapor.
Evaporator Condenser
Air
temperature
Air direction
Humidity
time
R
www.danvex.fi 6
When liquid turns into a gaseous state, the energy should flow in reverse. This energy is
called the heat of evaporation. It does not cause any rise of temperature, it is only necessary
for the change from a liquid to a gaseous state. Vice versa, the energy is released when gas
turns into liquid, such energy is called heat of condensation.
The heat generated at condensation and evaporation and is identical.
For water this is 2250kJ/kg (4.18kJ = 1kcal)
This shows that a relatively large amount of energy is released in the process of water vapor
condensation.
If the moisture to be condensed is not generated at evaporation in the room but is introduced
from outside, e.g. via ventilation, the heat of condensation released in the process will be
used for the room heating.
If it is required to dry materials or rooms the heat energy recirculates, i.e. it is consumed
during evaporation and is released during condensation. A large amount of heat energy is
generated at the supplied air dehumidification process, which is expressed as a rise of
temperature.
Normally the time necessary for drying does not depend only on the unit capacity, but is de-
termined by the rate at which the material or the building elements release the moisture they
contain.
Safety Instructions
Prior to delivery the units are subject to comprehensive testing of their materials, functional
capabilities and quality.
However hazards can arise if the unit is operated by untrained persons unfamiliar with its
operation principles or in case the unit is not used for the intended purpose. The following
safety instructions must be observed:
◊ It is prohibited to install or operate the units in the locations subject to explosion hazard.
◊ It is prohibited to install or operate the units in the locations with oil, sulphur, chlorine or salt
containing atmospheres.
◊ The units must be installed upright.
◊ It is prohibited to use a direct jet of water for the unit washing.
◊ It is prohibited to cover the air inlet and outlet holes.
◊ The intake side of the unit must be free of dirt and loose objects.
◊ It is prohibited to insert objects in the unit.
◊ It is prohibited to cover or transport the unit during operation.
◊ All electric cables outside the unit must be protected against damage (e.g. from animals
etc.).
◊ It is necessary to insure that all cables meet the requirements for capacity, length and
purpose.
◊ The unit must only be transported in vertical condition. The condensate containers must be
drained prior to each transportation of the unit.
◊ It is prohibited to use the unit for purposes other than intended or not specified in this
operations instructions.
In case the requirements are not observed our company disclaims any liability and out
warranty becomes null and void.
R
www.danvex.fi
Only authorized personnel is permitted to perform works on cooling and
electrical system!
Unit description
The unit is designed for automated, versatile and trouble-free air dehumidification. Due to its
compact dimensions it is easy to transport and operate.
The unit operates on condensation principle. It is equipped with a closed loop cooling system,
low noise and low maintenance fan and with a power cable with a plug.
The unit's control panel is equipped with a LCD display used for the system functional checks.
A fully automated unit control system, a trouble-free regulated humidistat, an integrated
overflow system as well as flexible hose connection for direct condensation discharge assure
fail safe and long-term operation of the unit.
The unit complies with the fundamental safety and health requirements of the existing EU
regulations.
The unit is easy and safe to operate.
Unit location
The unit is operated in the buildings where dry air is necessary to prevent significant financial
losses (for example, due to mould formation).
The unit is mainly used for drying and dehumidification of:
◊ Common rooms, bedrooms, bathrooms and cellar rooms.
◊ Kitchens, summer cottages, caravans.
Functions
The unit operates on condensation principle.
The fan intakes moist surrounding air into the units rear side through the air filter, evaporator
and condenser located behind the evaporator.
Heat is extracted at the cold evaporator. The air is cooled to below the dew point. The water
vapor contained in the room air deposits as condensate or frost on the evaporator fins.
7
R
www.danvex.fi 8
Dried and cooled air is heated in the condenser (radiator) again. Then it is discharged to
outside, the air temperature is about 5 degrees higher than the room temperature.
The dried air is mixed with surrounding air again. The relative humidity gradually drops to the
required RH value due to continuous outside air circulation through the unit.
Depending on the room temperature and relative humidity the condensed water can drip
continuously or only during certain defrosting stages into a condensate tank through
integrated drain channels.
When the tank is full triple acoustic signal sounds and the units switches off.
The signal will be repeated every 5 minutes, E4 will be shown on the display till the tank is not
drained. The unit will switch on again with 3 minutes delay.
For uncontrolled continuous operation of the unit it is required to drain the condensate using
an external water hose.
Installation
For optimum, economical and safe unit operation the following instructions must be followed:
◊ The unit must be installed securely upright to ensure unhindered condensate discharge into
the condensate tray.
◊ If possible the unit must be installed in the centre of the room so that optimal air circulation
is ensured.
◊ There should be 50 cm distance from the unit to the walls.
◊ It must be ensured that the air is able to be sucked in freely at the rear of the unit and to be
discharged through the upper part of the air throttle.
◊ It is prohibited to locate the unit in close proximity to radiators and other heat sources.
◊ The room to be dried or dehumidified must be closed to prevent the air entering from
neighbor rooms and from outside.
◊ Windows and doors must be closed to prevent free air exchange between the room and
ambient atmosphere.
Fan
Dried air
Compressor
Moist air
Condensation
tray
Condenser
Evaporator
Outlet
drain port
R
www.danvex.fi
◊ If the unit is used in dust-laden environments it is necessary to take appropriate
maintenance measures specially adapted to the particular operation conditions.
See the chapter «Maintenance and service».
◊ It is possible to increase the air circulation by locating the unit at a height about 1 meter
from the floor.
Important information on electrical connections
◊ Electric wiring of the unit should be done in accordance with DIN VDE 0100, Part 704 for
electric current supply sources equipped with automatic circuit-breakers.
◊ If the unit is installed in humid premises such as bathrooms or kitchens it should be
equipped with proper automatic circuit-breakers at the buyer's expense.
Commissioning
Prior to commissioning works or to comply with local requirements it is necessary to check air
intake openings and outlet openings to be sure that they are free from foreign matters. Intake
filters condition should be checked as well.
The following instructions are to be observed:
◊ Extension cables should be of proper cross-section.
◊ It is allowed to use extension cables if they are fully disentangled or stretched!
◊ It is not allowed to pull the unit by the power cord.
◊ Upon actuation the unit operates in fully-automatic mode till it is switched off by the
regulator
when the condensate tank is full.
◊ The condensate tank should be properly installed.
Otherwise the unit will not operate!
9
The window
should be
closed
The door
should be
closed
Minimum distance = 0.5 m
R
www.danvex.fi 10
◊ The unit is equipped with a protection device that prevents the compressor from switching
on at restart immediately after the unit switching off, thus preventing the compressor damage
The compressor switches on after 3 minutes only.
We do not ensure the efficient operation of the unit if the room temperature is below 10 °C
and if the relative humidity is below 40 %.
Dehumidifier design
Control panel and LCD display:
290h model
Transportation
wheels Power cord
Rear cover
Air filter
Drain hole
Carbon filter
Air outlet
Tank
Control panel
TiO2 system
Handle
Dehumidification mode
Clothes drying mode
Increase
Decrease
Timer
Humidity/temperature indicator
High Low
speed Timer
Mode button
ON/OFF
Speed button
Defrosting mode
Timer indicator
R
www.danvex.fi
Start up and operation
1) Use ON/OFF button to switch the unit on/off.
2) Select the desired dehumidification mode using the MODE CHOOSE button. The
modes shifting sequence is as follows: Dehumidification - Clothes drying.
3) In the "Dehumidification" mode set the required humidity in the room using UP/DOWN
buttons. It is possible to set the humidity within the range from 30% to 90%.
4) Use the FAN SPEED CHOOSE button to regulate the fan speed (low or high speed).
5) In the "Clothes drying" mode humidity and fan speed parameters are not set.
6) Use the TIMER SETTING button to set the switching off timer (the unit switch off time
can be set from 30 minutes to 12 hours).
Service and Maintenance
Long-life and trouble-free performance is based upon regular maintenance and watch
service.
Nevertheless, complete equipment inspection should be carried out annually, it is also
required to perform complete cleaning of the equipment after any long idle periods. Frequent
maintenance is not required since all moving parts of the equipment are provided with
permanent lubrication. The cooling system is of a closed and low-maintenance type. The
cooling system maintenance should be performed by an authorized service center only.
Please, make sure the power plug is disconnected from the mains socket prior
to any maintenance jobs!
◊ Do not allow dust or other matters to build up on the machine.
◊ It is allowed to clean the unit with dry or slightly wet clothes.
It is forbidden to clean the unit using a direct water jet.
◊ Do not use any abrasive detergents or solvent-containing cleansers; use proper cleansers
and detergents only even if the unit is heavily polluted.
◊ It is required to check the air filter condition regularly.
Clean and replace it as appropriate.
Only authorized personnel is permitted to perform works on cooling and
electrical system.
11
R
www.danvex.fi 12
Troubleshooting
The equipment was repeatedly tested by its manufacturer to ensure its normal operation.
Nevertheless, should a trouble happen, please follow the below guidelines:
Unit fails to start:
◊ Check the power cable connection.
230V / 1~ / 50 Hz
◊ Check the fuses installed by the manufacturer.
◊ Check the power plug condition.
◊ Check the humidistat settings.
Relative humidity in the room should be higher than the set-up humidity level.
The unit starts with no condensation:
◊ Check the indoor temperature (the lower the temperature is the low the unit efficiency).
Operational temperature range should be from +5 °C to +32 °C.
◊ Check the humidity level
Minimum relative humidity level is 40 %.
◊ Make sure air intake filter is clean.
Clean and replace as appropriate.
◊ Check heat-exchanger fins for contamination.
The equipment panels should be opened to carry out the inspection; these procedures
can be performed in an authorized service center only.
◊ "Е4" is displayed on LCD = it is required to drain condensate.
Please, make sure the power plug is disconnected from the mains socket prior
to any maintenance jobs!
The unit operates with noise, vibrates or sweats:
◊ Make sure the equipment is installed on even surface and in upright position.
◊ Make sure the condensate tray and adapter are clean.
The equipment panels should be opened to carry out the inspection; these procedures
can be performed in an authorized service center only.
Should the equipment not operate properly upon all the mentioned tests are done, please call
the authorized service center for assistance.
Only authorized personnel is permitted to perform works on cooling and
electrical system.
R
www.danvex.fi
13
Model
Operational temperature range
Operational humidity range
Dehumidification (at 30 °С / 80% RH)
Air capacity
Cooling agent
Power
Frequency
Current
Rated consumption, max
Sound pressure, L 1m
pA
Depth
Width
Height
Gross weight
°С
% RH
l/day
m3/hour
-
V
Hz
A
kW
dB (A)
mm
mm
mm
kg
DEH-290H
+5..+32
30-100
29
190
R134A
1~230
50
1,6
0,36
42
320
245
605
22
Specifications
Warranty obligations
DanVex warrants that all the equipment parts will answer the technical requirements for 12
months from the date of delivery (warranty period).
The warranty does not cover wearable parts such as filters. The warranty covers the defects in
workmanship and materials.
During the warranty period DanVex repairs and replaces the part having a defect of material or an
manufacturing error.
DanVex completely fulfills its warranty obligations when it supplies the Customer a repaired or a
spare part.
Parts repair or replacement does not result in the warranty period extension.
The parts and components replaced under the warranty belong to DanVex.
DanVex or its distributor upon DanVex request has a right to inspect the defective parts and to
check the correctness of the warranty claim.
Warranty repair execution conditions:
The damage occurred during the equipment normal operation. All recommendations and
instructions of the manufacturer concerning the equipment installation, operation and
maintenance were observed. Only original parts and materials were used for the equipment
maintenance and repair.
R
www.danvex.fi 14

Other DanVex Dehumidifier manuals

DanVex DEH-3K User manual

DanVex

DanVex DEH-3K User manual

DanVex DEH-1200P User manual

DanVex

DanVex DEH-1200P User manual

DanVex DEH-1700P User manual

DanVex

DanVex DEH-1700P User manual

DanVex AD-550 User manual

DanVex

DanVex AD-550 User manual

DanVex AD-200 User manual

DanVex

DanVex AD-200 User manual

DanVex DEH-600wp User manual

DanVex

DanVex DEH-600wp User manual

DanVex AD-10000 User manual

DanVex

DanVex AD-10000 User manual

DanVex AD-200 User manual

DanVex

DanVex AD-200 User manual

DanVex DEH-400P User manual

DanVex

DanVex DEH-400P User manual

DanVex DEH-1600i User manual

DanVex

DanVex DEH-1600i User manual

DanVex AD-3000 User manual

DanVex

DanVex AD-3000 User manual

DanVex AD-800 Operating instructions

DanVex

DanVex AD-800 Operating instructions

DanVex DEH-900i User manual

DanVex

DanVex DEH-900i User manual

DanVex DEH-500i User manual

DanVex

DanVex DEH-500i User manual

DanVex AD-400 User manual

DanVex

DanVex AD-400 User manual

DanVex DEH-600P User manual

DanVex

DanVex DEH-600P User manual

DanVex DEH-1700wp User manual

DanVex

DanVex DEH-1700wp User manual

DanVex DD Series User manual

DanVex

DanVex DD Series User manual

Popular Dehumidifier manuals by other brands

Abestorm SLGR Elite user manual

Abestorm

Abestorm SLGR Elite user manual

AeonAir RDH60EB user manual

AeonAir

AeonAir RDH60EB user manual

Oceanic OCEADH12LPA Instruction booklet

Oceanic

Oceanic OCEADH12LPA Instruction booklet

Toshiba TDDP2213ES2 user manual

Toshiba

Toshiba TDDP2213ES2 user manual

Heat Controller Comfort-Aire BHD-301-C Service manual

Heat Controller

Heat Controller Comfort-Aire BHD-301-C Service manual

Phoenix DryMAX XL quick start guide

Phoenix

Phoenix DryMAX XL quick start guide

Meaco 25L instruction manual

Meaco

Meaco 25L instruction manual

Dantherm CDP 35T Service manual

Dantherm

Dantherm CDP 35T Service manual

Sensu Air TV80006 operating instructions

Sensu Air

Sensu Air TV80006 operating instructions

VEAB Heat Tech LAF 31 manual

VEAB Heat Tech

VEAB Heat Tech LAF 31 manual

Lenoxx DH100 user manual

Lenoxx

Lenoxx DH100 user manual

WC Wood HED36B Specifications

WC Wood

WC Wood HED36B Specifications

Fakir LE 56 Instructions for use

Fakir

Fakir LE 56 Instructions for use

INVENTOR C2-10L user manual

INVENTOR

INVENTOR C2-10L user manual

Frigidaire LAD504DUL use & care

Frigidaire

Frigidaire LAD504DUL use & care

MICROWELL DRY 800 METAL Installation and user manual

MICROWELL

MICROWELL DRY 800 METAL Installation and user manual

Condair DC Series Installation and operation manual

Condair

Condair DC Series Installation and operation manual

Mycond ROOMER Eco 25 user manual

Mycond

Mycond ROOMER Eco 25 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.