manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. EDI
  6. •
  7. Test Equipment
  8. •
  9. EDI DA-300 User manual

EDI DA-300 User manual

THIS MANUAL CONTAINS TECHNICAL INFORMATION FOR
THE DA-300®IO Tester
REVISION: June 19, 2017
Version 1.0
888-0300-002
DA-300®IO Tester
Operations Manual
THE DA-300®IO Tester IS DESIGNED AND MANUFACTURED IN THE USA BY
EBERLE DESIGN INC., PHOENIX, ARIZONA
EDI IS CERTIFIED TO ISO 9001:2008 QUALITY SYSTEMS STANDARDS.
DA-300 IS A REGISTERED TRADEMARK OF EBERLE DESIGN INC. INFORMATION
CONTAINED HEREIN IS PROPRIETARY TECHNICAL INFORMATION OF EBERLE
DESIGN INC. PUBLICATION, REPRODUCTION OR USE IN WHOLE OR PART IS NOT
PERMITTED EXCEPT UNDER TERMS AGREED UPON IN WRITING.
© COPYRIGHT 2017 EDI
Table of Contents
Section 1 GENERAL ......................................................................................................... 1
Section 2 SPECIFICATIONS............................................................................................. 2
Section 3 PROCEDURES ................................................................................................. 3
DA-300®IO TESTER
Operations Manual
Eberle Design Inc. Page 1
Section 1
GENERAL
Overview
The Data Aggregator DA-300®provides the ability to monitor several DC and AC analog
signals as well as detector outputs from a traffic cabinet. The DA-300®also generates relay
outputs. Production testing and demonstration of a DA-300®unit may occur outside a
traffic cabinet and thus a bench tool capable of simulating these inputs to and receive the
outputs from a DA-300®unit is needed.
The DA-300®IO tester (model DIOT) was created to fulfill this need. It provides user
adjustable DC and AC voltages to a DA-300®simulating real inputs; and it receives the DA-
300®relay outputs displaying the contact statuses.
The DIOT supports a simple intuitive user interface consisting of 36 labeled toggle switches
(one for each DA input), Two front panel rotating knobs (one for DC adjust and one for AC
adjust) and 8 LEDs (one for each relay output). The adjustable AC and DC voltages are
read by two different meters.
•Labeled toggle switches apply or remove either AC or DC voltages from an AC or
DC input respectively.
•Other labeled toggle switches simulate discrete detector input states.
•The left top panel knob when rotated clockwise increases the DC voltage, while
rotating it counterclockwise, the DC voltage drops.
•The right top panel knob when rotated clockwise lowers the AC voltage, while
rotating counterclockwise raises the AC voltage.
•The front panel toggle switch labeled PWR, turns the tester on or off, when in the
“off” position all AC and DC voltages are removed from the inputs to a connected
DA-300®regardless of the status of their toggle switches. As a safety feature, if
the DIOT is still plugged in but turned off, the AC voltage will still be displayed.
DA-300®IO TESTER
Operations Manual
Eberle Design Inc. Page 2
Section 2
SPECIFICATIONS
(Note: An output channel of a tester is an input to the DA-300®)
Input Voltage: 80 to 145 VAC
Output Power DC Voltage: 24VDC @ 1.25 A
Output Adjustable DC Voltage: 0 to 24VDC @ 50 mA per channel
Output Adjustable AC Voltage: 70 to 112 VAC @ 100 mA per channel
Digital Reference Voltage: 22 to 24VDC @ 50 mA per channel
Variable DC Output Channels: 8
Variable AC Output Channels: 8
Simulated Detector Input Channels: 16
DA-300®Interface: One to One Harnesses with header connectors at
both ends.
DA-300®IO TESTER
Operations Manual
Eberle Design Inc. Page 3
Section 3
PROCEDURES
SETUP:
1. Verify the harnesses are connected securely to the DA-300®under test and the DA-
300®IO tester. The harnesses are keyed to go into only their respective ports on both
the IO tester and DA-300®.
2. Verify all top panel labeled switches are off.
3. Turn IO Tester on by front panel ON/OFF toggle switch.
A. Apply an AC or DC voltage to a single DC or AC Analog input of DA unit
under test.
1. Select and flip the toggle switch labeled for the required Analog Input of the
DA-300®under test.
2. If a DC Analog channel is to be tested, adjust the DC voltage displayed by
top meter to the required start value by rotating the front panel left knob.
Increase voltage by rotating knob clockwise; and decrease DC voltage by
rotating it counter clockwise.
3. If an AC Analog channel is to be tested, adjust the AC voltage displayed by
bottom larger meter to the required start value by rotating the front panel
right knob. Increase voltage by rotating knob counter clockwise; and
decrease DC voltage by rotating it clockwise.
4. Freely adjust the DC or AC voltages as required by the test for this DA-300®
input channel.
5. When the test for this channel is complete, flip the toggle switch of step 1
back down.
B. Apply simultaneous AC or DC voltages to multiple DC or AC Analog inputs
of DA-300®unit under test.
1. Select and flip the toggle switches labeled for the required Analog Inputs of
the DA-300®under to be tested.
2. If DC Analog channels are to be tested, adjust the DC voltage displayed by
top meter to the required start value by rotating the front panel left knob.
Increase voltage by rotating knob clockwise; and decrease DC voltage by
rotating it counter clockwise. (All DC channels selected in step 1 will receive
the same adjusted DC voltage.)
3. If AC Analog channels are to be tested, adjust the AC voltage displayed by
bottom larger meter to the required start value by rotating the front panel
right knob. Increase voltage by rotating knob counter clockwise; and
decrease DC voltage by rotating it clockwise. (all channels selected in step
1 will receive the same adjusted AC voltage.)
4. Freely adjust the DC or AC voltages as required by the test for the DA-300®
input channels undergoing testing.
5. When the test for this input channel is complete, flip the toggle switches of
step 1 back down.
DA-300®IO TESTER
Operations Manual
Eberle Design Inc. Page 4
C. Simulating a Detector Input
1. There are 16 detector toggle switches labeled DET1 through DET16.
2. When a detector toggle switch on the IO Tester is pushed up, the IO Tester
simulates that particular channel as a turned-on detector output or “call” to
the connected DA unit.
3. When the detector toggle switch is pushed down, the IO Tester simulates
that particular channel as a turned-off detector output to the connected DA-
300®unit.
4. All detector channels can be turned on or off at the same time or any
combination of on and off as required by the specific test or demonstration.
16 Detector Toggle Switches

Other EDI Test Equipment manuals

EDI T3D User manual

EDI

EDI T3D User manual

EDI DSTS-5A User manual

EDI

EDI DSTS-5A User manual

EDI CTT-2 User manual

EDI

EDI CTT-2 User manual

Popular Test Equipment manuals by other brands

Fluke HART 744 user manual

Fluke

Fluke HART 744 user manual

Anritsu MT9812B Operation manual

Anritsu

Anritsu MT9812B Operation manual

JONARD TOOLS TEP-200 instruction manual

JONARD TOOLS

JONARD TOOLS TEP-200 instruction manual

Viavi FIT-82P03 quick start guide

Viavi

Viavi FIT-82P03 quick start guide

Keysight Technologies N5224AU-401 Installation note

Keysight Technologies

Keysight Technologies N5224AU-401 Installation note

Tektronix 454A Operator's handbook

Tektronix

Tektronix 454A Operator's handbook

Hioki 3237 instruction manual

Hioki

Hioki 3237 instruction manual

SKF LAGD 1000 series Instructions for use

SKF

SKF LAGD 1000 series Instructions for use

SphingoTec Nexus IB10 Quick user guide

SphingoTec

SphingoTec Nexus IB10 Quick user guide

Getinge ISOTEST user manual

Getinge

Getinge ISOTEST user manual

Akku Vision TEST TOWER quick start guide

Akku Vision

Akku Vision TEST TOWER quick start guide

Lindy 43058 user manual

Lindy

Lindy 43058 user manual

Krohn-Hite 526 operating manual

Krohn-Hite

Krohn-Hite 526 operating manual

JBM 53536 instruction manual

JBM

JBM 53536 instruction manual

WIKA CalibratorUnit CPU6000 Series operating instructions

WIKA

WIKA CalibratorUnit CPU6000 Series operating instructions

Aventics Essential-Test-Box operating manual

Aventics

Aventics Essential-Test-Box operating manual

Keithley System SourceMeter 2602B quick start guide

Keithley

Keithley System SourceMeter 2602B quick start guide

EXFO Power Blazer user guide

EXFO

EXFO Power Blazer user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.