manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Edwards
  6. •
  7. Security Sensor
  8. •
  9. Edwards SIGA-PHDB Assembly instructions

Edwards SIGA-PHDB Assembly instructions

© 2018 United Technologies Corporation 1 / 2 P/N 3102363-EN • REV 004 • ISS 16FEB18
SIGA-PHD(B) Intelligent
Multisensor Photo-Heat
Detector Installation Sheet
Description
The Signature Series SIGA-PHD(B) Intelligent Multisensor Photo-Heat
Detector is an intelligent device that contains a photoelectric smoke
sensor and a rate-of-rise heat sensor with a fixed temperature setting.
The detector analyzes the data from both sensing devices and
determines whether an alarm should be initiated. Can be operated as a
single detector using smoke or heat to initiate an alarm or as a split
sensor with heat and smoke initiating separate signals.
LED indicator. The LED indicator (see Figure 1 below) displays the
following states:
•Normal: Green LED indicator flashes, no action.
•Alarm/active: Red LED indicator flashes, evacuate the area.
Figure 1: SIGA-PHD(B) features
2
1. Self-locking tab
2. LED indicator
Installation
Notes
•This detector does not operate without electrical power. As fires
frequently cause power interruption, discuss further safeguards
with the local fire protection specialist.
•This detector does not sense fires in areas where smoke or heat
cannot reach the detector. Smoke or heat from fires in walls, roofs,
or on the opposite side of closed doors may not reach the detector.
•Photoelectric detectors have a wide range of sensing capabilities,
and are best suited for detecting slow, smoldering fires. The heat
sensor in this device provides a source of supplemental
information. The heat sensor by itself does not provide life safety
protection.
•To ensure proper operation, store the detector within the
recommended ranges. Allow the detector to stabilize to room
temperature before applying power.
•The dust cover (supplied) must remain on the detector during
installation and be removed prior to commissioning and service.
The dust cover is not a substitute for removing the detector during
new construction or heavy remodeling.
•Do not use smoke detectors with detector guards unless the
combination has been evaluated and found suitable.
•In Canada, install according to the CAN/ULC-S524 Standard for
the Installation of Fire Alarm Systems, the CSA C22.1 Canadian
Electrical Code, and the local authority having jurisdiction.
•Upon completion of the original installation and following any
modifications or additions to the system, perform a calibrated
sensitivity test per NFPA code. Signature Series devices can
perform this test and the panel can generate a system sensitivity
report.
To install the detector:
1. Install and wire the base, as described on the installation sheet
supplied with the base.
2. Remove the serial number label from the detector and attach it to
the project documentation.
3. Attach the detector to the base by rotating the detector clockwise
until it snaps into the locked position.
Testing
Before testing, notify the proper authorities that the fire alarm system is
undergoing maintenance and will be temporarily out of service.
Test each sensor in the detector.
Caution: Heat damage. Excessive heat may damage the detector
outer cover. Do not apply excessive heat when using a hair dryer.
When using a Testifire detector tester, you must install a SIGA Testifire
Adapter Assembly.
Make sure the SIGA Testifire Adapter Assembly (model
SIGA-TSTSPACER) is installed in the Testifire detector tester before
testing. Refer to the SIGA Testifire Adapter Assembly Installation
Sheet (P/N 3101942-ML) for further details.
To perform an initial installation test:
1. Remove the detector from its base and verify that the proper
detector address, trouble signals, and messages are reported.
2. For SIGA-PHD(B) detectors placed in the air ducts, verify that the
airflow is within specifications. See “Specifications” on page 2.
2 / 2 P/N 3102363-EN • REV 004 • ISS 16FEB18
3. If wired for Class A operation, verify that the detector continues to
operate first with SLC_IN disconnected, and then with SLC_OUT
disconnected. (Refer to the installation sheet for the base.)
4. Place a momentary ground fault on the SLC circuit to verify
operation of the ground fault detection circuitry.
5. Run a system detector sensitivity report on all detectors and verify
that readings fall within acceptable limits.
6. Perform a sensor function test, as described below.
To perform sensor function tests:
1. If desired, use the fire alarm control panel to put the detector or
zone into a service group for testing. (Refer to the panel technical
reference manual for instructions.)
2. Activate the smoke sensor using No Climb Products model Smoke
Centurion/M8, FireTech Smoke or Smoke Sabre smoke aerosol
spray, a smoke generator, or the Testifire detector tester per the
manufacturer’s instructions.
3. Activate the heat sensor using a hair dryer (maintaining a distance
of three inches) or using a Testifire detector tester per the
manufacturer’s instructions.
Maintenance
To ensure proper operation, plan maintenance (regular or selected) of
the detector in accordance with the AHJ and all applicable governing
laws, codes, or standards. Refer to CAN/ULC-S536 Standard for the
Inspection and Testing of Fire Alarm Systems and NFPA 72 National
Fire Alarm and Signaling Code.
Refer to Technical Bulletin P/N 3102403-EN for additional information
and cleaning instructions.
Specifications
Operating voltage
15.20 to 19.95 VDC
Current
Normal operating current
Alarm
51 µA
68 µA
Vibration level
10 to 35 Hz, with an amplitude of
0.01 in.
Rate-of-rise
15°F/min (8°C/min)
Air velocity [1]
0 to 4,000 ft./min (0 to 20.32 m/s)
Maximum spacing
for Heat Detectors [3]
50 ft. (15.2 m) centers
Wall mount distance from
ceiling
12 in. (305 mm) max.
Compatible bases
Standard
Relay
Isolator
Audible
SIGA-SB, SIGA-SB4
SIGA-RB, SIGA-RB4
SIGA-IB, SIGA-IB4
SIGA-AB4G, SIGA-AB4GT,
SIGA-AB4G-LF
Compatible detector testers [2]
Testifire 1000, Testifire 2000
Operating environment
Temperature
Relative humidity
32 to 100°F (0 to 38°C)
0 to 93% noncondensing
Storage temperature
−4 to 140°F (−20 to 60°C)
Environmental compensation
Automatic
[1] For duct installation, use a SIGA-DMP duct detector mounting plate
and install per P/N 387053P-EN.
[2] Requires the SIGA-TSTSPACER Testifire adapter assembly.
[3] When replacing SIGA-HRS and SIGA-HFS detectors with the
SIGA-PHD(B), ensure that the spacing is 50 ft. (15.2 m) or less.
Regulatory information
North American
standards
CAN/ULC-S529, CAN/ULC-S530, UL 268,
UL 268A, UL 521
UL/ULC smoke
sensitivity range
0.53 to 3.94 %/ft. (1.7 to 12.35 %/m) obscuration
UL/ULC fixed-
temperature alarm
rating
135°F (57.2°C)
UL/ULC Actual
alarm point
129 to 141°F (53.9 to 60.6°C)
Response time
index
Quick(evaluated by FM Approvals)
FCC compliance
This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any
interference received, including interference that
may cause undesired operation.
Industry Canada
compliance
This Class A digital apparatus complies with
Canadian ICES-003.
Contact information
For contact information, see www.edwardsfiresafety.com

Other Edwards Security Sensor manuals

Edwards AB4G Assembly instructions

Edwards

Edwards AB4G Assembly instructions

Edwards 517FH Series User manual

Edwards

Edwards 517FH Series User manual

Edwards SIGA-HRD Assembly instructions

Edwards

Edwards SIGA-HRD Assembly instructions

Edwards SIGA2-HRS Owner's manual

Edwards

Edwards SIGA2-HRS Owner's manual

Edwards GasCheck G3 Magshield Installation and operating instructions

Edwards

Edwards GasCheck G3 Magshield Installation and operating instructions

Edwards ELD500 Series User manual

Edwards

Edwards ELD500 Series User manual

Edwards Signature Series Assembly instructions

Edwards

Edwards Signature Series Assembly instructions

Edwards SIGA-IM Assembly instructions

Edwards

Edwards SIGA-IM Assembly instructions

Edwards SIGA-HRD Assembly instructions

Edwards

Edwards SIGA-HRD Assembly instructions

Popular Security Sensor manuals by other brands

CoCo AMST-606 user manual

CoCo

CoCo AMST-606 user manual

Centsys FLUX SA installation manual

Centsys

Centsys FLUX SA installation manual

STI F3SJ-AM P Series user manual

STI

STI F3SJ-AM P Series user manual

Baumer URAM 50P7121 quick start guide

Baumer

Baumer URAM 50P7121 quick start guide

Antec Scientific DECADE II SDC 174 user manual

Antec Scientific

Antec Scientific DECADE II SDC 174 user manual

Elko inels RFWD-100 quick start guide

Elko

Elko inels RFWD-100 quick start guide

König SAS-DVRPIR10 manual

König

König SAS-DVRPIR10 manual

Jung FMDW360WW operating instructions

Jung

Jung FMDW360WW operating instructions

SKF Lincoln 254-15165-9 Service manual

SKF

SKF Lincoln 254-15165-9 Service manual

Aeon Labs AEO MULTISENS quick start

Aeon Labs

Aeon Labs AEO MULTISENS quick start

Linxon LX218 operating manual

Linxon

Linxon LX218 operating manual

LEGRAND 675 29 quick start guide

LEGRAND

LEGRAND 675 29 quick start guide

Danfoss MCB 152 operating instructions

Danfoss

Danfoss MCB 152 operating instructions

Lince 1630DT/JOLLY Installation, Programming and Operating Instructions

Lince

Lince 1630DT/JOLLY Installation, Programming and Operating Instructions

Atom AT4100MW instruction manual

Atom

Atom AT4100MW instruction manual

Global Fire ZEOS-AD-S instructions

Global Fire

Global Fire ZEOS-AD-S instructions

Carena TORSHAMN manual

Carena

Carena TORSHAMN manual

Risco ShockTec 601SM installation instructions

Risco

Risco ShockTec 601SM installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.