
4 / 6 P/N 3100672-EN • REV 07 • ISS 23JAN14
Regulatory information
Manufacturer Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA
Authorized EU manufacturing representative:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands
Year of
manufacture
The first two digits of the product serial number
(located on the product identification label) are
the year of manufacture.
EN 54 EN 54-18: 2005
CPR [1] 0832-CPR-F0326
UL ratings Regulated 24 DC, Regulated 24 FWR
ULC ratings 20 to 31 VDC or 20 to 31 VFWR
North American
standards
Meets: UL 268, UL 464, CAN/ULC-S525, and
CAN/ULC-S529
Follow: CSA C22.1 and CAN/ULC-S524
This device is prohibited from being installed in a
dwelling unit as defined in the National Building
Code of Canada.
[1] GSA series not CPR approved
Contact information
For contact information, see www.edwardsutcfs.com.
Applications
This section describes applications typically found in the North
American marketplace that apply to the AB4G and Signature
audible bases. For additional examples, see the applicable
control panel application manual.
Local alarm signaling application
Figure 4 shows the components and wiring required for a local
alarm signaling application.
All other audible detector bases on the same riser remain silent
until their detectors are activated. The audible detector base
remains audible until the smoke clears and the control panel is
reset.
Zone alarm signaling application
Figure 5 shows the components and wiring required for a zone
alarm signaling application.
In this application, use a CRR module to activate all the
audible detector bases in the same notification zone when any
one of their detectors activates (initiates an alarm event). The
audible detector base remains audible until:
• Smoke is cleared from the active detectors and the control
panel is reset.
• The control panel’s Auto Signal Silence timer expires.
• It is silenced by the CRR that is programmed as a
silencing relay. (This function of the CRR is panel
dependent.)
For more information about the Auto Signal Silence timer
function, and if the CRR can be programmed to silence the
panel, see the applicalbe control panel manual.
Synchronized alarm signaling application
Figure 6 shows the components and wiring required for a
synchronized alarm signaling application.
In this application, use a CRR module to activate all audible
detector bases when any alarm signal-initiating device
activates. Use a G1M-RM to synchronize the sound. The
audible detector base remains audible until:
• Smoke is cleared from the active detectors and the control
panel is reset.
• The control panel’s Auto Signal Silence timer expires.
• It is silenced by the CRR that is programmed as a
silencing relay. (This function of the CRR is panel
dependent.)
For more information about the Auto Signal Silence timer
function, and if the CRR can be programmed to silence the
panel, see the applicalbe control panel manual.